AVVERTENZE PER L’INSTALLATORE D812160_04

ENGLISH

INSTALLER WARNINGS

WARNING! Important safety instructions. Carefully 

read and comply with all the warnings and instruc-

tions that come with the product as incorrect instal-

lation can cause injury to people and animals and 

damage to property. The warnings and instructions 

give important information regarding safety, instal-

lation, use and maintenance. Keep hold of instruc-

tions so that you can attach them to the technical 

file and keep them handy for future reference.

GENERAL SAFETY

This product has been designed and built solely for 

the purpose indicated herein. Uses other than those 

indicated herein might cause damage to the product 

and create a hazard.

- The units making up the machine and its installation 

must meet the requirements of the following European

Directives, where applicable: 2004/108/EC, 2006/95/

EC, 99/05/EC and later amendments. For all countries 

outside the EEC, it is advisable to comply with the

standards mentioned, in addition to any national

standards in force, to achieve a good level of safety.

- The Manufacturer of this product (hereinafter referred 

to as the “Firm”) disclaims all responsibility resulting

from improper use or any use other than that for

which the product has been designed, as indicated

herein, as well as for failure to apply Good Practice in 

the construction of entry systems (doors, gates, etc.) 

and for deformation that could occur during use.

- Before commencing installation, check the product

for damage.

- Make sure the stated temperature range is compatible 

with the site in which the automated system is due to 

be installed.

- Do not install this product in an explosive atmosphere: 

the presence of flammable fumes or gas constitutes a 

serious safety hazard.

- Disconnect the electricity supply before performing

any work on the system. Also disconnect buffer bat-

teries, if any are connected.

- Before connecting the power supply, make sure the

product’s ratings match the mains ratings and that a 

suitable residual current circuit breaker and overcur-

rent protection device have been installed upline from 

the electrical system. Ensure that there is an automa-

tion, switch or 16A all-pole thermal magnetic circuit

breaker on the grid to enable complete disconnection 

in the conditions of overvoltage III category.

- Make sure that upline from the mains power supply

there is a residual current circuit breaker that trips at 

no more than 0.03A as well as any other equipment

required by code.

- Make sure the earth system has been installed cor-

rectly: earth all the metal parts belonging to the entry 

system (doors, gates, etc.) and all parts of the system 

featuring an earth terminal.

- Only use original spare parts for any maintenance or 

repair work. The Firm disclaims all responsibility for the 

correct operation and safety of the automated system 

if parts from other manufacturers are used.

- Do not make any modifications to the automated

system’s components unless explicitly authorized by 

the Firm.

- Instruct the system’s user on what residual risks may be 

encountered, on the control systems that have been 

applied and on how to open the system manually in 

an emergency. give the user guide to the end user.

- Dispose of packaging materials (plastic, cardboard,

polystyrene, etc.) in accordance with the provisions

of the laws in force. Keep nylon bags and polystyrene 

out of reach of children.

WIRING

WARNING! 

For connection to the mains power supply, 

use: a multicore cable with a cross-sectional area of at 

least 5x1.5mm

2

 or 4x1.5mm

2

 when dealing with three-

phase power supplies or 3x1.5mm

2

 for single-phase

supplies (by way of example, type H05 VV-F cable can 

be used with a cross-sectional area of 4x1.5mm

2

). To 

connect auxiliary equipment, use wires with a cross-

sectional area of at least 0.5 mm

2

.

- Only use pushbuttons with a capacity of 10A-250V

or more.

-  Wires must be secured with additional fastening near 

the terminals (for example, using cable clamps) in

order to keep live parts well separated from safety

extra low voltage parts.

-  During installation, the power cable must be stripped 

to allow the earth wire to be connected to the relevant

terminal, while leaving the live wires as short as pos-

sible.  The earth wire must be the last to be pulled

taut in the event the cable’s fastening device comes 

loose.

WARNING!

 safety extra low voltage wires must be kept 

physically separate from low voltage wires.

Only qualified personnel (professional installer) should 

be allowed to access live parts.

 

SCRAPPING

Materials must be disposed of in accordance 

with the regulations in force. Do not throw 

away your discarded equipment or used 

batteries with household waste. You are 

responsible for taking all your waste electri-

cal and electronic equipment to a suitable 

recycling centre.

Anything that is not explicitly provided for in the 

installation manual is not allowed. Proper ope-

ration can only be guaranteed if the information 

given herein is complied with. The Firm shall not 

be answerable for damage caused by failure to 

comply with the instructions featured herein.

While we will not alter the product’s essential 

features, the Firm reserves the right, at any time, 

to make those changes deemed opportune to 

improve the product from a technical, design or 

commercial point of view, and will not be required 

to update this publication accordingly.

DECLARATIONS OF CONFORMITY CAN BE FOUND 

AT http://www.bft-automation.com/CE 

INSTRUCTIONS FOR USE AND ASSEMBLY CAN BE 

FOUND IN THE DOWNLOAD SECTION.

12 -

  MIME AC

 MIME AC - 

 13

D812771 00550_03

Summary of Contents for MIME AC

Page 1: ... MIME MIME AC Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur 433 Mhz TWO CHANNEL MINIATURE RECEIVER FOR INDOOR USE M ...

