blaubergventilatoren.de
CiViC eC dB 1000
15
Install the Wi-Fi antenna.
CONDENSATE DRAINAGE ARRANGEMENT
The unit is equipped with a drain pump for timely removal of condensate from the unit.
Connect the flexible hose going from the pump outlet to the sewage system.
min 3°
U-trap (hydraulic lock)
Sewage system
min 50 mm
WARNING!
To ensure water drainage, pipes should be mounted with a slope of at least 3°.
Provide free drainage for the condensed water, otherwise it is accumulated inside the unit that may cause the equipment damage and
condensate outflow to the room.
The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C!
If the expected ambient air temperatures are below 0 °C, the condensate drainage system must be heat-insulated and equipped with
heating.