5.Current Sharing with Remote Sense

RSP-1500 has the built-in active current sharing function and can be connected in parallel, up to 4 units, to provide higher output power as exhibited below :

Difference of output voltages among parallel units should be less than 0.2V.

The power supplies should be paralleled using short and large diameter wiring and then connected to the load.

Sense lines should be twisted in pairs to minimize noise pick-up.

When remote sensing is used in parallel operation, the sensing wire must be

connected only to the master unit

+V

+V

+V

+V

-V

-V

-V

-V

AC/L

AC/L

AC/L

AC/L

AC/N

AC/N

AC/N

AC/N

No.1(Master)

No.2(Slave)

No.3(Slave)

No.4(Slave)

Load

+V

-V

+S

-S

+S,-S  and  CS  are  connected  mutually  in  paralle

l

The total output current must not exceed the value determined  by the following equation:

Maximum output current at parallel operation=(Rated current per unit)

(Number of unit)

0.9

×

×

1

5

0

0

W Single Output with PFC Function

MEAN WELL 

RSP

-

1

5

0

0

 SERIES

Beta Dyne, Inc.

 

508-697-1993

www.betadynepower.com

Summary of Contents for RSP-1500-12

Page 1: ...gn flexibility by equipping various built in functions such as the output programming active current sharing remote ON OFF control auxiliary power etc 48 RSP 1500 Series name Output wattage Output vol...

Page 2: ...e are measured at 20MHz of bandwidth by using a 12 twisted pair wire terminated with a 0 1uf 47uf parallel capacitor 3 Tolerance includes set up tolerance line regulation and load regulation 4 The pow...

Page 3: ...tics INPUT VOLTAGE V 60Hz 100 90 80 70 60 50 LOAD 90 100 120 140 150 160 180 200 220 240 264 EFFICIENCY LOAD The curve above is measured at 230VAC Efficiency vs Load 48V Model MODEL MODEL INPUT INPUT...

Page 4: ...er the output voltage can be trimmed to 70 100 Typ of the nominal voltage by applying Connect an external resistor between on CN1 or CN2 and S V S V also need to be connected TRIM pin4 S pin3 or pin4...

Page 5: ...rnal 12V auxiliary output 2 2K AUX RC1 12V typ AUXG 150 RCG RC2 SW 620 5V 150 RC2 12V typ RCG AUXG 2 2K RC1 AUX SW 150 RC2 12V typ AUXG SW RCG 2 2K RC1 AUX Connection Method CN3 CN2 PIN2 RC2 PIN1 RCG...

Page 6: ...voltage 10mA max Function P OK The signal is Low when the power supply is above 65 of the rated output voltage or say Power OK Description The signal turns to be High when the power supply is under 65...

Page 7: ...wisted in pairs to minimize noise pick up When remote sensing is used in parallel operation the sensing wire must be connected only to the master unit V V V V V V V V AC L AC L AC L AC L AC N AC N AC...

Page 8: ...ignment HRS DF11 8DP 2DS or equivalent CN1 CN2 CN1 and CN2 are connected internally Mating Housing Terminal HRS DF11 8DS or equivalent HRS DF11 SC or equivalent 7 1 Kgf cm 0 Pin No 1 2 Function RCG RC...

Page 9: ...gnment Pin No 1 3 2 Assignment Diagram M x a imum mounting torque 18Kgf cm AC L AC N 2 1 6 5 Control Pin No Assignment HRS DF11 6DP 2DS or equivalent CN3 Mating Housing Terminal HRS DF11 6DS or equiva...

Reviews: