Be126 NFPA20 Installation Manual V4XX - 03 Nov - 2018 page 32
32
Section 33.0 - PROGRAMMING PARAMETERS, SETTINGS & OPTIONS
You can program the Be126 in OFF mode of operation only. Push the
[OFF]
button
to enter the OFF mode of
operation. Push
[MENU]
: the
Main Menu
appears on display. Push
[ ↓ ]
on
[ ↑ ]
to browse the menu list.
Repeatedly push
[ ↑ ]
to reach the top of the
Main Menu
. When you find the sub-menu that you are looking for,
push
[→]
to enter the sub-menu; the first parameter of the list will appear on the screen (see the example
below).
Display
Instructions
>START DELAY
2 sec
STOP DELAY
OFF
START DELAY
8 sec .
STOP DELAY
OFF
.
>START DELAY
8 sec
STOP DELAY
OFF
_________________________
SAVE?
< YES NO >
_________________________
A) - The first parameter of the list is back-lit and an arrow notice you that the
parameter is currently selected.
B) - Push the
[→]
button to enter the parameter programming field; the setting of the
parameter is back-lit. Push
[ ↓ ]
or
[ ↑ ]
to modify the parameter as requested by you.
C) - Push the
[
←
]
button to return. You can push the
[ ↓ ]
button to choose an other
parameter or push again the
[
←
]
button to exit programming.
D) Before quitting, the Be126 asks for a confirmation. Push the
[
←
]
to quit & save the
modification or push
[→]
to quit without saving the modification.
NOTE:
you have 60 seconds to make a decision. After one minute, the Be126
automatically quit the programming without saving the setting.
We recommend that you limit the access for programming by using passwords.
The USER password (see section 10.0) limits the access to the following menus & parameters
[SET DATE & TIME]
[TEST SCHEDULER]
[DISPLAY & LANGUAGE]
[DATA COMMUNICATION]
[MAINTENANCE]
[MISCELLANEOUS]
The OEM password (see section 11.0) limits the access to the following menus & parameters
[ENGINE TYPE ]
[ENGINE PARAMETERS]
[ROTATIONAL SPEED]
[TANK FUEL LEVEL]
[OIL PRESSURE]
[ENGINE TEMPERATURE]
[WATER PRESSURE]
[AUXILIARY °C]
[MISCELLANEOUS]
[MAINS PARAMETERS]
[RESTORE DEFAULTS]
[CLEAR MEMORY]
[CLEAR EVENTS]
[CLEAR N° START]
The OEM password has priority over USER password. In other words, using an OEM password you can pay
access to the