Observe the national and international regulations on door safety.
Only trained, qualified personnel may mount and start up the detector.
The unit may only be opened and repaired by Bircher Reglomat.
The unit may only be operated from a safety extra-low voltage (SELV) system with safe electrical separation.
Always consider the safety functions of your application as a whole, never just in relation to one individual section of the system.
The installer is responsible for carrying out a risk assessment and installing the detector and the door system correctly.
Avoid touching any electronic components.
The door drive and transom profile must be grounded correctly.
Start-up
2
Montage
Translation of the original instructions
Recommended start-up sequence: I. Mounting
II. Connection
Mounting
I
General
Safety instructions
1
Please keep for further use!
Hood
Light window detector indication
no function
Cable bushing
Mounting holes
Detector electronic
Microwave module
LED microw.: green
PrimeMotion B
1.
Remove cover hood
2.
Lay and connect cable
3.
Mount detector
Radarfeld
Microwave motion detector for opening
automatically controlled doors
1.
Position drill template
2.
Drill the holes, remove drill template
3.
Lay cable and mount detector
ENGLISH
Mounting of the detector
II
Electrical connections
Connecting
3
PrimeMotion B
Controller
1 white
2 brown
3 green
4 yellow
Cable
white
brown
green
yellow
Power Supply
3 m
Radar
output*
–
+
11.5 - 36 VDC
12 - 28 VAC
Microwave
1
2
3
4
4 3 2 1
+
Mechanical fine tuning
4
–
–
+
+
Manual inclination settings
0° ... +45° in 5° steps
Manual inclination settings
– 20° ... +20° in 5° steps
–
–
+
+
1m
2m
0m
0m
1m
2m
3m
4m
Wide radar field
turn 90°
Narrow radar field
min. = 0.16 x 0.8, max. = 2 x 4 m (WxD)
min. = 0.5 x 0.25, max. = 4 x 2 m (WxD)
+
1m
2m
0m
0m
1m
2m
3m
4m
–
Inclination angle: 35°
Inclination angle: 35°
2.2 m
2.2 m
–
90°
*
See also DIP-switch-settings (Chap. 5)
289118I
12/16
Radar field