The drain pan in the heat recovery section is equipped with a drain pipe for condensate removal.
Connect the pipe, the U-trap or U-trap of the other type (hydraulic lock) that is not included in the delivery set and a sewage system with
metal, plastic or rubber connecting hoses. While laying the connection pipes provide the slope of minimum 3° downwards.
Before starting operation of the unit make sure that the water flows freely into the sewage collection system, otherwise condensed water
may build up in the unit during the heat exchanger operation which, in turn, may cause equipment failure and water ingress into the
premises. Fill up the U-trap with water before using it. When using other U-trap systems read the installation instruction to prepare the
condensate drain system for operation.
For the units with a drain pump make sure that the flexible hose from the pump must is connected to the sewage system.
The drain pump provides timely pumping of the condensed water from the unit.
to sewage system
THE CONDENSATE DRAIN SYSTEM IS DESIGNED FOR USE IN PREMISES WITH AMBIENT
TEMPERATURE ABOVE 0 °C!
IF THE EXPECTED AIR TEMPERATURES ARE BELOW 0 °C, THE CONDENSATE DRAINAGE
SYSTEM MUST BE EQUIPPED WITH HEAT INSULATION AND PREHEATING FACILITIES.
www.blaubergventilatoren.de
civic ec lB(e)(2) 300/500(-e)