![Bierer DCI-50-CT Operating Instructions Manual Download Page 5](http://html1.mh-extra.com/html/bierer/dci-50-ct/dci-50-ct_operating-instructions-manual_2749419005.webp)
5
IDENTIFY URD CABLE USING STRCV
1.
Follow the “DC TRANSMITTER SET-UP AND TEST”
Procedure outlined on page 4.
2.
Ensure the power light is on, the blue pulse light is pulsing, and
the green short continuity light is illuminated. If the red open
light is on, turn the unit off, check your connections and try
again.
3.
Turn the STRCV on and place the tip on the wire close to the
transmitter to verify cable and direction of the pulse.
4.
At the test site, slowly approach the cable with the tip of the
STRCV. And identify the cable with the pulse going in the same
direction. Only the cable with the pulse pointing in the same
direction is the correct cable. Other cables may show a pulse
present but will be harder to pick up and will pulse in the wrong
direction.
5.
After testing is complete remove all equipment and restore cable
to its original condition.