Technical data
3-1
3
Technical data
3.1
General characteristic features
•
Self-control to verify flawless function of the device in keep-
ing with European standards EN 230, EN 298 and TRD
411 to 414.
•
Two externally selectable sensitivity and time levels
•
Fully electronic construction
•
Tested by the German Technical Inspection Association TÜV
•
Approved of by DIN DVGW and DIN CERTCO
•
Suitable for safety related applications up to SIL 3 (according to IEC 61508)
3.2
Electrical system, mechanical system, function
two switch-OFF time
adjustable in six steps (1 to 6 seconds)
two sensitivity ranges
adjustable in 99 steps
switch-ON treshold
adjustable in 64 steps (25 to 75 %)
switch-OFF treshold
< 25%
flame relay
two changeover contacts (1 changeover contact
potential-free internal 1 amp fuse)
flame intensity display
0 to 100 %
by bar graph
flame intensity output
0 (4) to 20 mA
(Ra < 360 ohm)
flame evaluation display
000 – 999
LED-seven segment
impulse dividing ratio
1:1 , 1:2 , 1:4
switching treshold - pre-alarm warning 50%
pre-alarm warning
+ 24 V DC, 100 mA
short-circuit-proof
time level selection II
+ 24 V DC, 40 mA
quantisation changeover
jumpers
active-ON time II
+ 15 V DC, 10 mA
status indicators
time level I or II ON
green LED
pre-alarm warning ON
yellow LED
evaluation and
monitor channel. ON
yellow LED