TECHNICAL MAINTENANCE

BEFORE MOUNTING MAKE SURE THE CASING DOES NOT CONTAIN ANY FOREIGN 

OBJECTS (E.G. FOIL, PAPER).

The unit must undergo technical maintenance 3 to 4 times a year. Maintenance includes general cleaning of the unit and the following 
operations:

1. Filter maintenance (3-4 times per year).

Clogged filters increase air resistance in the system and reduce supply air volume. Clean the filters as required, but not less than 3-4 times 
per year. Clean the filter with a vacuum cleaner or replace with a new filter. For new filters, contact the Seller.

2. Heat exchanger maintenance (once a year).

Some dust may accumulate on the heat exchanger even in case of regular maintenance of the filters.  To maintain the high heat recovery 
efficiency, regular cleaning is required. To clean the heat exchanger pull it out of the air handling unit, clean it with compressed air or a 
vacuum cleaner. After that install the heat exchanger back into the unit.  To remove the filters and the heat exchanger, follow the steps 
as shown on the right. 

3. Fan maintenance (once a year). 

Even in case of regular maintenance of the filters and the heat exchanger, some dust may 
accumulate inside the fans and reduce the fan performance and supply air flow volume. 
To clean the fan use a soft cloth, brush or compressed air.
Do not use water, aggressive solvents or sharp objects as they may damage the impeller.

4. Technical maintenance of the condensate drainage system (four times a year).

The condensate drainage (drain line) may get clogged by particles contained in the 
exhaust air. Pour some water inside the drain pan to check the pipe for clogging. Clean 
the U-trap and the drain pipe if required.

5. Technical maintenance of air intake devices (twice per year).

The supply duct grille may get clogged with leaves and other objects reducing the unit performance and supply air delivery. Check the 
supply grille twice per year and clean it as required.

6. Technical maintenance of air duct system (every 5 years).

Even regular fulfilling of all the stated above maintenance operations described above may not completely prevent dirt accumulation in 
the air ducts which reduces the unit capacity.  Duct maintenance consists in regular cleaning or replacement.

7. Control unit maintenance (if necessary).

The control unit is positioned inside the unit casing. To access the control unit, remove the fixing screws on the panel and remove the 
control unit lid.
Access to the control unit:

1

2

3

www.blaubergventilatoren.de

KOMFOrt EC S(1/2)(B)(-E) 

17

Summary of Contents for 4058448021602

Page 1: ...160 KOMFORT EC SB160 E KOMFORT EC S1 160 KOMFORT EC S1 160 E KOMFORT EC S1B160 KOMFORT EC S1B160 E KOMFORT EC S2B300 KOMFORT EC S2B300 E KOMFORT EC SB350 KOMFORT EC SB350 E KOMFORT EC S1B350 KOMFORT EC S1B350 E KOMFORT EC SB550 KOMFORT EC SB550 E KOMFORT EC S2B550 KOMFORT EC S2B550 E ...

Page 2: ...d transportation regulations 19 Acceptance certificate 23 Seller information 23 Installation certificate 23 Warranty card 23 SAFETY REQUIREMENTS All user s manual requirements as well as the provisions of all the applicable local and national construction electrical and technical norms and standards must be observed when installing and operating the unit Disconnect the unit from power supply prior...

Page 3: ...e the efficient air flow Do not sit on the unit and do not put objects on it The unit is allowed to be used by children aged from 8 years old and above and persons with reduced physical sensory or mental capabilities or no experience and knowledge provided that they have been given supervision or instruction regarding safe use of the unit and understand the risks involved Do not allow children to ...

Page 4: ... and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogenic germs THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UN...

Page 5: ...S160 E KOMFORT EC SB160 KOMFORT EC SB160 E KOMFORT EC S1 160 KOMFORT EC S1 160 E KOMFORT EC S1B160 KOMFORT EC S1B160 E Power supply voltage V 50 60 Hz 1 230 Maximum unit power W 51 Maximum unit current A 0 4 Maximum air capacity m3 h 180 RPM 3770 Sound pressure level at 3 m distance dBA 24 22 Transported air temperature С 25 40 Casing material painted steel Insulation mineral wool 20 mm 40 mm Extr...

Page 6: ... 1 230 Maximum unit power W 170 170 147 370 333 Maximum unit current A 1 30 1 30 1 2 2 5 2 3 Maximum air capacity m3 h 330 380 380 625 750 RPM 3200 3230 Sound pressure level at 3 m distance dBA 30 28 30 26 Transported air temperature С 25 40 Casing material painted steel Insulation mineral wool 20 mm 40 mm 20 mm 40 mm Extract filter filtration class G4 G4 Intake filter filtration class F7 G4 optio...

