CNCR-110 • Two-wire 4-20
13
7 Menu overview
Menu item
Selection
Default settings
Measurement loop name Alphanumeric characters
Sensor
Medium
Liquid
Bulk solid
Liquid
Application liquid
Storage tank, agitator tank, dosing tank, pumping
station/pump shaft, rain overflow basin, tank/collec
-
tion basin, plastic tank (measurement through tank
top), mobile plastic tank (IBC), level measurement in
waters, flow measurement flume/overflow, demon
-
stration
Storage tank
Application bulk solid
Silo (slim and high), bunker (large
volume), stockpile (point measurement/
profile detection), crusher, demonstration
Silo
(slender and high)
Units
Distance unit of the device
Temperature unit of the instrument
Distance in ft.
Temperature in °F
Adjustment
Max. adjustment (distance A) - 20mA (100%)
Min. adjustment (distance B) - 4mA (0%)
Distance from sensor
Max. adjustment 0.0 m
Min. adjustment 8.0 m
Menu item
Selection
Default settings
Damping
Integration time
0 s
Current output
Output characteristics
4 to 20 mA = 0% to 100%
Current range
Min. current 4 mA and
max. current 20.5 mA
Reaction when malfunctions occur
Failure mode
< 3.6 mA
Linearization
Linearization type
Linear
Scaling
Scaling size
Scaling unit
Scaling format
0% correspond to 0 l
100% correspond
to 100 l
Display
Menu language
Displayed value
Backlight
English
Distance
On
Access protection
Bluetooth access code
-
Parameter Protection
Deactivated