KOMFORT EC LW

Table 10. Controller parameters (continued)

Function

Indication

5

Alarms

E1: 

outdoor air temperature sensor breakout or short circuit. The fans stop.

E2:

 exhaust air temperature sensor breakout or short circuit. The fans stop.

E3:

 return heat medium temperature sensor breakout or short circuit. The fans stop.

E4:

 breakout or short circuit of the temperature sensor for the water heater freezing protection. The fans stop.

E5

: breakout or short circuit of the supply air temperature sensor. The fans stop.

F1:

 heat exchanger freezing. The exhaust air temperature downstream of the heat exchanger measured by the 

TE2 

temperature sensor is below the 0 0C 

set point within the 10 min time period when the fans are turned on. The bypass damper is completely opened. The fans continue operating.

O1: 

emergency system shutdown on signal from the fire alarm panel. The fans stop.

O2: 

filter clogging. The fans stop.

P1: 

supply fan failure. The fans stop.

P2:

 exhaust fan failure. The fans stop.

U1:

 heater freezing danger. The alarm is generated if the air temperature downstream of the water heater falls down below +3 °C. 

U2:

 low return heat medium temperature. The alarm is generated if the return heat medium temperature falls down below the set critical point. In case of 

any of the above freezing dangers the fans stop, the heat medium regulating valve is completely opened and the circulating pump is starts. The fans may 

not be started in case of any of these freezing dangers. The system restart is possible only after removal of the water freezing danger, i.e. after removal of 

the 

U2

 alarm, i.e. after rising of the return heat medium temperature 

TE3

 or after removal of the 

U1

 alarm, after rising of the air temperature downstream 

of the heater above set point to prevent the water heater freezing.

U3:

 appears if return heat medium temperature at the end of the water heater warming-up cycle in Winter mode before the fans start does not exceed 

+40 °C (factory setting). The fan start is disabled in case of this alarm.

U4:

 pump failure. No signal from the fluid pressure switch in the water heater after the signal to activate the circulating pump. This alarm causes the 

hydronic coil heater pump shutdown. The fan operation status does not change. In case of the alarm the fans keep operating if they were turned on before 

the pump failure.

6

Settings

Password: 

password is part of Configuration Menu. 2222 by default. 

• 

The password consists of 4 digits and is displayed as ****. 

• 

Then use the 

 and 

 buttons to enter the first password digit and 

press Enter. Enter the second number with the buttons 

 and 

then press Enter etc. 

• 

Press Esc to get back to the previous digit. 

• 

Upon entering the 4th digit of the correct password the display shows 

the 

Settings menu

 automatically.

Help line

Help line

Online temp-res

Outside

temperature (TE1)

Temperature 

aft.exhc.(TE2)

Temperature 

of return

heat exch. (TE3)

Heater 

temperature (TE4)

Intake

temperature (TE5)

5.0 

0

C

5.0 

0

C

50.0 

0

C

50.0 

0

C

5.0 

0

C

Help line

SYSTEM STATUS 

Heater

Heat exch.

Pump

Cooler

Winter/Summer

0

100

Off

Off

Summer

Temp. setpoints

T.ret.w.heat.:

T.ret.w.min.:

T.seas.ch.

T.ret.w.spoint:

T.w.heat. min.:

T.h.exch.ch.:

T.h.exch.min.:

T.cool.min.: 

40 

0

C

0

C

0

C

20 

0

C

0

C

0

C

-5 

0

C

20 

0

C

Settings

-> Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Heater settings

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Cooler settings

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Pump settings

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Fan

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Heat exch.sett.

Cooler settings

Heater settings

Contol law

Protection

-> Control law

Control law

Protection

Supply air:

 G    2.00

 T     60

Dead zone:  0.5

Ret.w.t. control:

 G    2.00

 T     60

Dead zone:  0.5

Heating time:  

180 s

Heat exch.sett.

F1 Fault delay:    600

Supply air control law:

 G       1.00

 T         100

Dead zone:        0.5

Exhaust air control law :

 G       1.00

 T        100

Dead zone:        0.5

Cooler delay on:     600  s

Pump settings

Min.work.time:  

  20 s

Summer mode: 

   Enable

Fan

P1, P2 Fault delay:   30  s

VUT-...-WH

Password

Settings menu. 

This menu contains basic controller settings. 

Editing the Settings menu must be performed by professionals only, otherwise 

it may cause controller failure or breakdown.

Help line

Help line

Online temp-res

Outside

temperature (TE1)

Temperature 

aft.exhc.(TE2)

Temperature 

of return

heat exch. (TE3)

Heater 

temperature (TE4)

Intake

temperature (TE5)

5.0 

0

C

5.0 

0

C

50.0 

0

C

50.0 

0

C

5.0 

0

C

Help line

SYSTEM STATUS 

Heater

Heat exch.

Pump

Cooler

Winter/Summer

0

100

Off

Off

Summer

Temp. setpoints

T.ret.w.heat.:

T.ret.w.min.:

T.seas.ch.

T.ret.w.spoint:

T.w.heat. min.:

T.h.exch.ch.:

T.h.exch.min.:

T.cool.min.: 

40 

0

C

0

C

0

C

20 

0

C

0

C

0

C

-5 

0

C

20 

0

C

Settings

-> Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Heater settings

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Cooler settings

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Pump settings

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Fan

Settings

Heater

Cooler

Pump

Fan

Heat exchanger

-> Heat exch.sett.

Cooler settings

Heater settings

Contol law

Protection

-> Control law

Control law

Protection

Supply air:

 G    2.00

 T     60

Dead zone:  0.5

Ret.w.t. control:

 G    2.00

 T     60

Dead zone:  0.5

Heating time:  

180 s

Heat exch.sett.

F1 Fault delay:    600

Supply air control law:

 G       1.00

 T         100

Dead zone:        0.5

Exhaust air control law :

 G       1.00

 T        100

Dead zone:        0.5

Cooler delay on:     600  s

Pump settings

Min.work.time:  

  20 s

Summer mode: 

   Enable

Fan

P1, P2 Fault delay:   30  s

VUT-...-WH

Password

KOMFORT_EC_LW_v1(5)_EN.indd   18

07.09.2015   13:06:26

Summary of Contents for KOMFORT EC L1W300-2

Page 1: ...OPERATION MANUAL KOMFORT EC LW HEAT RECOVERY AIR HANDLING UNIT KOMFORT_EC_LW_v1 5 _EN indd 1 07 09 2015 13 06 19 ...

Page 2: ...4 Operation logic 5 Delivery set 5 Technical data 7 Mounting 9 Condensate drainage 10 Connection to power mains 11 Control panel mounting 13 Unit control 15 Control panel troubleshooting 15 Automatic control system 22 Technical maintenance 22 Troubleshooting 23 Acceptance certificate 23 Connection certificate 23 Warranty card KOMFORT_EC_LW_v1 5 _EN indd 2 07 09 2015 13 06 19 ...

Page 3: ...fe of the unit TRANSPORTATION AND STORAGE REGULATIONS Transportation of the unit is allowed by any vehicle provided the unit is transported in the original package and is protected against weather and mechanical damages Use hoist machinery for handling and transportation to prevent possible mechanical damages of the unit Fulfil the requirements for transportation of the specified cargo type during...

Page 4: ...ses by the heat exchanger is used for its defrosting After the freezing danger is over the bypass damper is closed and the intake air passes through the heat exchanger again The heat exchanger reverts to the regular operation mode The drain pan under the heat exchanger block is used for condensate collection and drainage The unit is equipped with a 2 row water glycol heater for operation at low ou...

Page 5: ...ature C from 25 up to 60 Casing material aluzinc Insulation 25 mm mineral wool Extract filter cassette G4 Intake filter cassette F7 Connected air duct diameter mm 150 160 315 Weight kg 40 Heat recovery efficiency up to 90 Heat exchanger type counter flow Heat exchanger material polystyrene Model Replaceable G4 cassette filter Replaceable F7 cassette filter KOMFORT EC LW300 2 FP EC LW300 550 G4 FP ...

Page 6: ...long the line down to the water flow axis at the bottom of the graphic 0 072 l s Water pressure drop Draw the line from the point where line crosses the black curve to the pressure drop axis 3 5 kPa Water heater parameters calculation example Supply air temperature Prolong the line of air flow e g 400 m3 h up to the point where it crosses the outside air temperature blue curve e g 20 C then draw a...

Page 7: ... connection to the drain system While planning the ductwork layout avoid too long air duct sections numerous bends and reducers because it may reduce air flow The mounted air ducts must not be deformed Provide airtight connection of the air ducts to the unit spigots and fittings Install straight air ducts on both sides of the unit to minimize aerodynamic resistance caused by air flow turbulence th...

Page 8: ...ater connection In order to achieve maximum power the water heater should be counter flow connected Fig 7 All calculation diagrams ref Fig 3 4 are valid for the counter flow connection of the water heater In case of the direct flow basis connection the water heater has lower power but higher frost resistant properties Counterflow connection Direct flow connection water inlet water return water inl...

Page 9: ...rds min 3 Fill the system with water prior to connecting it to power supply During operation the U trap must always be filled with water Provide free drainage for the condensed water otherwise it is accumulated inside the unit which may cause the equipment damage and condensate outflow to the room The condensate drainage system is designed for normal operation in premises with air temperatures abo...

Page 10: ...valid electric standards Follow the respective electric standards safety rules DIN VDE 0100 TAB der EVUs The house cabling system must be equipped with a magnetic trip automatic switch at the external input The contact gap on all poles must be at least 3 mm VDE 0700 T1 7 12 2 EN 60335 1 The automatic switch trip current must be not below the rated current consumption ref to Table 1 Enable quick ac...

