Prox-E Installation Guide v1.2|10.2018|en 

Installation 

Cable types  

№ 

Cable connection 

Max. length 

Type 

Ethernet (IEEE 802.3)  

100 m. 

Four twisted pair cables of no lower than category five 

with a wire size of no less than 0.2 mm

Power source  

50 m. 

Duplex cable with a wire size of no less than 0.75 mm

2

 (for 

example, 3192Y) 

Turnstile, lock  

20 m. 

Duplex cable with a wire size of no less than 0.75 mm

2

 (for 

example, 3192Y) 

BioSmart Mini, BS-RD  

500 m. 

Four twisted pair cables of no lower than category five 

with a wire size of no less than 0.2 mm

2

 

Exit buttons, sensors 

10 m. 

CQR-6 or RAMCRO-6 cable 

Wiegand interface 
(input and output) 

60 m. 

Four twisted pair cables of no lower than category five 

with a wire size of no less than 0.2 mm

2

 

General installation notes 

 

Install the controller on vertical surface; 

 

Cables must be installed in accordance with the operational code for electrical 
installations; 

 

Do not lay cables within 30 cm of sources of electromagnetic interference; 

 

All cables must only intersect power cables at a right angle; 

 

All cable extensions must be soldered. 

 

Carefully check for mechanical damage on the surface of the controller circuit board and 
case; 

 

In order to avoid short circuits, the protected ends of cables used to connect the controller 
must not exceed 5 mm. 

Mounting on wall 

1.

 

Decide where to install controller, using a mounting template. 

2.

 

Drill holes, according to a mounting template and insert dowels inside the holes. 

3.

 

Cut out cable input plates  

Summary of Contents for Prox-E

Page 1: ...BioSmart Prox E Installation Guide www biosmart tech com...

Page 2: ...eneral installation notes 8 Mounting on wall 8 Mounting on DIN rail 9 Power supply connection 10 Network connection 10 BioSmart Readers connection 11 Fail safe lock connection with external power supp...

Page 3: ...owed properly before putting the unit into operation Do not turn on the power supply until all installation procedures are finished this may lead to injury or equipment damage Do not disconnect or con...

Page 4: ...t BS RD and BioSmart Mini readers Controller is compatible with BioSmart Studio software version V5 0 3 269 and above Specifications Number of users 30 000 Logged events 100 000 Number of time groups...

Page 5: ...2018 en Part names and functions Name Description Alarm LED Alarm indication Work LED Work mode indication Mounting screw Fastens front cover Mounting holes Suited for fixing screws Cable inputs Detac...

Page 6: ...ackage contents Item Number pcs BioSmart Prox E Controller 1 Mounting kit four 6 35 dowels four 3 5 38 self tapping screws 1 Opening the case Remove the front cover retaining screw Detach the cover fr...

Page 7: ...gs reset BOOT Jumper Boot mode VL1 Opto isolator Controls case opening Connector names and description Name Description Used for 1 GND Power supply ground Power supply 2 12V 12V Power supply Power sup...

Page 8: ...red indicator output 24 WI01 Wiegand input 01 Reader wiegand 00 25 WI11 Wiegand input 11 Reader wiegand 01 26 SP1 Reader speaker input Reader speaker output 27 L_G1 Reader green indicator input Reader...

Page 9: ...Four twisted pair cables of no lower than category five with a wire size of no less than 0 2 mm2 General installation notes Install the controller on vertical surface Cables must be installed in acco...

Page 10: ...ttons if needed according to p 2 5 2 11 Put cables through previously made holes 6 Attach the covering and fix the retaining screw Mounting on DIN rail 1 Place the lower clip on the edge of the rail 2...

Page 11: ...um of 1 500 mA which has obtained the approval of IEC EN 60950 1 See recommended cable type and maximum length of the cable in Cable types table Network connection See recommended cable type in Cable...

Page 12: ...pe in Cable types table Note Prox E supports up to four readers Caution Avoid star type topology when connecting readers Unique address should be provided for each reader Addresses are set using switc...

Page 13: ...ternal power supply See recommended cable type in Cable types table Install a diode as it shown on figure to protect controller relay from reverse current Use 1N4007 diode 1000V 1A or similar Use sepa...

Page 14: ...ternal power supply See recommended cable type in Cable types table Install a diode as it shown on figure to protect controller relay from reverse current Use 1N4007 diode 1000V 1A or similar Caution...

Page 15: ...1N4007 diode 1000V 1A or similar Use separate power supplies for lock and controller Caution Make sure K4 jumper is off Fail secure lock connection without external power supply See recommended cable...

Page 16: ...15 Prox E Installation Guide v1 2 10 2018 en Exit buttons and door sensors connection See recommended cable type in Cable types table...

Page 17: ...16 Prox E Installation Guide v1 2 10 2018 en Wiegand output connection See recommended cable type in Cable types table...

Page 18: ...17 Prox E Installation Guide v1 2 10 2018 en Wiegand input connection See recommended cable type in Cable types table...

Page 19: ...Support support biosmart tech com 420 246 097 126 Skype BioSmart TechSupport 420 246 097 126 Konevova 2660 141 130 00 Prague Czech Republic www biosmart tech com sale biosmart tech com...

Reviews: