ML0027 October 28, 2013
Copyright 2013 Bitronics, LLC
15
4.0 TROUBLESHOOTING
4.1 Error/Informational Messages
Message
Explanation
Action
No Comm
No valid messages are being received by
the display.
Check cable connections and
setup parameters on the Remote
Display and M870 transducer.
Config Error
There was an error in the stored
configuration parameters. The default
parameters have been restored.
Enter setup mode and check that
all parameters are set properly. If
error persists contact the factory.
Remove Power!
Instrument configuration has been
changed or new code has been
downloaded. Applies only to devices
manufactured prior to July, 2002.
Remove power to the instrument
for a few seconds and then
reapply.
5.0 FIRMWARE UPGRADES
The M870D is field upgradable. Please refer to specific instructions provided with new firmware.