7
Repeater mode parameters
Parameterization of the device is done from the ETS. The description of each parameter is shown in this chapter.
7.1.1
General
Nombre
Manual function
Valores
Disabled / Pass all telegrams / Pass all Physical telegrams / Pass all Group telegrams
Descripción Configuration setting for telegram routing when the Manual Function is active.
Nombre
Switch-off time for Manual Function
Valores
10 min / 1 hour / 4 hours / 8 hours
Descripción After expiry of this time period the Manual Function is switched off automatically.
7.1.2
Main line
For Group Telegrams and Physical Telegrams the setting “transmit all” is intended only for testing purposes. Please do not
use for normal operation.
Name
Telegram routing
Values
Group and Physical: route / Configure
Description
-
Route: all telegrams are routed
-
Configure: the following parameters must be set manually.
Name
Physical telegrams
Values
Transmit all (not recommended) / Block
Description
-
Transmit all:
Physical telegrams are all routed
. It is used only for tests, it shouldn´t be used
for normal operations.
-
Block:
Physical telegrams are all blocked.
Name
Physical/Group telegrams: Repetition if errors on main line
Values
No / Up to 3 repetitions / Only one repetition
Description
After main line transmission error (e.g. due to missing receiver) Physical telegrams
- No: Are not repeated
- Up to 3 repetitions: Are repeated max. 3 times
- Only one repetition: Are repeated once
Name
Telegram confirmation on main line
Values
If routed / always