Bitzer BDC 152 (2F) (V) Operating Instructions Manual Download Page 2

2

HXO-501-1 AUS

• 

Insertion of any object into condenser fans is to be avoided as this may result in personal injury and/or 

equipment damage.

• 

Operating sound pressure levels may cause discomfort. Refer to catalogue for calculated sound levels

3.  

Application Ranges

• 

These condensers are intended for use in commercial refrigeration systems with a maximum operating 

ambient temperature of approximately 60°C (special designs available on application).

• 

Recommended refrigerants: HFCs, HCFCs (also suitable for CFCs).

• 

This series of condenser is not suitable for use with NH3 (Ammonia), R410a or R744 (CO2).

• 

Standard condensers are not to be installed in hazardous/combustible environments. 

4. 

Installation Guide

 

 

The BDC Series of Air Cooled Condensers are suitable for Vertical and Horizontal air flow.

 

a) 

Mounting - Vertical Air Flow

•  Remove the condenser from its crate.

•  Vertical air flow condensers are shipped without legs fitted.

•  Legs are supplied within each BDC Series condenser crate.

•  Using an appropriate lifting device (refer Figure 1 for recommended lifting methods), attach the 

 

       legs to the condenser using the bolt kit supplied.

•  Place the condenser into the installation position and secure using the mounting holes located in 

 

       the legs.

 

b) 

Mounting - Horizontal Air Flow

•  Remove the condenser from its crate.

•  Horizontal airflow condensers are shipped with mounting feet fitted in final position.

•  Using an appropriate lifting device (refer Figure 2 for recommended lifting methods).

•  Place the condenser into the installation position and secure using the mounting holes located in 

 

       the feet. 

NOTE: 

• 

Minimum diameter of fixing bolts is to be 12.70mm (½”)

• 

The use of lifting devices during installation is recommended where applicable

• 

Observe recommended condenser mounting locations as per Figure 2.1, parts 1 and 2

• 

Remove the transport brackets from the BDC Series condensers (vertical only)

• 

Ensure the condenser is installed level, to avoid liquid locking within the condenser

• 

Refrigeration piping connections should be carried out in accordance with the current Refrigeration 

Code of Good Practice* (beware of HOT surfaces present during the welding procedure).

Summary of Contents for BDC 152 (2F) (V)

Page 1: ...ctrical power is to be isolated prior to the commencement of any electrical work During normal operation Pressurised Refrigerant is contained within the condenser Extreme care should be taken to avoid...

Page 2: ...rate Using an appropriate lifting device refer Figure 1 for recommended lifting methods attach the legs to the condenser using the bolt kit supplied Place the condenser into the installation position...

Page 3: ...ARE IN mm UNLESS OTHERWISE SPECIFIED DRAWING STANDARD AS1100 BDC 5F 6R V MAIN ASSY WITH SPREADER T CAVANAGH 23 8 17 REFER BOM 4500 22 60 M IN LE N G T H 6 0 M A X SPREADER BAR DISCHARGE LINE CONNECTI...

Page 4: ...ission of BITZER Australia DATE DRAWN BY BDC 5F 6R H MAIN ASSY WITH SPREADER 1 20 A3 SHT 3 of 3 BITZER AUSTRALIA Pty Ltd A B N 70 057 670 023 3rd ANGLE PROJECTION DATE APPROVED BY INSPECTION DIMENSION...

Page 5: ...Model s Dimensions in mm BDC 152 2F BDC 228 3F BDC 304 4F BDC 380 5F BDC 456 6F BDC 608 8F BDC 760 10F A 970 1250 1390 1680 1390 1810 2080 B 1110 1390 1530 1680 1530 1940 2220 C 1250 1530 1810 2140 18...

Page 6: ...on with solid air restriction to 1 side of platform For a multiple condenser Installation with solid air restriction to 1 side of 1 end of platform For an individual condenser Installation with solid...

Page 7: ...LATION T CAVANAGH 01 08 17 REFER BOM Figure 2 1 Part 2 2 Maximum height of solid air restriction from condenser platform is 2 8m Avoid obstructions within 2 x Diameter of fan above condenser For alter...

Page 8: ...0 023 3rd ANGLE PROJECTION DATE APPROVED BY INSPECTION DIMENSIONS XXXXX DECIMAL 1 0mm ONE DECIMAL 0 5mm TWO DECIMAL 0 2mm ANGLE 0 5 U N O TOLERANCES MASS kg MATERIAL FINISH NAME DO NOT SCALE ALL DIMEN...

Page 9: ...rical power must be isolated prior to cleaning All fan motors contain bearings and are maintenance free 9 De commissioning Instructions Pump down refrigeration system into the receiver or suitable con...

Page 10: ...Zealand BITZER Australia Pty Ltd Unit 5 5 7 Henry Rose Place Albany 0632 Auckland New Zealand tel 64 9 415 2030 www bitzer com au In the interest of continuous improvement BITZER reserves the right to...

Reviews: