Standards and certifications • Requirements for immunity to disturbances (immunity)
Sect
ion 5
Sta
nda
rds a
nd
certi
fica
tion
s
215
Automation PC 820 User's Manual V 1.20
4.5 Conducted disturbances
4.6 Magnetic fields with electrical frequencies
4.7 Voltage dips, fluctuations and short-term interruptions
Test carried out according to
EN 61000-4-6
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Limits according to
EN 61800-3
AC power I/O
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
criteria A
DC power I/O
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
criteria A
Functional ground connections
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
criteria A
Signal connections >3 m
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
criteria A
Table 149: Test requirements - Conducted disturbances
Test carried out according to
EN 61000-4-8
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Test direction x, test in the field of
an induction coil 1 m x 1 m
30 A/m, criteria A
30 A/m, criteria A
Test direction y, test in the field of
an induction coil 1 m x 1 m
30 A/m, criteria A
30 A/m, criteria A
Test direction z, test in the field of
an induction coil 1 m x 1 m
30 A/m, criteria A
30 A/m, criteria A
Table 150: Test requirements - Magnetic fields with electrical frequencies
Test carried out according to
EN 61000-4-11
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
AC power inputs
Voltage dip
70% (30% reduction), 0.5 periods,
criteria B
-
AC power inputs
Voltage dip
40% (60% reduction), 5 periods,
criteria C
-
AC power inputs
Voltage dip
40% (60% reduction), 50 periods,
criteria C
-
AC power inputs
Voltage interruptions
< 5% (> 95% reduction), 250
periods, criteria C
-
AC power inputs
-
20 interruptions, 0.5 periods,
criteria A
Table 151: Test requirements - Voltage dips, fluctuations, and short-term interruptions
Summary of Contents for 5PC820.SX01-00
Page 2: ...2 Automation PC 820 User s Manual V 1 20...
Page 4: ...4 Automation PC 820 User s Manual V 1 20...
Page 6: ...6 Automation PC 820 User s Manual V 1 20...
Page 80: ...80 Technical data Individual components Automation PC 820 User s Manual V 1 20...
Page 108: ...108 Commissioning Known problems issues Automation PC 820 User s Manual V 1 20...
Page 304: ...304 Automation PC 820 User s Manual V 1 20 Figure index...
Page 310: ...Table index 310 Automation PC 820 User s Manual V 1 20...
Page 312: ...Model number index 312 Automation PC 820 User s Manual V 1 20 9S0000 01 020 26 193...