CONNECTING THE REMOTE CONTROL PAD TO THE UNIT
The remote room controller supplied with the unit should be connected to the
designated connection points on the provided terminal block on the control
panel using Non Screened 16/0.2mm (0.5mm
2
) cable. Cable ties and cable
glands are provided to secure cables. The number of cable cores will depend on
the type of room controller as detailed below.
THIS CONNECTION IS VOLTAGE FREE AND SHOULD NOT BE CONNECTED TO ANY
OTHER VOLTAGE SOURCE.
The Model TB/TS-BIDDLE wall mounted controller for temperature sensing only,
requires 2 cores connected to terminals numbered 1 – 2.
The Model TB/TS/K-BIDDLE for manual heating & automatic / no ventilation
adjustment requires 3 cores connected to terminals 1, 2 & 3 only.
Cables must be connected to both the terminal block located inside the unit
control panel and the remote control pad using the identically numbered
terminal.
See the unit wiring diagrams (page 13/14) and installation instructions supplied
with the control pad for details.