Bierer DCI-50-CT Operating Instructions Manual Download Page 5

 

 

 
 

IDENTIFY URD CABLE USING STRCV 

 

1.

 

Follow the “DC TRANSMITTER SET-UP AND TEST” 
Procedure outlined on page 4. 

2.

 

Ensure the power light is on, the blue pulse light is pulsing, and 
the green short continuity light is illuminated. If the red open 
light is on, turn the unit off, check your connections and try 
again. 

3.

 

Turn the STRCV on and place the tip on the wire close to the 
transmitter to verify cable and direction of the pulse. 

4.

 

At the test site, slowly approach the cable with the tip of the 
STRCV. And identify the cable with the pulse going in the same 
direction. Only the cable with the pulse pointing in the same 
direction is the correct cable. Other cables may show a pulse 
present but will be harder to pick up and will pulse in the wrong 
direction. 

5.

 

After testing is complete remove all equipment and restore cable 
to its original condition. 

 
 
 

 
 

 
 

Summary of Contents for DCI-50-CT

Page 1: ...1 Operating Instructions DCI 50 CT Cable Identifier...

Page 2: ...Liability Bierer Associates Inc warrants this product to be free from defects in workmanship and material under normal use and service conditions for a period of one year from date of shipment Due to...

Page 3: ...MAN HOLE OR DITCH ODD MAN OUT DCI 50 RED LEAD BLACK LEAD DCI 50 H1B H1A X1 X3 X2 H1B H1A TRANSFORMER SWITCH GROUNDED FAR END MAN HOLE OR DITCH ODD MAN OUT H1A H2A H3A H1B H2B H3B SIGNAL MOVING IN OPP...

Page 4: ...he battery before operation 3 Install the battery to the unit by sliding the battery into the battery holder 4 Make sure the alligator clips are not touching and turn the unit on 5 The power and open...

Page 5: ...on and place the tip on the wire close to the transmitter to verify cable and direction of the pulse 4 At the test site slowly approach the cable with the tip of the STRCV And identify the cable with...

Page 6: ...around the cable at the source so the red arrow faces away from the transmitter on the cable Pointing towards the grounded end of the cable 5 Adjust the sensitivity knob till a clear positive indicat...

Page 7: ...es away from the transmitter on the cable Pointing towards the grounded end of the cable 5 If the red cable is attached to the center conductor and the black cable is attached to the ground the needle...

Page 8: ...to unit 1 With power off of the unit plug the CT into the back of the transmitter 2 Clamp the CT around the neutral between the cable and the common neutral The unit will do the rest 3 When removing...

Reviews: