www.blaubergventilatoren.de
Freshbox 100
11
CONNECTION TO POWER MAINS
CONNECTION OF ADDITIONAL EXTERNAL CONTROLS
• The unit is rated for connection to 1~230 V/50 (60) Hz power mains.
• The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section selection
must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and
installation method.
• The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric
circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown
of the unit. The trip current of the automatic circuit breaker
QF
must exceed the maximum current consumption of the unit (refer
to the technical data table). The recommended trip current of the circuit breaker is the next current in the standard trip current row
following the maximum current of the connected unit. The automatic circuit breaker is not included in the delivery set.
Wiring diagram of the additional controls in the control unit
A4*
1
L
2
N
3
PE
4
LA
5
PK
PK1* RH1*
6
PK
7
H
8
H
9
YN
10
YL
11
L1
12
N1
L N
13
PE1
PE
L N
PE
QF*
230 V AC
2 1
2 1
Connection of additional external control contacts
is implemented in the control unit. For accessing
the control unit open the unit door, release the
screws fixing the shielding and remove it.
Wiring diagram of the CO2 sensor inside the unit
CO2*
+24
V
GND
Co
m
NO
Br
own
Gr
een
Black
Whit
e
1
2
3
B1*
+
Gr
een
Black
Br
own
Whit
e
Connecting humidity sensor or CO2 sensor to the
control unit via a cable, which is attached to the
bracket.
Designation
Unit name
Note
RH1*
Connecting contact humidity or CO2 sensor in the control unit
B1*
or
CO2*
Connecting contact humidity or CO2 sensor via cable
A4*
Heating element for condensate heating
РК1*
Contact from fire alarm panel
Remove the jumper during installation
QF*
Automatic circuit breaker
*Additionally connected devices are purchased separately.
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER’S LABEL.