37
4.4
ANGLED WALL RADIATION SHIELD
(
RSM+, RSMI30, RSMI45)
When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled
firestop or wall radiation shield must be installed. Only one is required.
Note: 45º angle for Canada only
In cold climate locations, we recommend that you use the insulated wall radiation shield
since it will maintain the home’s thermal barrier.
RSM+ and RSMI30, RSMI45
CHIMNEY – 7” dia.
ANGLE
HOLE SIZE
30º
340 mm x 845 mm (13
3
/
8
" x 33 _ ")
Secure Temp
ASHT+
Nova Temp
45º
Canada
only
340 mm x 591 mm (13
3
/
8
" x 23 _ ")
30º
380 mm x 972 mm (15" x 38 _ ")
Secure Temp
S2100+
Nova Temp
45º
Canada
only
380 mm x 657 mm (15" x 25
7
/
8
")
ACBI
30º only
432 mm x 1080 mm (17" x 42 _ ")
Table 5
Figure 33