Installation Manual for information on wiring requirements for the fingerprint
readers. The Outdoor Enclosure will additionally require the following cables:
o
Power: The heater and thermostat (optional) shall require an external
power supply, sold separately. Power supply should be rated for either:
12 VDC, 7.0 A
24 VDC, 3.5 A
o
Earth Ground: The Sub Panel of the Outdoor Enclosure must have a
connection to Earth Ground. This connection may be shared with the
Veri-Series fingerprint reader.
It is recommended that the distance between the power supply source and
the enclosure be closely coupled to minimize cable lengths. It is also
recommended that a minimum conductor of 18 AWG be used when installing
the product. The cabling utilized should be UL-Approved.
Temporarily remove the pressure screw, slip washer, and washer.
Adapt all the modules to the cables.
Be sure to achieve a 0.1 – 1.0 mm gap between the module halves.
Lubricate all the modules by smearing the lubricant provided onto the rubber
areas (i.e., inside the frame, around and between the module halves, etc.).
Start by placing a module half at the bottom.
Place the cables in the adapted modules.
Add the second module half on top.
Add the next module and continue packing until the space is filled.
Put the washer and slip washer back in place.
Adjust the washer to match the compression rubber.
Reinstall the pressure screw and tighten it hard to compress the gland.
*When pulling the cables through the Roxtec Gland seal, please ensure that there is
enough slack to reach through the Sub Panel opening and make the connections to
the optional heater, Veri-Series 15-Conductor Pigtail or Weidmuller Connectors, but
not so much slack whereby the cable will significantly bend behind the back plate.
Connecting the Heater and Thermostat
If the Outdoor Enclosure purchased did not include a heater and thermostat, please
proceed to the next section.
The Outdoor Enclosure optionally includes a heater designed to maintain the Veri-
Series fingerprint reader at an ambient temperature of approximately 24
°
C (75
°
F).
The heater shall require an external power supply. There is no polarity to the heater,
which will accept 12 to 36 V AC/DC. However, a power supply rated at either 12 VDC
/ 7.0 A or 24 VDC / 3.5 A is recommended. It is recommended that this power supply