UNIT INSTALLATION

To get the best performance of the unit and to minimize turbulence-induced air pressure losses, connect the straight air duct section to 
the spigots on both sides of the unit while installing.
Minimum straight air duct length:
•  equal to 1 air duct diameter on the intake side
•  equal to 3 air duct diameter on the outlet side
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects. To prevent uncontrollable access to 
the fans, the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 12.5 mm.
When selecting the unit mounting position, enable free excess to the service panel for maintenance and service operations.
The unit should be mounted strictly horizontally in the longitudinal and transverse planes.  In case of non-compliance, unit’s casing 
distortion and operation disturbance will occur.

Unit wall mounting

Unit floor mounting

Fasteners for wall mounting are not included in the delivery set 
and should be ordered separately.
While choosing fasteners consider the material of the mounting 
surface as well as the weigh of the unit, refer to the “Technical data” 
section.  Fasteners for unit mounting should be selected by the 
installation specialist.
Install the fasteners in the wall.  Suspend the unit on fasteners. 
Achieve a strictly vertical position of the unit by rotating the 
adjustable stop (1). 

1

Install the unit on the pre-mounted floor supports, minimum 150 
mm height, to ensure sufficient access for the drain pipe connection 
to the U-trap and for condensate drain system installation.

min 150 mm

CONDENSATE DRAINAGE

Condensate drainage is required for the KOMFORT EC S(1)(B)160/350/550 unit series.
The hole for the drain pipe is at the bottom of the unit. Remove the plug from the hole. Open the service panel and remove the plug 
in the drain pan. Install the drain pipe from the delivery set into the hole, then connect the drain pipe to the sewage system using the  
SFK 20x32 U-trap kit (available upon separate order).  Make sure the U-trap is always filled with water. The pipe slope downwards must 
be at least 3°.

1

2

3

4

min 3°

1 – drain pipe; 2 – U-trap; 3 – drain hose; 4 – sewage system

www.blaubergventilatoren.de

KOMFOrt EC S(1)(B)160/350/550(-E) 

10

Summary of Contents for 4058448021695

Page 1: ...C S160 KOMFORT EC S160 E KOMFORT EC S1 160 KOMFORT EC S1 160 E KOMFORT EC SB160 KOMFORT EC S1B160 KOMFORT EC SB160 E KOMFORT EC S1B160 E KOMFORT EC SB350 KOMFORT EC S1B350 KOMFORT EC SB350 E KOMFORT EC S1B350 E KOMFORT EC SB550 KOMFORT EC SB550 E ...

Page 2: ...sportation regulations 17 Manufacturer s warranty 18 Certificate of acceptance 19 Seller information 19 Installation certificate 19 Warranty card 19 SAFETY REQUIREMENTS All user s manual requirements as well as the provisions of all the applicable local and national construction electrical and technical norms and standards must be observed when installing and operating the unit Disconnect the unit...

Page 3: ... efficient air flow Do not sit on the unit and do not put objects on it The unit is allowed to be used by children aged from 8 years old and above and persons with reduced physical sensory or mental capabilities or no experience and knowledge provided that they have been given supervision or instruction regarding safe use of the unit and understand the risks involved Do not allow children to play ...

Page 4: ... It is rated for continuous operation Transported air must not contain any flammable or explosive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogenic germs THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SE...

Page 5: ...er type Counter flow Heat exchanger material Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane Polystyrene Enthalpy membrane SEC class A A A A A A A A A A A A A A The KOMFORT EC S 1 B 160 350 550 E units are equipped with an enthalpy heat exchanger and do not require co...

Page 6: ... 370 690 590 640 388 143 KOMFORT EC SB160 E 125 18 340 330 665 580 600 388 143 KOMFORT EC S1B160 E 125 18 380 370 710 620 640 388 143 KOMFORT EC SB350 E 160 18 600 583 760 675 730 426 230 KOMFORT EC S1B350 E 160 18 480 470 760 675 730 426 200 KOMFORT EC SB550 E 200 18 730 720 760 675 823 498 288 www blaubergventilatoren de KOMFORT EC S 1 B 160 350 550 E 6 ...

Page 7: ... through the inlet and outlet spigots Thedifferencebetweenthesupplyandextractairflowtemperatureleadstocondensategenerationinthe KOMFORTECS 1 B 160 350 550 units Condensate is collected in the drain pan and is removed outside through the drain pipe The KOMFORT EC S 1 B 160 350 550 E units are equipped with a heat exchanger with an enthalpy membrane and do not require condensate drainage Accessories...

Page 8: ...th the heat exchanger The temperature of the air is not changed after passing through the heat exchanger INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Back side view Heat exchanger freeze protection frost danger appears when the extract air temperature downstream of the heat exchanger is lower than 5 C and intake air temperature upstream of the heat exchanger is lower than 3 C for units with prehe...

Page 9: ...TAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Left hand service side INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Right hand service side Release the latches disconnect the ground cable and remove the service panel Remove the latches and move them to the opposite side Remove the back panel by undoing the three screws hidden under plastic plugs Install the back panel www blaubergventilatoren de KOMF...

Page 10: ...ordered separately While choosing fasteners consider the material of the mounting surface as well as the weigh of the unit refer to the Technical data section Fasteners for unit mounting should be selected by the installation specialist Install the fasteners in the wall Suspend the unit on fasteners Achieve a strictly vertical position of the unit by rotating the adjustable stop 1 1 Install the un...

Page 11: ...al wire cross section selection must be based on the maximum load current maximum conductor temperature depending on the wire type insulation length and installation method The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short circuit The circuit breaker installation place must provide ...

Page 12: ...D X1 L SQ PE N NO NO A B NC C C C NO C NO C 24V 24V L 2 N 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 10V GND А В 24V 1 2 PK1 1 2 1 2 P1 1 2 1 2 1 2 CCU Boost 1 2 SM1 1 2 SM2 U U CO2 GND 0 10V 24V Brown Yellow Green White Power input 230 VAC Designation Name Model Wire Note SM1 Supply air damper actuator NO 2 x 0 75 mm2 3A 30DC 250 AC SM2 Extract air damper actuator NO 2 x 0 75 mm2 3A 30DC...

Page 13: ...SM2 Extract air damper actuator NO 2 x 0 75 mm2 3A 30VDC 250 AC РК1 Contact from fire alarm panel NC 2 x 0 75 mm2 CCU CCU control NO 2 x 0 75 mm2 3A 30VDC 250 AC P1 External control panel 4 x 0 25 mm2 Boost On Off contacts for the Boost mode NO 2 x 0 75 mm2 CO2 External CO2 sensor NO 3 x 0 75 mm2 Is not included in the delivery set The U supply voltage of the SM1 SM2 external dampers is selected d...

Page 14: ... re install the heat exchanger into the unit 3 Fan maintenance once per year Even in case of regular maintenance of the filters some dust may accumulate inside the fans and reduce the fan performance and supply air flow Fans should be cleaned by the service technician 4 Condensate drainage system maintenance 4 times per year The condensate drainage drain line may get clogged by dirt and dust parti...

Page 15: ...r duct pipe flanges Install anti vibration connectors Water leakage only for the KOMFORT EC S 1 B 160 350 550 units The drainage system is soiled damaged or installed incorrectly Clean the drain line Check the drain line slope angle Make sure that the U trap is filled with water and the drain pipes are frost protected If troubleshooting steps have failed contact the Seller of the product In case o...

Page 16: ...ir the user must provide the unit the user s manual with the purchase date stamp and the payment paperwork certifying the purchase The unit model must comply with the one stated in the user s manual Contact the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manu...

Page 17: ...www blaubergventilatoren de KOMFORT EC S 1 B 160 350 550 E 17 ...

Page 18: ...www blaubergventilatoren de KOMFORT EC S 1 B 160 350 550 E 18 ...

Page 19: ...is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards The unit operates normally as intended by th...

Page 20: ...www blaubergventilatoren de B203EN 03 ...

Reviews: