10 A

24 V AC/DC, 100-240 V AC, 50/60 Hz

A1 / A2: 

▲ 

Supply voltage (24 V DC or 24 V AC) / LVAC: 100 … 240 V AC

1 / 2: 

 

Sensor 1

3 / 4: 

 

Sensor 2

11 / 14: 

▲  

Safety output 1   

21 / 24: 

▲  

Safety output 2   

5 / 6: 

 

Status output 

 

i

  No function test possible without connected outputs (Display E 007 or E 008)

 

  Wiring mandatory

Connected sensors with a terminating resistor of 8.2 kOhm are monito-
red for a change in current.  
In the idle mode
•  all safety outputs are conductive
•  the LED lights up green
•  both dots on the display flash

When one or more sensors are 

actuated

•  the total resistance of the sensor system drops towards zero ohm
•  the defined switching threshold is not reached anymore
• the corresponding Safety output opens
•  the LED lights up orange, P appears on the display

In the event of a 

fault 

in the sensor circuit (for example cable breakage)

•  the total resistance of the sensor system increases 
•  the defined switching threshold is exceeded
•  

both

 Safety outputs open

•  the LED lights up red, E appears on the display

1

2

1

4

Configuration and set-up

3

Function

4.1   Terminals

4.2   Switch on supply voltage

Wiring the device

If necessary, configure the device

Block diagram

Function and

safety check

Function and

safety check

Safety 

Output 1

Safety 

Output 2

Status

Output

Power supply

Function test

•  Press sensor 1, check LED (orange), display (P 

,

 

 1). Check if output 1 is open.

•  Release sensor
•  If present, press sensor 2, check LED, display (P 

, 2). Check if output 2 is open.

• Release sensor
After successful testing, the system is ready for operation.
Display: A and two flashing dots

4.3  Function test

Sensor  1

8k2

Sensor 2

8k2

Outputs

Contacts

Unpowered 

Sensor 1  

idle

Sensor 1 

actuated  

Sensor 2 

idle

Sensor 2 

actuated  

Sensor 1 + 2 

idle

Fault  

Safety output 1

OPEN

closed

OPEN

closed

OPEN

Safety output 2

OPEN

closed

OPEN

closed

OPEN

Status output

OPEN

OPEN

OPEN

closed

OPEN

Summary of Contents for EsGate 3

Page 1: ...amage It is the responsibility of the equipment manufacturer to carry out a risk assessment and to install both the detector and the equipment in compliance with applicable national and international regulations and safety standards as well as the Machinery Directive 2006 42 EC should this apply Before commencing the installation or assembly complete the following safety precautions Check the volt...

Page 2: ...ple cable breakage the total resistance of the sensor system increases the defined switching threshold is exceeded both Safety outputs open the LED lights up red E appears on the display 1 2 1 4 Configuration and set up 3 Function 4 1 Terminals 4 2 Switch on supply voltage Wiring the device If necessary configure the device Block diagram Function and safety check Function and safety check Safety O...

Page 3: ...ter press Mode Data query Mode E and r press Data Exit Diagnostic menu Press Mode button for 2 seconds Errors flash r Resistors S Output 1 S Output 2 S both outputs C Configu ration h Fall delay time C Configu ration Error 5 latest 1 value 1 1or E 1 1 or E 11 11 or E C 001 h 002 con Error 4 2 value 0 0 or E 0 0 or E 00 00 or E con flashing Error 3 Error 2 Error 1 End 2 sec Factory setting 4 5 Conf...

Page 4: ...ice mode further information can be displayed H Hardware Version S Software Version t Type Cat acc to EN ISO 13849 1 U Internal supply voltage o Current chip temperature E The last five error messages displayed by pressing Data E rES press and hold Data button until is displayed to reset the error messages Should other fault messages appear please contact your supplier 1 2 If an error is detected ...

Reviews: