Page 4 — English

 

Use only recommended or equivalent replacement parts 
and accessories and follow instructions in the 

Maintenance

 

section of this manual. Use of any other parts or failure 
to follow maintenance instructions may create a risk of 
shock or injury.

 

Maintain the unit per maintenance instructions in this 
Operator’s Manual.

 

Inspect the unit before each use for loose fasteners, fuel 
leaks, etc. Replace damaged parts.

DANGER:

Risk of fire and serious burns: 

Never remove fuel cap 

when unit is running. Shut off engine and allow the unit 
to cool at least five minutes. Remove cap slowly.

WARNING:

When this generator is used to supply a building 
wiring system:

 generator must be installed by a quali-

fied electrician and connected to a transfer switch as 
a separately derived system in accordance with NFPA 
70, National Electrical Code. The generator shall be 
connected through a transfer switch that switches all 
conductors other than the equipment grounding con-
ductor. The frame of the generator shall be connected to 
an approved grounding electrode. Failure to isolate the 
generator from power utility can result in death or injury 
to electric utility workers. 

 

Do not use this generator to provide power for emergency 
medical equipment or life support devices.

 

Always use a battery-powered carbon monoxide detec-
tor when running the generator. If you begin to feel sick, 
dizzy, or weak while using the generator, shut it off and 
get to fresh air immediately. See a doctor. You may have 
carbon monoxide poisoning.

 

Place the generator on a flat, stable surface with a slope 
of no more than 4°.

 

Operate outdoors in a well-ventilated, well-lit area isolated 
from working areas to avoid noise interference.

 

Operating the generator in wet conditions could result in 
electrocution. Keep the unit dry.

 

Keep the generator a minimum of 3 feet away from all 
types of combustible material. 

 

Do not operate generator near hazardous material.

 

Do not operate generator at a gas or natural gas filling 
station.

 

Do not touch the muffler or cylinder during or immediately 
after use; they are HOT and will cause burn injury.

 

This generator has a neutral floating condition. This means 
the neutral conductor is not electrically connected to the 
frame of the machine.

 

Do not allow the generator’s gas tank to overflow when 
filling. Fill to 1 in. below the top neck of the gasoline tank 
to allow for fuel expansion. Do not cover the fuel tank cap 
when the engine is running. Covering the fuel tank cap 
during use may cause engine failure and/or damage to 
the tool.

 

Do not smoke when filling the generator with gasoline.

 

Shut down the engine and allow to cool for five minutes 
before adding gasoline or lubricant to the generator.

 

Do not remove the oil dipstick or the fuel tank cap when 
the engine is running.

 

Pay close attention to all safety labels located on the 
generator.

 

Keep children a minimum of 10 feet away from the gen-
erator at all times.

 

The unit operates best in temperatures between 23°F and 
104°F with a relative humidity of 90% or less.

 

Operating voltage and frequency requirement of all 
electronic equipment should be checked prior to plug-
ging them into this generator. Damage may result if the 
equipment is not designed to operate within a +/- 10% 
voltage variation, and +/- 3 hz frequency variation from 
the generator name plate ratings. 

 

For outdoor use only.

 

Save these instructions. Refer to them frequently and use 
them to instruct others who may use this product. If you loan 
someone this product, loan them these instructions also.

IMPORTANT SAFETY INSTRUCTIONS

SPECIFIC SAFETY RULES

Summary of Contents for BMi2100A

Page 1: ...e contiene hasta 10 de etanol WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product ADVERTENCIA Para reducir el riesgo de lesiones el u...

Page 2: ...See this fold out section for all of the figures referenced in the operator s manual Consulte esta secci n desplegable para ver todas las figuras a las que se hace referencia en el manual del operado...

Page 3: ...receptacle recept culo de 12 V cc L Low oil indicator luz de bajo nivel de aceite M Overload indicator indicador de sobrecarga B A B A B A C Fig 4 Fig 2 Fig 3 A Power indicator indicador de potencia B...

Page 4: ...right to start desplace derecha de la palanca del anegador para arrancar B Move choke lever left to run desplace izquierda la palanca del anegador para poner en marcha A Engine maintenance cover cubie...

Page 5: ...A B Fig 14 A Spark plug cap tapa de la buj a B Spark plug buj a A B Fig 13 A Oil cap dipstick tapa de relleno de aceite varilla medidora de aceite B Container recipiente ON OFF B A A Screws tornillos...

Page 6: ...the nut and tighten the nut fully Connect the other end of the wire securely to a suitable ground source that is in contact with the soil for a minimum distance of 8 ft The National Electric Code con...

Page 7: ...nwindows orinotherunventilatedspace where dangerous carbon monoxide fumes can collect Carbon monoxide a colorless odorless and extremely dangerous gas can cause unconsciousness or death Keep all bysta...

Page 8: ...noise interference Operating the generator in wet conditions could result in electrocution Keep the unit dry Keep the generator a minimum of 3 feet away from all types of combustible material Do not o...

Page 9: ...e extremely flammable and explosive Fire or explosion can cause severe burns or death Hot Surface To reduce the risk of injury or damage avoid contact with any hot surface Lifting Hazard To reduce the...

Page 10: ...low the Opera tor s Manual instructions Risk of Fire Do not add fuel while the product is operating Generator is a potential source of electric shock Do not expose to moisture rain or snow Do not oper...

Page 11: ...ble materials in the direct path of the exhaust SPARK ARRESTOR Operation of this equipment may create sparks that can start fires around dry vegetation A spark arrestor may be required The operator sh...

Page 12: ...generator Damage may result if the equipment is not designed to operate within a 10 voltage variation and 3 hz frequency variation from the generator name plate ratings To avoid damage always have an...

Page 13: ...e nothing connected to the generator outlets before starting its engine The correct and safe way to manage generator power is to sequentially add loads as follows 1 With nothing connected to the gener...

Page 14: ...is provided to protect the generator against electrical overload DC RECEPTACLE Yourgeneratorhasa12V 7 5ampDCreceptacleforcharging lead acid batteries WARNING The 12 V DC receptacle is designed to char...

Page 15: ...erator Battery Charging Cable Assembly Engine Lubricant SAE 10W 30 Funnel Screwdriver Spark Plug Wrench Operator s Manual WARNING If any parts are damaged or missing do not operate this product until...

Page 16: ...the manufacturer of this product The use of attachments or accessories not recommended can result in serious personal injury NOTICE The spark arrestor on this product has not been evaluated by the USD...

Page 17: ...d until the fluid level rises between the minimum and maximum marks on the dipstick n Replace and secure the oil cap dipstick USING FUEL STABILIZER Fuel gets old oxidizes and breaks down over time Add...

Page 18: ...N position n Put the auto idle switch in the OFF O position n Pull the starter grip and rope until the engine runs NOTE Do not allow the grip to snap back after starting return it gently to its origin...

Page 19: ...ngine is configured for operation below 2 000 feet altitude at the factory Your engine must be reconfigured for operation above 2 000 feet altitude Operating the engine with the wrong engine configura...

Page 20: ...y hot and could damage the engine GENERAL MAINTENANCE Keep the generator in a clean and dry environment where it is not exposed to dust dirt moisture or corrosive vapors Do not allow the cooling air s...

Page 21: ...s in the fuel system drain the fuel from the tank and carburetor before storing DRAINING THE FUEL TANK NOTICE Remove all lubricant from the unit before draining the fuel tank Failure to do so could ca...

Page 22: ...When generator has exceeded the maximum figures specified in the table maintenance should still be cycled according to the intervals of time or hours stated herein MAINTENANCE STORAGE When preparing t...

Page 23: ...s not work Circuit protector engaged Item plugged in is defective Remove any load from the generator Turn the auto idle switch to off then depress the DC circuit breaker Try a different item AC recept...

Page 24: ...ompany or its authorized service representative Warranty is voided if the customer fails to install maintain and operate the product in accordance with the instruc tions and recommendations of the Com...

Page 25: ...ouds 3 Dirt or grit related wear caused by improper air cleaner maintenance most often resulting in worn piston piston rings cylinders valves valve guides carburetor or other internal components 4 Bro...

Page 26: ...ra a un ngulo de a lo sumo 45 Si aun as la jabalina se encuentra con el estrato rocoso se la puede enterrar en una trinchera de al menos 75 cm 30 pulg de profundidad En cualquier caso el extremo super...

Page 27: ...a debida instrucci n para su manejo No haga arrancar o funcionar el motor en un espacio confi nado de edificio cerca de ventana abiertas o en otro rea sin ventilaci n donde se puedan recolectar las em...

Page 28: ...diato Vea a un doctor Puede sufrir intoxicaci n por mon xido de carbono Coloque el generador en una superficie estable horizontal con una pendiente de no m s de 4 Utilice la unidad al aire libre en un...

Page 29: ...del mismo son extremadamente inflamables y explosivos El fuego o una explosi n pueden causar quemaduras graves e incluso la muerte Superficie caliente Para reducir el riesgo de lesiones corporales o d...

Page 30: ...ni la use en lugares h medos Usar un generador en el interior PUEDE MARTARLO EN POCOS MINUTOS Los gases de escape del generador contienen mon xido de carbono Es un veneno que no puede verse ni olerse...

Page 31: ...PARACHISPAS El uso de este equipo puede producir chispas propensas a iniciar incendios cerca de vegetaci n seca Es posible que se necesite un parachispas El operador debe ponerse en contacto con las...

Page 32: ...50 pies 15 1800 3600 46 m 150 pies 31 m 100 pies 20 m 65 pies 20 2400 4800 53 m 175 pies 38 m 125 pies 23 m 75 pies 25 3000 6000 46 m 150 pies 31 m 100 pies 30 3600 7200 38 m 125 pies 20 m 65 pies 40...

Page 33: ...ga preferiblemente la m xima carga que tenga 3 Deje que se estabilice la salida del generador el motor marchauniformementeyeldispositivoacopladofunciona correctamente 4 Enchufe y active la siguiente c...

Page 34: ...ecarga el ctrica PRISE DE C C Su generador tiene un recept culo de corriente continua de 12 V y 7 5 A para cargar bater as de cido de plomo ADVERTENCIA El recept culo de CC de 12 V est dise ado para c...

Page 35: ...l del operador ADVERTENCIA Si falta o est da ada alguna pieza no utilice este producto sin haber reemplazado la pieza Usar este producto con partes da adas o faltantes puede causar lesiones serias al...

Page 36: ...e acompa a a este producto no ha sido evaluado por el Servicio Forestal del Departamento de Agricultura de EE UU y no se puede usar en terrenos forestales de EE UU Adem s los usuarios del producto deb...

Page 37: ...osque n Retire de nuevo la varilla medidora de lubricante y verifique el nivel de lubricante El nivel de lubricante debe estar entre las marcas m nima y m xima en la varilla medidora n Si el nivel est...

Page 38: ...lesiones personales graves NOTA Siempre utilice gasolina sin plomo con un octanaje nominal inicial de 86 o mayor Nunca utilice gasolina vieja pasada o contaminada y no utilice mezcla de aceite y gaso...

Page 39: ...mientras est carg ndose Esto es normal y no indica ning n problema NOTA Utilice solamente el cable para cargar bater as para cargar bater as h medas de cido de plomo ventiladas n Despu s de la bater...

Page 40: ...generador MANTENIMIENTO Para limpiar la unidad n Con un cepillo de cerdas suaves y o una aspiradora afloje y elimine la tierra y la basura n Limpie las aberturas de ventilaci n con aire a baja presi...

Page 41: ...el espacio golpee suavementesobreunasuperficieduraelelectrododetierra n Asiente en su lugar la buj a y enr squela con la mano para evitar trasroscarla n Apri tela con una llave para comprimir la arand...

Page 42: ...arburador para recibir el combustible afloje el tornillo n Permita que se drene completamente el combustible y caiga en el recipiente n Vuelva a apretar el tornillo de drenaje n Lleve el interruptor d...

Page 43: ...stabilizador MANTENIMIENTO PROGRAMA DE MANTENIMIENTO NOTA Si recibe un manual del motor para este generador en particular respete el cronograma de mantenimiento que se indique en el manual del motor y...

Page 44: ...place seg n sea necesario No funciona el recept culo de C C El disyuntor est enganchada Est defectuosoeldispositivoconectado Desconecte todas las cargas del generador Coloque el interruptor de encendi...

Page 45: ...la Compa a o a sus representantes de servicio autorizados La garant a queda anulada si el cliente no instala mantiene o utiliza el producto respetando las instrucciones y las recomendaciones de la Co...

Page 46: ...ocasionado por el mantenimiento inadecuado del filtro de aire que generalmente provoca el desgaste de los pistones los aros del pist n los cilindros las v lvulas las gu as de las v lvulas el carburado...

Page 47: ...P gina 23 Espa ol NOTES NOTAS...

Page 48: ...rt culo el n mero de fabricaci n y el n mero de serie de este producto se encuentra en una placa o etiqueta pegada a la caja del motor Le recomendamos anotar los n meros en los espacios suministrado a...

Reviews: