BLAUBERG Komfort EC D5B180 S14 Installation Manual Download Page 5

The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C! If the expected ambient
air temperatures are below 0 °C, the condensate drainage system must be equipped with heat insulation and pre-heating facilities.
Condensate drainage is not required for the Komfort EC D5B180-E modification. 

CONNECTION TO POWER MAINS

The air-handling unit is rated for connection to single-phase AC 120V/60 Hz power mains.  The unit must be connected to power mains using 
durable, insulated and heat-resistant conductors (cables and wires) with minimum cross section not less than 20 AWG.
The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event 
of overload or short-circuit.  The position of the external automatic circuit breaker must ensure free access for quick power-off of the unit.  The 
circuit breaker trip current must correspond to the unit current consumption, refer to the Technical data section.
Connect the cables to the control unit using the electric lead-ins on the side of the unit. 
Make the electric connections through the terminal block, located in the control unit, in compliance with the External wiring diagram.

Access to the control unit 

External control units wiring diagram

2

3

4

14

13

12

11

10

9

8

7

6

5

15

L

1

External device 
NO (CO

2

 sensor)

PK fire alarm panel

(remove the jumper while 

connecting the contact)

120 V/ 60 Hz 

Control panel

- Tx Rx +

GND Tx

Rx +U

3

2

1

GND

+U

0-10V

GND

+U 0-10V

N

PE

РК

C

X1

16

SM-L

17

SM-N

Humidity 

sensor 

W

hit

e

Bro

wn

Gr

een

Yello

w

XP

QF

Electric actuators

 of the external air dampers

SM1

supply

L1      N

SM2

exhaust

L1      N

Designation

Name

Model

Wire**

N.o

External control unit contacts

LF230

2 x 20 AWG

SМ1*

Supply air damper actuator

LF230

2 x 20 AWG

SМ2 *

Exhaust air damper actuator

LF230

2 x 20 AWG

РК*

Contact from fire alarm panel

NO

2 x 20 AWG

* Is not included in the delivery set.
** Maximum connecting cable length is 65 ft!

www.blauberg.us

MUI_82_Komfot_(EC)_D5B180_EN-01

174 N. 36th Street, Lafayette, IN 47905
e-mail: [email protected]

5

Summary of Contents for Komfort EC D5B180 S14

Page 1: ...too short or not connected protect the unit parts from ingress of foreign objects To prevent uncontrollable access to the fans the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 1 2 inch While installing the unit ensure convenient access for subsequent maintenance and repair The unit must be mounted on a plane wall ceiling Mounting of the u...

Page 2: ... by the Customer Service technician Unscrew the thumbscrews on the unit before attaching it to the mounting brackets Set the unit thumbscrews into the mating cutouts in the mounting brackets and tighten the thumbscrews Unit mounting example EXTRACT AIR SUPPLY AIR INTAKE AIR EXHAUST AIR Drainage hole EXTRACT AIR SUPPLY AIR Drainage hole Diagram 1 Wall vertical installation Diagram 2 Wall horizontal...

Page 3: ...ain pipes is in the cover of the unit Remove the plug from the hole open the service panel and install the drain pipe from the delivery set into the hole The drain pipes should be installed only in the holes indicated on the diagrams For suspended and wall mounted horizontal installation use two holes on the side of the unit for a wall mounted vertical installation use a hole at the bottom of the ...

Page 4: ...g to the Diagram 1 Then connect the drain pipe to the sewage system using the SG 32 U trap kit available upon separate order The pipes are required to have a minimum slope of 3 Each drain pipe is connected to a different U trap min 3 Drain hose U trap Sewage system Drain pipe www blauberg us MUI_82_Komfot_ EC _D5B180_EN 01 174 N 36th Street Lafayette IN 47905 e mail info blauberg us 4 ...

Page 5: ...nd to the unit current consumption refer to the Technical data section Connect the cables to the control unit using the electric lead ins on the side of the unit Make the electric connections through the terminal block located in the control unit in compliance with the External wiring diagram Access to the control unit External control units wiring diagram 2 3 4 14 13 12 11 10 9 8 7 6 5 15 L 1 Ext...

Reviews: