background image

12

 -

ARIES/ARIES-P - Ver. 04

D811184A_04

INSTALLATION MANUAL

ENGLISH

Thank you for buying this product, our company is sure that you will be more

than satisfied with the product

s performance. The product is supplied with

a

WARNINGS

 leaflet and an 

INSTRUCTION MANUAL

.

These should both be read carefully as they provide important information

about safety, installation, operation and maintenance.

This product complies with the recognised technical standards and safety

regulations. We declare that this product is in conformity with the following

European  Directives:  89/336/EEC  and  73/23/EEC  (and  subsequent

amendments).

1) GENERAL OUTLINE

The

ARIES

 control unit has been designed for swing gates. It can be used

for one or two gate controllers.

The control unit mod. ARIES P can also be used to perform opening of a

single actuator while keeping the other one closed (pedestrian access).

2) GENERAL SAFETY
WARNING! An incorrect installation or improper use of the product
can cause damage to persons, animals or things.

The

Warnings

  leaflet  and 

Instruction  booklet

  supplied  with  this

product should be read carefully as they provide important information

about safety, installation, use and maintenance.

Scrap packing materials (plastic, cardboard, polystyrene etc) according

to the provisions set out by current standards. Keep nylon or polystyrene

bags out of children

s reach.

Keep  the  instructions  together  with  the  technical  brochure  for  future

reference.

This product was exclusively designed and manufactured for the use

specified in the present documentation. Any other use not specified in

this documentation could damage the product and be dangerous.

The Company declines all responsibility for any consequences resulting

from  improper  use  of  the  product,  or  use  which  is  different  from  that

expected and specified in the present documentation.

Do not install the product in explosive atmosphere.

The Company declines all responsibility for any consequences resulting

from  failure  to  observe  Good  Technical  Practice  when  constructing

closing structures (door, gates etc.), as well as from any deformation

which might occur during use.

The installation must comply with the provisions set out by the following

European  Directives:  89/336/EEC,  73/23/EEC,  98/37/ECC  and

subsequent amendments.

Disconnect the electrical power supply before carrying out any work on

the installation. Also disconnect any buffer batteries, if fitted.

Fit an omnipolar or magnetothermal switch on the mains power supply,

having a contact opening distance equal to or greater than 3mm.

Check  that  a  differential  switch  with  a  0.03A  threshold  is  fitted  just

before the power supply mains.

Check that earthing is carried out correctly: connect all metal parts for

closure (doors, gates etc.) and all system components provided with an

earth terminal.

The Company declines all responsibility with respect to the automation

safety  and  correct  operation  when  other  manufacturers

  components

are used.

Only use original parts for any maintenance or repair operation.

Do not modify the automation components, unless explicitly authorised

by the company.

Instruct the product user about the control systems provided and the

manual opening operation in case of emergency.

Do  not  allow  persons  or  children  to  remain  in  the  automation

operation area.

Keep radio control or other control devices out of children

s reach, in

order to avoid unintentional automation activation.

The  user  must  avoid  any  attempt  to  carry  out  work  or  repair  on  the

automation  system,  and  always  request  the  assistance  of  qualified

personnel.

Anything which is not expressly provided for in the present instructions,

is not allowed.

3) TECHNICAL SPECIFICATIONS

Power supply:...............................................................230V 

±

10% 50Hz

Absorption on empty:.................................................................0.5A max

Output power for accessories:..........................................24V~ 6VA max

Max relay current:................................................................................8A

Max power of motors:...............................................................300 W x 2

Torque limiter:.................................................Self-transformer with 4 pos

Limit switch:................................................................Adjustable run time

Panel dimensions:.........................................................................See fig.1

Cabinet protection:............................................................................IP55

Working temperature:...............................................................-20 +55

°

C

4) TERMINAL BOARD CONNECTIONS

 (Fig.2)

CAUTION:  Keep  the  low  voltage  connections  completely
separated from the power supply connections.

Fig.3  shows  the  fixing  and  connection  method  of  the  drive  condensers

whenever they are not fitted to the motor.

JP5

1-2 Single-phase power supply 230V 

±

10%, 50 Hz (1=L/2=N).

For  connection  to  the  mains  use  a  multiple-pole  cable  with  a  minimum

cross section of 3x1.5mm

2

 of the type indicated in the above-mentioned

standard (by way of example, if the cable is not shielded it must be at least

equivalent to H07 RN-F while, if shielded, it must be at least equivalent to

H05 VV-F with a cross section of 3x1.5mm

2

).

JP3

3-4 (mod.ARIES-P) 230V 40W max. blinker connection.

5-6 (mod.ARIES) 230V 40W max. blinker connection.

7-8-9 Motor M1 connection - 8 common, 7-9 start.

10-11-12 Motor M2(r) connection - 11 common, 10-12 start.

JP4

13-14 Open-close button and key switch (N.O.).

13-15 Stop button (N.C.). If unused, leave bridged.

13-16 Photocell or pneumatic edge input (N.C.). If unused, leave bridged.

17-18 24V  3W max. gate open warning light.

18-19  24V~  0.25A  max.  (6VA)  output  (for  supplying  photocell  or  other

device).

20-21 Antenna input for radio-receiver board (20 signal - 21 braid).

