1
5
3. Use
the
UP ARROW
and
DOWN ARROW
keys to change the
value.
4. After a value is selected, press
ENTER
to retain that value.
5. Press
the
INDEX
key until
InPb
appears on the display.
InPb
determines the action the controller will perform, when the
InPt
timer runs out. If
InPt
has a value of
OFF
,
InPb
will not be
displayed. There are three options for this menu item:
•
FAIL
Output is disabled.
•
AVE
The output will hold at the last known average
percentage of output.
•
PrE
The output will maintain a preprogrammed
percentage of output as specified in
PrE1
and
PrE2
.
If
PrE
is selected, the following menu item will appear.
•
PrE1
Select 0 to 100% for Set Point 1
6
. Use the
UP ARROW
and
DOWN ARROW
keys to change the
value.
7
. After a value is selected, press
ENTER
to retain that value.
Loop Break
Protection
1. Press
the
UP ARROW
and
ENTER
keys to enter the
Secondary Menu.
2. Press
the
INDEX
key until
LPbr
appears on the display. If,
during the operation, the output is at its minimum or maximum,
and the input has moved less than 5
o
F (3
o
C) over the time
specified in
LPbr
, the
LOOP bAd
message will appear. If
ALLb
is
On
, then this condition will cause an alarm.
LPbr
has
a range
1
to
9999
seconds, or
OFF
.
3. Use
the
UP ARROW
and
DOWN ARROW
keys to change the
value.
4.
Press
ENTER
to retain that value.
Tuning
1. Press
the
UP ARROW
and
ENTER
keys to enter the
Secondary Menu.