Page 7: ...rough the inspection door on top of the unit For accessing the control unit remove the service panel after mounting and wiring operations The control unit is accessible for service operations through the hinged mounting plate The power cable and ground cable are connected to the control unit via the cable glands The bypass damper is open or closed depending on operation mode of the unit The temper...

Page 8: ...ns constant after passing the heat exchanger INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Back side view Heat Exchanger Freeze Protection The unit has two automatic heat exchanger freeze protection modes depending on the unit model In case of a freezing danger the supply fan is turned off To activate the Freeze Protection mode refer to the user s manual for the control panel the Engineering menu ...

Page 9: ...ty sensor connector to the respective connector on the control unit refer to the External wiring diagram Exhaust air duct Contact socket for connection to the control unit Humidity sensor Contact socket for connection to the humidity sensor Mount Reheating The process of supply air reheating by the EVH duct heater is described in the user s manual for the control panel For details refer to the Eng...

Page 10: ...le from the control unit is pre wired at the factory Extract air duct Connector for connection to the control unit Humidity sensor Mount 1 2 3 1 2 3 Connector for connection to the humidity sensor Indoor mounting of the FS2 sensor The FS2 sensor must be mounted in a room where the unit will maintain the set humidity level The sensor is fixed on the wall or ceiling surface using a screw or a double...

Page 11: ... access for maintenance and servicing INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR Left handed modification INTAKE AIR EXHAUST AIR SUPPLY AIR EXTRACT AIR Right handed modification Service side change before unit mounting www blaubergventilatoren de KOMFORT EC S 1 2 B E 11 ...

Page 12: ...r subsequent maintenance and repair The unit must be mounted on a plane wall Mounting of the unit to an uneven surface can lead to the unit casing distortion and operation disturbance Unit wall mounting Unit floor mounting Fasteners for wall mounting are not included in delivery and must be ordered separately While choosing fasteners consider the material of the mounting surface as well as the wei...

Page 13: ... plug from the hole open the service panel and install the supplied drain pipe into the hole then connect the drain pipe to the sewage system using the SFK 20x32 U trap kit available upon separate order While laying the hoses provide the slope downwards min 3 min 3 Drain hose U trap Sewage system Drain pipe www blaubergventilatoren de KOMFORT EC S 1 2 B E 13 ...

Page 14: ...or Is not included in the delivery set Maximum connecting cable length is 20 m The unit is rated for connection to 1 230 V 50 60 Hz power mains The unit must be connected to power mains using insulated electric conductors cables wires The actual wire cross section selection must be based on the maximum load current maximum conductor temperature depending on the wire type insulation length and inst...

Page 15: ...larm panel NС 2 x 0 75 mm2 Р1 Control panel Is not included in the delivery set Maximum connecting cable length is 20 m Power input 230 V ELECTRIC SHOCK HAZARD Remove the jumper White Brown Green Yellow SM2 L N SM1 FS1 L 1 2 1 2 N 1 2 PK1 1 2 CO2 S2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 L N C PE NO PK Tx Rx PK U U U 0 10V 0 10V SM L SM N GND GND GND Tx Rx U GND 1 2 3 Power input 230 V...

Page 16: ...er input 230 V ELECTRIC SHOCK HAZARD Designation Name Type Wire CCU DX cooler N0 2 x 0 75 mm2 SМ1 Supply air damper actuator LF230 2 x 0 75 mm2 SМ2 Extract air damper actuator LF230 2 x 0 75 mm2 РК1 Contact of fire alarm panel N0 2 x 0 75 mm2 Р1 Control panel ТЕ1 Outdoor temperature sensor КН Kitchen hood contact N0 2 x 0 5 mm2 Is not included in the delivery set Maximum connecting cable length is...

Page 17: ...accumulate inside the fans and reduce the fan performance and supply air flow volume To clean the fan use a soft cloth brush or compressed air Do not use water aggressive solvents or sharp objects as they may damage the impeller 4 Technical maintenance of the condensate drainage system four times a year The condensate drainage drain line may get clogged by particles contained in the exhaust air Po...

Page 18: ...ctors Water leakage only for the KOMFORT EC S 1 2 B units The drainage system is clogged damaged or incorrect installed Clean the drain line Check the drain line slope angle Make sure that the U trap is filled with water and the drain pipes are frost protected The DI1 or DI3 errors are displayed on the control panel the errors are identical for both heaters Missing heater during activated heating ...

Page 19: ...anty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual User s failure to ...

Page 20: ...www blaubergventilatoren de KOMFORT EC S 1 2 B E 20 ...

Page 21: ...www blaubergventilatoren de KOMFORT EC S 1 2 B E 21 ...

Page 22: ...www blaubergventilatoren de KOMFORT EC S 1 2 B E 22 ...

Page 23: ...nit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards The unit operates normally as intended b...

Page 24: ...www blaubergventilatoren de B106 1EN 09 ...

Reviews: