3
Configu-
ration
Holding
time
001*
Sensor 1 + 2
001
none
End
002
Sensor 1
002
100 ms
003
Sensor 2
003*
200 ms
004
500 ms
005
1 s
E
last 5 error messages (displayed by pressing “Data”)
r
current resistances of the sensors (displayed in kOhm: 1, 2, 4, 6, 8, 10, 12 or 14)
S
shows the state of output 1:
output activated, 1 = current flow =ˆ okay, E = no current flow =ˆ error
(press “Data”) output deactivated, 0 = no current flow =ˆ okay, E = current flow =ˆ error
S
shows the state of output 2:
output activated, 1 current flow =ˆ okay, E = no current flow =ˆ error
(press “Data”) output deactivated, 0 = no current flow =ˆ okay, E = current flow =ˆ error
S
shows the state of both outputs:
outputs activated, 1 = current flow =ˆ okay, E = no current flow =ˆ error
(press “Data”) outputs deactivated, 0 = no current flow =ˆ okay, E = current flow =ˆ error
C
shows the current configuration (active inputs):
001 = both inputs 1 and 2, 002 = only input 1, 003 only input 2
h
The holding time (extension of the output signal):
001 = none, 002 =100 ms, 003 = 200 ms, 004 = 500 ms, 005 = 1000 ms
C
configuration: entering into the configuration mode by pressing “data”
→
chap. 4.5
Enter Diagnostic menu:
Press “Mode” and “Data” buttons simultaneously for
2 seconds
→
Status LED flashes orange
To see the next parameter, press “Mode”, Data query
(Mode E and r): press “Data”
Exit Diagnostic menu:
Press “Mode” button for 2 seconds
Errors flash
r
Resistors
S
Output 1
S
Output 2
S
both
outputs
C
Configu-
ration
h
Fall-delay
time
C
Configu-
ration
Error 5
latest
1
value
1
1or E
1
1 or E
11
11 or E
C
001
h
002
con
Error 4
2
value
0
0 or E
0
0 or E
00
00 or E
con
(flashing)
Error 3
Error 2
Error 1
End
›
›
›
›
›
›
›
›
›
›
›
›
›
2 sec
*
Factory setting
4.5 Configuration mode
(edit mode)
4.4 Diagnostic menu
(read only)
Data
Back to
start
Mode
›
›
›
›
Back
to top
›
›
›
›
›
›
›
›
›
›
2 sec
Access Configuration
(see chapter 4.5)
On initial commissioning, the device must be adapted (configured)
to the application.
Configuration
• Press the “Mode” button to select the requested parameter.
• Press the “Data” button to set the value.
Exit Configuration menu:
Press “Mode” until “h End”, than press “Data”.
Adjustable parameters:
C active inputs: 001 = both inputs 1 and 2, 002 = only input 1,
003 only input 2
h The holding time (extension of the output signal):
001 = none, 002 =100 ms, 003 = 200 ms, 004 = 500 ms, 005 = 1000 ms
›
›
›
›
›
›
›
›
›
›
›
›
›
›
Exit
Configuration
menu
›
{
{
›
To enter Configuration menu
(see also chapter 4.4):
• Enter diagnostic menu: Press “Mode” and “Data” buttons simultaneously for 2 seconds
→
Status LED flashes orange.
• Press “Mode” repeatedly until “C” and “con” are displayed.
• Press “Data” button, “con” starts flashing.
• Press “Mode” and “Data” buttons simultaneously until “con” stops flashing.
• Release “Mode” and “Data”, “C” starts flashing, both safety outputs open.
E
C
h
h