Page 2: ... 2 attivo quando connesso al 4 Ch 2 local control input active when connected to 4 Touche commande locale ch 2 active si connectée sur le 4 Ingresso alimentazione neutro o _ Supply input neutral or _ Entrée alimentation neutre ou _ Ingresso alimentazione fase o Supply input phase or Entrée alimentation neutre ou Comune contatti relè Relay contact common Commun contacts relais Contatto n o uscita c...

Page 3: ...i oppure 2 pulsanti Local inputs 2 switches or 2 buttons Entrées locales 2 interrupteurs ou 2 touches Ingressi locali 2 interruttori oppure 2 pulsanti Local inputs 2 switches or 2 buttons Entrées locales 2 interrupteurs ou 2 touches 2carichiresistivi230VAC1250VAMaxciascuno 2 resistive loads 230VAC 1250VA Max each 2 charges résistives 230V CA 1250VA maxi chacune Motore230VACasincronomonofase Max125...

Page 4: ... Se la cancellazione è andata a buon fine la ricevente emetterà If clearing has been successful the receiver will emit Si l effacement a réussi le récepteur émettra La cancellazione della memoria porta il dispositivo alle impostazioni di fabbrica nessun telecomando memorizzato modalità luce bistabile temporizzazioni default vedi FIG D5 paragrafo PROGRAMMAZIONETIMEOUT DI FUNZIONAMENTO Clearing the ...

Page 5: ...la ricevente emetterà About 1 second after releasing the button the receiver will emit Environ 1 seconde après avoir lâché la touche le récepteur émettra Dopo circa 1 secondo dal rilascio pulsante la ricevente emetterà About 1 second after releasing the button the receiver will Environ 1 seconde après avoir lâché la touche le récepteur émettra Premere il tasto della ricevente in corrispondenza del...

Page 6: ... di 10 secondi To clear another transmitter repeat point 7 To end the procedure wait for the 10 second timeout Pour effacer un autre émetteur répétez le point 7 Pour achever la procédure attendez le délai de 10 secondes SELEZIONE MODALITÀ DISPOSITIVO DEVICE MODE SELECTION SÉLECTION MODES DISPOSITIF Attenzione Verranno cancellati anche itelecomandi in memoria WARNING THE REMOTE CONTROLS INTHE MEMOR...

Page 7: ...visi acustici a ogni pressione del pulsante Briefly press the button the number of times equal to the mode you wish to program X 1 pressure 0 minutes X 2 pressures 1 minute X 60 pressures 59 minutes The receiver flashes and bleeps three times every time the button is pressed Appuyez brièvement sur la touche un nombre de fois égal au mode que vous voulez programmer X 1 pression 0 minute X 2 pressio...

Page 8: ...ri alla funzione selezionata ogni 2 secondi PROCEDURE RADIO RADIO PROCEDURES PROCÉDURES RADIO APPRENDIMENTO DEL PRIMO TELECOMANDO O DI ULTERIORI TELECOMANDI IN MODALITÀ MOTORE LEARNING THE FIRST REMOTE CONTROL OR FURTHER REMOTE CONTROLS IN MOTOR MODE APPRENTISSAGE DE LA PREMIÈRETÉLÉCOMMANDE OU D ULTÉRIEURESTÉLÉCOMMANDES EN MODE MOTEUR Briefly press the button the number of times equal to the mode ...

Page 9: ... up 6 pressures mode 2 6 Deadman down 7 pressures mode 2 7 Stop 8 pressures mode 2 8 Up 9 pressures mode 2 9 Down 10 pressures return to function 1 The system will show the user the selection made via the LED with a number of quick flashes and bleeps equal to the selected function every 2 seconds Appuyez brièvement sur la touche un nombre de fois égal au mode que vous voulez programmer 1 pression ...

Page 10: ...tem featuring an earth terminal Only use original spare parts for any maintenance or repairwork TheFirmdisclaimsallresponsibilityforthe correctoperationandsafetyoftheautomatedsystem if parts from other manufacturers are used Do not make any modifications to the automated system s components unless explicitly authorized by the Firm Instructthesystem suseronwhatresidualrisksmaybe encountered on the ...

Page 11: ...ereforeprotectionadequatetothe installedload s fuseorcircuitbreaker mustbeprovided It is forbidden to install the receiver in SELV system sections i e bell circuits video entry systems 12 24V spot lights etc The control devices buttons or switches and the con necting cables must have isolation features suitable to electrical systems with operating voltage no lower than 300VAC 3 APPLICATIONS Remote...

Page 12: ...a maximum time equal to the set operating time For all the MOTOR modes In case of a voltage drop when the supply is restored the minireceiver keeps the outputs OFF 9 PROCEDURES MEMORY CLEARING FIG D1 REMOTE CONTROL MEMORY CLEARING FIG D2 SINGLE REMOTE CONTROL CLEARING FIG D3 DEVICE MODE SELECTION FIG D4 OPERATION TIMEOUT PROGRAMMING FIG D5 ENGLISH D812771 00550_03 Bft Spa Via Lago di Vico 44 36015...