Be126               NFPA20 Installation Manual    V4XX  - 03 Nov  -  2018                                               page 11 

 

11 

2.4.5  ENGINE PROTECTION MODE TEST FACILITY 

 
 You enable the 

‘Engine Protection Mode’ by connecting the terminal JF-10 to battery minus. This setting is used 

in general purpose diesel water pump for various applications: farm irrigation systems, pumping stations for 
water supply systems, automatic diesel pumping stations. In these applications the Be126 plays the additional 
important role of protecting the diesel engine. 
 
You have at your disposal a wide choice of test options: 

 

start the engine directly by using the scheduler without using a drain valve 

test the engine starting circuits holding the fuel valve closed 

run the engine on a daily basis for a programmed time 

test the engine at nominal or idle speed 

 
The settings to configure test are included in the

 

[MISCELLANEOUS]

 and 

[TEST SCHEDULER]

 

sub-menu (see 8.0).  

 
  

Section 3.0  -  SYSTEM STATUS PAGE  

 

The Be126 displays the ‘System Status Page’ when you push the 

[HOME] 

button, when you change a mode of 

operation and when the Be126 starts the engine.  
 

Example of a typical ‘System Status Page’  

 

    AUTO       

MANUAL   

      OFF   

 F

 

 

START DEMAND   

OFF

     

WATER PRESSURE 12.1  

NOT RUNNING

 

SA       16:16:13               12 / 09 / 15 

 

The mode of operation is indicated by a back-lighted message (in the example:  

[MANUAL]

). The 

[START DEMAND OFF]

 means that there are no requests to start 

the engine. The message 

[START DEMAND ON] 

indicates that Be126 detected a 

start of request (or in other words, a possible fire situation). When you configure 
the pressure transmitter, the Be126 indicates the value of the water pressure. The 
fourth line indicates the status of the engine: running or not. The last line, on the 
bottom, displays the real time clock. To browse the engine instruments push the 
 

[ ↓ ]

 arrow. To open the main menu page push the 

[MENU] 

button. 

 

 

2.4.6  TEST LAMP FACILITY 

 
 

To test all LED indicators (LED stands for ‘Light Emitting Diode’) push and hold the LAMP TEST pushbutton 

(see front fascia description in section 1.1). 
 

Section 3.1  -  ENGINE INSTRUMENTS PAGE  

 
 

Example of an engine instrument page 

(to enter this page push the 

[HOME] 

button and then, push 

[ ↓ ]

.

 

 

     (RPM)    

  1500 

F

 

 

   ENGINE

 

 

   
     (BAR)             (°C)            FUEL (%)   

    6.5        88.5        92

 

 

 
This is the most important instrument page of the engine. It displays the main 
information about Rotational Speed, Oil Pressure, Coolant Temperature and Fuel 
Level in the tank. 
 
 To browse other pages push the 

[ ↓ ]

 arrow. To return to the 

‘System Status 

Page

’ push the 

[HOME]

 button at any time. 

 

 
 
 
 
 
 
 
 

Summary of Contents for BE126

Page 1: ...the Be124 to the buyer with the Default parameters at no extra charge The buyer shall furnish sufficient information on any alleged defects in the product so as to enable BD to determine there cause...

Page 2: ...0 Dimensions 42 0 Display 3 0 Display Languages 27 0 Display Settings 27 0 D Plus Monitoring 37 0 Dynamo Alternator monitoring 37 0 Engine Be126 Status Page 3 0 Engine Running 37 0 Engine Alarms Bypa...

Page 3: ...serve Fuel 16 0 Service 1 2 3 15 0 Settings Parameters 33 0 Scheduler 8 0 Speed error 14 0 Speed settings 14 0 Speed indication 3 1 Sensors Fuel C Oil 40 3 3 Sensors test 31 0 Service Maintenance 15 0...

Page 4: ...PTION Page 9 2 4 TEST MODE OF OPERATION DESCRIPTION Page 10 2 4 X UNI EN 12845 NFPA EPM MANUAL TEST FACILITIES Page 10 3 0 LED INDICATORS DISPLAYS DESCRIPTION Page 11 3 1 BE126 STATUS PAGE INSTRUMENTS...

Page 5: ...R SETTINGS Page 23 20 0 AUXILIARY TEMPERATURE ALARMS SETTINGS Page 24 21 0 MISCELLANEOUS FUNCTIONS SETTINGS Page 25 22 0 MAINS PARAMETERS PROGRAMMING Page 26 23 0 RESTORING FACTORY SETTINGS Page 26 24...

Page 6: ...ICATIONS Page 38 39 0 SOFTWARE UPGRADES REVISIONS Page 38 40 0 TERMINAL DESCRIPTION Page 39 41 0 TYPICAL WIRING DIAGRAM Page 43 42 0 REAR VIEW AND DIMENSIONS Page 44 WARNING The Be126 can start the en...

Page 7: ...you connect MCB MOD BUS compatible battery chargers The Be126 monitors the power utility as well You can use the Be126 controller in standard diesel engine pump water station by enabling the Engine Pr...

Page 8: ...EN applications the Be126 ignores the PREGLOW setting Push the button to open the engine instruments page In case the battery voltage drops below 6 volts the Be126 may reset the software The controlle...

Page 9: ...t nominal speed When the engine is running use the display arrows to browse the instruments If you get lost during navigation push the HOME button the display will open the System Status Page Based on...

Page 10: ...e sections 10 9 7 1 2 3 4 5 of the UNI EN 12845 Standard Note If after a minute time the pressure fails to drop down the Be126 will trigger the alarm TEST FAILURE WARNING see the section 21 0 2 to cha...

Page 11: ...NUAL OFF F START DEMAND OFF WATER PRESSURE 12 1 NOT RUNNING SA 16 16 13 12 09 15 The mode of operation is indicated by a back lighted message in the example MANUAL The START DEMAND OFF means that ther...

Page 12: ...HOME button and then repeatedly push the button HOURS 18 5 F SERVICE S1 H S2 H S3 H 82 182 282 This page provides information about running hours and maintenance timers When a timer reaches a zero cou...

Page 13: ...PN106 XXX AIR FILTER BAR SPN107 XXX See above TURBO BAR SPN102 XXX EXHAUST C SPN173 XXX See above LOAD SPN92 XX ECU ENGINE HOURS XXXXXXX See above COOLANT SPN111 XXX COOLANT BAR SPN109 XXXX See above...

Page 14: ...ENGINE TYPE ENGINE PARAMETERS ROTATIONAL SPEED MAINTENANCE TANK FUEL LEVEL OIL PRESSURE ENGINE TEMPERATURE 12 0 13 0 14 0 15 0 16 0 17 0 18 0 choose the suitable ECU that matches your engine program m...

Page 15: ...ge in case of an alarm push the HOME button ALARM 1 10 LOW OIL PRESSURE SHUTDOWN 0 8 BAR Day HH MM SS DD MM YY ALARM 2 10 LOW OIL PRESSURE WARNING 2 8 BAR Day HH MM SS DD MM YY Use or to browse additi...

Page 16: ...s the NODE 1 Battery Charger 2 features the NODE 2 Connect Battery Charger 1 to battery set 1 Battery Charger 2 to battery set 2 Default MODBUS node for BE126 is 3 The nodes 1 2 are reserved for the b...

Page 17: ...sage CLEAR PASSWORD DONE d From now on you will no longer need a password to program the Be126 Note the password 0000 is not allowed If you have lost the password see section 35 0 for additional help...

Page 18: ...to JM8 9 terminals Section 13 0 4 PREGLOW TIME OFF PREGLOW mode 1 These parameters are disabled in NFPA APPLICATIONS Section 13 0 5 STOP SOLENOID 2 sec BELT BREAK OFF 1s 5mins 3 30VDC STOP SOLENOID y...

Page 19: ...AUTO mode after engine starting the engine can run at IDLE SPEED then after an IDLE TIME see 14 0 3 it will reach the nominal speed You can set an IDLE SPEED only supposing your engine has the CANbus...

Page 20: ...cond bypass alarm delay You are required to connect a resistive sensor to the JM 5 input and to correctly configure the response curve see below IMPORTANT NOTE ABOUT FUEL LEVEL MEASUREMENT In order to...

Page 21: ...e LOW BAR WARNING By keeping both alarms to OFF the display will not indicate the oil pressure measurement Section 17 0 2 POINT 1 BAR 0 0 BAR POINT 1 OHM 10 OHM POINT 2 BAR 2 0 BAR POINT 2 OHM 51 OHM...

Page 22: ...PERATURE in addition to the TEMPERATURE sensor connected to JM 3 you are required to set up at least one TEMPERATURE alarm example LOW C WARNING By keeping all alarm with the option to OFF mode the di...

Page 23: ...the high water pressure alarm When the water pressure drops below the LOW PRESSURE setting the Be126 turns on the low water pressure alarm The alarms are recorded in the Memory Events Register togethe...

Page 24: ...lows you to select a 4 20mA transmitter or a 0 10V transmitter You can also set up the full scale of the transmitter see next Factory setting is 4 20mA IMPORTANT NOTE ABOUT AUXILIARY TEMPERATURE MEASU...

Page 25: ...imeout for the drain output terminal JB 5 It works in TEST mode of operation or when the scheduler is active After activating the drain output if the Be126 does not detect a drop of pressure before ex...

Page 26: ...e see above The range of the setting is in between 60 up to 600Vac The option OFF is provided to totally disable the Voltage alarm monitoring 22 0 3 UNDER HZ OFF OVER HZ OFF When the frequency falls b...

Page 27: ...ion 24 0 CLEAR THE MEMORY select the CLEAR MEMORY sub menu see section 4 0 Display Instructions for restoring the factory settings Defaults CLEAR MEMORY YES NO HOLD LEFT 5SEC CLEAR MEMORY DONE A Push...

Page 28: ...le for all applications English Italian Spanish French Section 28 0 PUSH BUTTONS TEST Push the OFF button to enter the OFF mode of operation Push the MENU button to open the Main Menu Use the or arrow...

Page 29: ...Instructions OUTPUTS TEST KEY UP DOWN SELECTION KEY RIGHT OUTPUT ON JC1 OUT 1 WARNING THIS PROCEDURE MUST BE CARRIED OUT BY QUALIFIED ONLY PERSONNEL THE ENGINE MAY START OR YOU CAN INADVERTENTLY ACTI...

Page 30: ...HIGH PRESSURE or a LOW PRESSURE alarm The Be126 System Status Page see 3 0 displays the water pressure measurement of the pressure transmitter connected to the terminal JM 1 The Be126 automatically up...

Page 31: ...you change the days C Push the button to choose the slow mode In this way by using the or arrows you can browse the 288 samples one every five minutes of a chosen day Section 32 1 DOWNLOADING WATER PR...

Page 32: ...modify the parameter as requested by you C Push the button to return You can push the button to choose an other parameter or push again the button to exit programming D Before quitting the Be126 asks...

Page 33: ...ously monitors your actions If you forget to make a decision save or quit or you remain in a programming page for over one minute without taking decisions for at least one minute the BE126 automatical...

Page 34: ...rnings and pre alarms will allow the engine to run In NPFA mode only over speed alarm is allowed to shutdown the engine 36 0 1 Clock Memory and System alarms CLOCK ERROR WARNING Real time clock failur...

Page 35: ...XXXRPM Engine rotational under speed shutdown You can program the limit and a bypass alarm time for it In NFPA EN applications the alarm does not shut down the engine section 14 0 START 1 FAILURE WARN...

Page 36: ...ode of operation You can monitor the ambient temperature or other critical part of the system See section 20 0 about the AUXILIARY C sub menu AUX C SENDER OPEN It indicates the failure of the temperat...

Page 37: ...Be126 terminates the crank when the voltage measured on the D W L terminal rises above the CRANK VDC setting When the engine starts running the voltage of the D WL increases The point to terminate the...

Page 38: ...Ph Ph Measurement precision 1 F S Impedance 2 M Ohm Resolution 1Vac Mains Frequency nominal frequency 20 0 Hz up to 70 0 Hz Precision 1 F S Accuracy 0 1Hz Digital Inputs open circuit voltage of approx...

Page 39: ...NOMINAL SPEED REQUEST This output energizes when you are required to run the engine at nominal speed By default the IDLE speed is disabled The output is immediately energized when the Be126 activates...

Page 40: ...tion of the START 1 pilot driver relay JC 7 RELAYS SUPPLY Positive Out This is the positive supply for the relays lamps connected to the outputs This supply is taken from the battery 1 2 via internal...

Page 41: ...own the engine after a programmable time see FUEL parameters in the section 16 0 JF 6 MANUAL TEST SWITCH You are required to connect here the manual start button for testing the engine in accordance w...

Page 42: ...justments and calibration Consult the section 19 0 to set up the pressure measurement JM 2 AUXILIARY TEMPERATURE This input monitors an auxiliary temperature transmitter See section AUXILIARY C submen...

Page 43: ...JP 1 2 3 4 5 6 L1 L2 L3 N N R S T MAIN PICK UP AUX PICK UP B C 1 FAILURE B C 2 FAILURE TEMPERATURE WATER PRESSURE FUEL LEVEL TEST BUTTON WATER LEVEL EMERGENCY OIL PRESSURE ENGINE PROTECTION DIGITAL I...

Page 44: ...ection 42 0 REAR VIEW AND DIMENSIONS 250 mm Recommended panel cut out 171mm X 239mm 169 mm Steel Cover Silicon Gasket 185 mm 22 mm 45 mm JB JM JA JF JI JG JN JH JC Supply 36Vdc max DB9 RS232 MODEM JL...