blaubergventilatoren.de
CiViC eC dB 1000
11
After moving the blocks to the installation site, connect the blocks 1, 2, 3.
Fasteners for unit mounting are not included in the delivery set and must be ordered separately.
While choosing fasteners consider the material of the mounting surface as well as the weigh of the unit, refer to the Technical data
section.
The selection of fasteners is carried out by a specialist of the installation organization.
The unit may be suspended on threaded rods or may be rigidly fixed to a horizontal surface by anchor bolts.
The unit is suspended using the supplied mounting bracket 6 and 2 L-brackets 5.
Two more brackets 7 can be mounted behind the unit, depending on the type of mounting.
min 1500 mm
min 1500 mm
min 1400 mm
To get the best performance of the unit and to minimize turbulence-induced air pressure losses, connect the straight air duct section to
both unit spigots. Minimum straight air duct length: equal to 1 air duct diameter on intake side, equal to 3 air duct diameters on outlet
side.
To protect the internal parts of the unit from ingress of foreign objects, it is necessary to install a grille or other protective device with
mesh width not more than 12.5 mm to prevent free access to the fans. The air ducts, protective grilles and devices are not included in the
delivery set and are available upon separate order.