Troubleshooting
6.1 FAILURE OR BREAKDOWN RESEARCH
Event
Possible cause
Remedy
Actuator does not
work
Lack of power supply
Restore it
Lack of hydraulic
supply
Open line interception
valve
Failure of the spring
Call BIFFI Italia S.r.l.
Customer Service
Blocked valve
Repair or replace
Wrong position of the
distributor of the
manual hydraulic group
Restore correct
position
Failure of the control
group
Call BIFFI Italia S.r.l.
Customer Service
Unexpected
intervention of torque
limit-device
Call BIFFI Italia S.r.l.
Customer Service
Actuator too slow
Low supply pressure
Restore (Sect. 1.4)
Wrong calibration of
flow regulator valves
Restore (Sect. 3.6)
Bad functioning of
quick exhaust valve
Call BIFFI Italia S.r.l.
Customer Service
Wear of the valve
Replace
Actuator too fast
High supply pressure
Restore (Sect. 1.4)
Bad functioning of
booster/quick exhaust
valve
Call BIFFI Italia S.r.l.
Customer Service
Wrong calibration of
flow regulator valves
Restore (Sect. 3.6)
Leakages on
hydraulic or
pneumatic circuits
Deterioration and/or
damage to gaskets
Call BIFFI Italia S.r.l.
Customer Service.
Incorrect position of
the valve
Wrong adjustment of
mechanical stops
Restore (Sect. 3.4)
Wrong warning of
microswitches
Restore (Sect. 3.5)
Hydraulic manual
pump does not work
handle positioned on
remote control
Position the handle on
the indication of the
operation to make
Leakages on the check
valve of the hydraulic
control group
Call BIFFI Italia S.r.l.
Customer Service