background image

111-G00     Page 4/16 

INSTALLATION 

PUMP MOUNTING 

A solid foundation reduces noise and vibration, and will 
improve pump performance. On permanent installations it is 
recommended the pumping unit be secured by anchor bolts 
as shown in Figure 2. This arrangement allows for slight 
shifting of position to accommodate alignment with the 
mounting holes in the base plate. 

  

Figure 2 - Pipe Type Anchor Bolt Box 

 

For new foundations, it is suggested that the anchor bolts be 
set in concrete. When pumps are to be located on existing 
concrete floors, holes should be drilled into the concrete to 
hold the anchor bolts. 

 

When installing units built on channel or structural steel type 
bases, use care to avoid twisting the base out of shape when 
anchor bolts are tightened. Place shims as needed under the 
edges of the base prior to tightening of the anchor bolts to 
prevent distortion. 

 
 

COUPLING ALIGNMENT 

The pump must be directly coupled to a gear reducer and/or 
driver with a flexible coupling.

  Verify coupling alignment 

after installation of new or rebuilt pumps.

  Both angular 

and parallel coupling alignment MUST be maintained 
between the pump, gear, motor, etc. in accordance with 
manufacturer’s instructions.  See Figure 3. 

1.  Parallel alignment:  The use of a laser alignment tool or 

dial indicator is preferred.  If a laser alignment tool or dial 
indicator is not available, use a straight edge.  Turn both 
shafts by hand, checking the reading through one 
complete revolution.  Maximum offset should be less 
than .005" (.127 mm). 

2.  Angular alignment:  Insert a feeler gauge between the 

coupling halves.  Check the spacing at 90° increments 
around the coupling (four checkpoints).  Maximum 
variation should not exceed .005" (.127 mm).  Some 
laser alignment tools will check angular alignment as 
well. 

3.  Replace the coupling guards after setting alignment. 

 

 

Figure 3 – Alignment Check 

PUMP ROTATION 

A right-hand pump rotates clockwise with the intake on the 
right side, when viewed from the driven end.  See Figure 4. 

A left-hand pump rotates counterclockwise with the intake on 
the left side, when viewed from the driven end.  See Figure 5. 
 
 

TO REVERSE PUMP FLOW 

To reverse the FLOW direction, some disassembly and 
reassembly is required.  See F

low Direction Options

 in the 

Maintenance section of this manual.   

If the rotation of the electric motor driving the pump is 
incorrect; see the motor manufacturer’s instructions to change 
the rotation of the electric motor to match it to the rotation of 
the pump. 
 
 

CHECK VALVES 

The use of check valves or foot valves in the supply tank is 
not recommended with self-priming, positive displacement 
pumps.  

If the possibility of liquid backflow exists when the pump is off, 
a check valve in the system is recommended because the 
pump can motor in the reverse rotation and create undue 
stress on all attached components.  Never start a pump when 
it is rotating in the reverse rotation as the added starting 
torque can damage the pump and related equipment.  If a 
check valve is used, install it at the pump discharge. 

 

Summary of Contents for 111-G01

Page 1: ...ckmer s website www blackmer com or by contacting Blackmer Customer Service Numbers in parentheses following individual parts indicate reference numbers on Blackmer Part Lists SAFETY DATA This is a SA...

Page 2: ...ervice or maintenance can cause personal injury or property damage PUMP DATA PUMP IDENTIFICATION A pump Identification tag containing the pump serial number I D number and model designation is attache...

Page 3: ...nd installation of the piping system review the following suggestions 1 Locate the pump as near as possible to the source of supply to avoid excessive inlet pipe friction 2 The inlet line should be at...

Page 4: ...and checking the reading through one complete revolution Maximum offset should be less than 005 127 mm 2 Angular alignment Insert a feeler gauge between the coupling halves Check the spacing at 90 inc...

Page 5: ...valves are fully open and that the drain valves and other auxiliary valves are closed 4 Install inlet and discharge pressure gauges on the pump in the threaded connections provided These can be used...

Page 6: ...ations OPTIONAL PUMP RELIEF VALVE Hazardous pressure can cause personal injury or property damage An external bypass valve and or an internal relief valve MUST be installed in the system to protect th...

Page 7: ...place as required Reattach R V cap O ring and RV cap Refer to the individual Blackmer pump parts lists for various spring pressure ranges Unless specified otherwise pumps are supplied from the factory...

Page 8: ...ns following the appropriate procedures and warnings as presented in this manual See the table on page 1 of this manual to determine your pump model Figure 6 Vane Replacement 1 Flush the pump per inst...

Page 9: ...casing 7 The mechanical seal spring assembly should come out with the shaft The stationary seat and stationary seal ring need to be removed from the seal cover 126 a To remove the seal cover remove th...

Page 10: ...n and prevent bearing damage coat the bearing 24 with grease and place it on the face of the bearing housing 57 c Using an arbor press press the bearing 24 into the housing 57 until it is flush with t...

Page 11: ...oosely assembled rotor and shaft on to the piece of steel in one of the vane slots completely filling the entire vane slot c Hold the assembly securely without damaging the OD of the rotor or shaft d...

Page 12: ...3 Secure the ball bearing 24C to the shaft by uniformly tightening the setscrews on the ball bearing Bearing MUST be tightened with allen wrench per Torque Table 1 or by using the special self indicat...

Page 13: ...ating properly causing the rotor and shaft to bind or turn hard Use a tissue paper alcohol to clean the seal faces NOTE Apply a light oil or suitable lubricant to bronze seal faces only OTHER POSSIBLE...

Page 14: ...e Air leaks in the suction line Restriction in the suction line Damaged or worn pump parts Too much lift for the vapor pressure of the fluid A dirty or clogged strainer Worn vanes Suction Valve Closed...

Page 15: ...111 G00 Page 15 16 NOTES...

Page 16: ...rine Magnetic Drive Pumps Stainless Steel 14 to 215 GPM Abaque Peristaltic Hose Pumps 0 1 to 210 GPM High Lift Solids Abrasives Reciprocating Gas Compressors Liquefied Gas Transfer Boosting Vapor Reco...

Reviews: