Komfort EC d5B180(-E) S14
12
www.blauberg.us
CONNECTION TO POWER MAINS
The air-handling unit is rated for connection to single-phase AC 120V/60 Hz power mains. The unit must be connected to power mains
using durable, insulated and heat-resistant conductors (cables and wires) with minimum cross section not less than 20 AWG.
The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the
event of overload or short-circuit. The position of the external automatic circuit breaker must ensure free access for quick power-off of
the unit. The circuit breaker trip current must correspond to the unit current consumption, refer to the Technical data section.
Connect the cables to the control unit using the electric lead-ins on the side of the unit.
Make the electric connections through the terminal block, located in the control unit, in compliance with the External wiring diagram.
Access to the control unit
External control units wiring diagram
2
3
4
14
13
12
11
10
9
8
7
6
5
15
L
1
External device
NO (CO
2
sensor)
PK fire alarm panel
(remove the jumper while
connecting the contact)
120 V/ 60 Hz
Control panel
- Tx Rx +
GND Tx
Rx +U
3
2
1
GND
+U
0-10V
GND
+U 0-10V
NО
N
PE
PК
РК
C
X1
16
SM-L
17
SM-N
Humidity
sensor
W
hit
e
Bro
wn
Gr
een
Yello
w
XP
QF
Electric actuators
of the external air dampers
SM1
supply
L1 N
SM2
exhaust
L1 N
Designation
Name
Model
Wire**
N.o
External control unit contacts
LF230
2 x 20 AWG
SМ1*
Supply air damper actuator
LF230
2 x 20 AWG
SМ2 *
Exhaust air damper actuator
LF230
2 x 20 AWG
РК*
Contact from fire alarm panel
NO
2 x 20 AWG
* Is not included in the delivery set.
** Maximum connecting cable length is 65 ft!
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS.
THE UNIT MUST BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE SHOWN ON THE RATING
PLATE.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID
THE WARRANTY.