Page 11: ... air temperature sensor Q1 Water heater TS1 Water heater freeze protection thermostat RK1 Plate heat exchanger Not included in the delivery set available as specially ordered accessories Fig 11 Functional diagram CONTROL PANEL MOUNTING The unit incorporates an integrated control system with the S13 wall mounted control panel with a sensor display Fig 12 The standard delivery set includes a 10 m ca...

Page 12: ...tangular control panel openings for 4 mm 2 Press the screwdriver to open the control panel 3 Route the required cables and wires and install a junction box included in the delivery set in the wall 4 Connect and place the executive element inside of the mounting box 5 Fix the back side of the control panel to the wall using screws 6 Connect the executive element to the front part of the control pan...

Page 13: ...ng Fan speed Auto High Medium Low In Auto mode the panel sets the fan s speed automatically depending on the actual and set temperature difference in the room AUTO Table 7 Unit control and operating parameter setting Fig 13 S13 control panel Button symbol Designation Power on off Operation mode control Speed selection Auto High Medium Low Temperature and operation mode setting buttons ROOM Fig 14 ...

Page 14: ...tion deactivation setting ref to Week timer setting AUTO 5 Selection of temperature control and setting mode Setting the week timer is as follows 5 1 Time setting Press and hold button on the display for 3 seconds to open the Settings mode Then select Minutes option using button and press to make appropriate adjustment Select Hours option using button and press to make appropriate adjustment 5 2 W...

Page 15: ... Fig 15 General functions of automatic control system ACS 1 Turning the unit on off 2 Keeping supply air temperature at set point 3 Control of the bypass damper actuator 4 Fan operation and control 5 Control of the air damper actuator 6 Control of the air damper actuator 7 System shutdown by the command from fire fighting system 8 Heater control Heater freezing and overheating control 9 Control of...

Page 16: ... C 5 0 C 20 0 C VUT WH Password 3 System status Heater heat medium regulating valve opening ratio Heat Exch heat exchanger activation ratio Pump circulating pump operating status Off circulating pump is not activated On circulating pump is activated Cooler cooler operating status Off cooler is not activated On cooler is activated Winter Summer system operation mode The automatic control system ope...

Page 17: ...ode the water heater freezing protection function is activated ref to Alarm list U2 T seas ch upper limit of the outdoor air temperature After reaching this limit the system changes into the Summer mode T ret w spoint minimum return heat medium temperature to maintain temperature mode when the fans are turned off The return heat medium temperature is automatically maintained at the set point in Wi...

Page 18: ...failure No signal from the fluid pressure switch in the water heater after the signal to activate the circulating pump This alarm causes the hydronic coil heater pump shutdown The fan operation status does not change In case of the alarm the fans keep operating if they were turned on before the pump failure 6 Settings Password password is part of Configuration Menu 2222 by default The password con...

Page 19: ...lve Dead zone dead zone C Parameters setting for the return heat medium temperature control by means of the regulating heat medium valve If the discrepancy is below the set point it is taken to be 0 Settings Settings Heater Cooler Pump Fan Heat exchanger Heater settings Settings Heater Cooler Pump Fan Heat exchanger Cooler settings Settings Heater Cooler Pump Fan Heat exchanger Cooler settings Hea...

Page 20: ...m regulating valve is operating Cooler Pump Fan Heat exchanger Cooler settings Settings Heater Cooler Pump Fan Heat exchanger Pump settings Settings Heater Cooler Pump Fan Heat exchanger Fan Settings Heater Cooler Pump Fan Heat exchanger Cooler settings Cooler delay on 600 s Pump settings Min work time 20 s Summer mode Enable Fan P1 P2 Fault delay 30 s 6 4 Fan settings Fan Fans settings menu Setti...

Page 21: ...g for supply air temperature control by means of the regulating heat medium valve Dead zone dead zone C Parameters setting for supply air temperature control by means of the regulating heat medium valve If the discrepancy is below this point it is taken to be 0 Exhaust air control law G proportional control factor of proportional integral control law sec Parameters setting for the return heat medi...

Page 22: ...vent dirt accumulation in the air ducts which reduces the unit capacity Duct maintenance means regular cleaning or replacement 7 Exhaust and intake diffusers maintenance if required Remove the exhaust and the intake diffusers and flush those with warm detergent solution Check the ductworks connections periodically WARNING Cut power supply to the unit off by turning the automatic electric switch QF...

Page 23: ... Member States relating to electromagnetic compatibility which relate to electrical appliances used in set voltage classes This certificate is issued following test carried out on samples of the product referred to above Quality Inspector s Stamp Manufacture Date ____________________ Company Expert s Full Name Date Signature Heat recovery air handling unit KOMFORT EC LW300 2 KOMFORT EC L1W300 2 KO...

Page 24: ...www blaubergventilatoren de KOMFORT_EC_LW_v 1 5 _EN KOMFORT_EC_LW_v1 5 _EN indd 24 07 09 2015 13 06 27 ...

Reviews: