24 V AC/DC, 100-240 V AC, 50/60 Hz
A1 / A2:
▲
Supply voltage (24 V DC or 24 V AC) / LVAC: 100 … 240 V AC
1 / 2:
Sensor 1
3 / 4:
Sensor 2
11 / 14:
▲
Safety output 1
21 / 24:
▲
Safety output 2
5 / 6:
Status output
i
No function test possible without connected outputs (Display E 007 or E 008)
▲
Wiring mandatory
Connected sensors with a terminating resistor of 8.2 kOhm are monito-
red for a change in current.
In the idle mode
• all safety outputs are conductive
• the LED lights up green
• both dots on the display flash
When one or more sensors are
actuated
• the total resistance of the sensor system drops towards zero ohm
• the defined switching threshold is not reached anymore
• the corresponding Safety output opens
• the LED lights up orange, P appears on the display
In the event of a
fault
in the sensor circuit (for example cable breakage)
• the total resistance of the sensor system increases
• the defined switching threshold is exceeded
•
both
Safety outputs open
• the LED lights up red, E appears on the display
1
2
1
4
Configuration and set-up
3
Function
4.1 Terminals
4.2 Switch on supply voltage
Wiring the device
If necessary, configure the device
Block diagram
Function and
safety check
Function and
safety check
Safety
Output 1
Safety
Output 2
Status
Output
Power supply
Function test
• Press sensor 1, check LED (orange), display (P
,
1). Check if output 1 is open.
• Release sensor
• If present, press sensor 2, check LED, display (P
, 2). Check if output 2 is open.
• Release sensor
After successful testing, the system is ready for operation.
Display: A and two flashing dots
4.3 Function test
Sensor 1
8k2
Sensor 2
8k2
Outputs
Contacts
Unpowered
Sensor 1
idle
Sensor 1
actuated
Sensor 2
idle
Sensor 2
actuated
Sensor 1 + 2
idle
Fault
Safety output 1
OPEN
closed
OPEN
closed
OPEN
Safety output 2
OPEN
closed
OPEN
closed
OPEN
Status output
OPEN
OPEN
OPEN
closed
OPEN