22 Common terminal (equivalent to terminal 13).

23 Terminal for pedestrian control. It moves the leaf of motor M2 connected

to terminal 10-11-12. This terminal is available only in ARIES-P control unit.

JP2

25-26  2nd  radio  channel  output  of  the  double-channel  receiver  board

(terminals not fitted on ARIES but fitted on ARIES-P) contact N.O.

JP1

 Radio-receiver board connector 1-2 channels.

5) FUNCTIONS
DL1: Power-on Led

 It is switched on when the board is electrically powered.

START: four-step logic: (DIP5 OFF)

gate closed:..................................................................................it opens

during opening:............................................... it stops and activates TCA

gate open:................................................................................... it closes

during closing:.................................... it stops and does not activate TCA

after stop:.........................................................................it starts opening

START: two-step logic: (DIP5 ON)

gate closed:..................................................................................it opens

during opening:................................it stops and activats TCA (if activated)

gate open:....................................................................................it closes

during closing:..............................................................................it opens

after stop:.....................................................................................it opens

STOP:

 In all cases: it stops the gate until a new start command is given.

PHOT:

Functions can be set with DIP-SWITCH.

Activated during closing if DIP3-ON.

Activated during opening and closing if DIP3-OFF.

SCA: Gate open indicating light.

with gate closed:...................................................................................off

when gate is opening:...........................................................................on

with gate open:.......................................................................................on

when gate is closing:.....................................................................flashing

6) DIP-SWITCH SELECTION
DIP1 Rapid closing

ON:  When  the  position  of  the  gate  photocells  is  exceeded,  during  both

opening and closing, the gate automatically starts to close even if TCA is

activated. We recommend setting DIP3 to ON (photocells only activated

during closing).

OFF: Function not activated.

DIP2 Blocks impulses

ON: During opening, START commands are not accepted.

OFF: During opening, START commands are accepted.

DIP3 Photocells

ON: Photocells only activated during closing.

OFF: Photocells activated during opening and closing.

Summary of Contents for ARIES

Page 1: ...ET D INSTALLATION INSTALLATIONS UND GEBRAUCHSANLEITUNG INSTRUCCIONES DE USO Y DE INSTALACION INSTRUÇÕES DE USO E DE INSTALAÇÃO CENTRALINA DI COMANDO D811184A ver 04 08 02 02 I CONTROL UNIT GB UNITÉ DE COMMANDE F STEUERZENTRALE D CENTRAL DE MANDO E CENTRAL DO MANDO P ARIES ARIES P 8 027908 113740 ...

Page 2: ...ARIES ARIES P Ver 04 3 D811184A_04 ...

Page 3: ...tocells only activated during closing OFF Photocells activated during opening and closing Automatic closing time TCA ON Automatic closing activated can be adjusted from 0 to 90s Preallarm mod ARIES P only ON The flashing light turns on abt 3 seconds before the motors start FOR THE INSTALLER check the boxes you are interested in START four step logic Gate closed Gate open During opening During clos...

Page 4: ...ontrol devices out of children s reach in order to avoid unintentional automation activation The user must avoid any attempt to carry out work or repair on the automation system and always request the assistance of qualified personnel Anything which is not expressly provided for in the present instructions is not allowed 3 TECHNICAL SPECIFICATIONS Power supply 230V 10 50Hz Absorption on empty 0 5A...

Page 5: ... sockets as described below Pos T1 1st TORQUE MINIMUM TORQUE Pos T2 2nd TORQUE Pos T3 3rd TORQUE Pos T4 4th TORQUE MAXIMUM TORQUE 4 motor torque values can be obtained To gain access to the torque adjustment sockets disconnect the mains supply and remove the protective case P of the transfomer CAUTION Excessive torque adjustment may jeopardise the anti squash safety function On the other hand insu...

Page 6: ... JP4 JP12 MOT1 MOT2 JP13 M1 M2 r JP14 JP15 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 MAX40W JP4 JP2 JP12 MOT1 MOT2 JP13 M1 M2 r JP14 JP15 7 8 9 10 11 12 COMM START STOP PHOT NO NO NO II CH NC NC 0V SCA 24Vac COMM ANTEN 13 14 15 16 17 18 19 20 21 22 23 25 26 JP2 NO II CH 25 26 COMM START STOP PHOT NO NC NC 0V SCA 24Vac COMM PED ANTEN ...

Page 7: ...LOS CONDENSADORES EN LA CENTRAL DE MANDO LIGA ÍE CONDENSADORES NA CENTRAL DE MANDO JP12 JP4 TW TCA DL1 66 55 44 TDELAY MOT1 MOT2 JP13 M1 M2 r JP14 JP15 5 6 7 23 22 21 20 19 26 25 II CH 18 17 16 15 14 13 JP4 11 12 10 9 8 7 6 5 JP3 JP11 JP6 JP7 2 T 0 5A 230V T 1A 110V T 2 5A 230V T 5A 110V 1 JP5 JP13 JP12 JP9 JP14 JP15 L 0V 0 12 12 T2 T3 T4 N 22 11 33 JP8 JP10 JP2 55 P 8 9 10 11 12 ON 1 2 3 4 5 6 DI...

Reviews: