background image

BERMAD 

Fire Protection

400 Series

FP 400E Materials Specifications

Construction Materials

The BERMAD FP 400E valves are available in a variety of materials to 

ensure optimal suitability for a wide range of applications. When the 

valve is designed for external corrosive environments and/or internal 

corrosive fluid, an adequate Body and Cover resistant material shall be 

used. 
It is recommended to apply the “High Build Epoxy Fusion-Bonded with 

UV Protection, Anti-Corrosion” specification (as shown below) when 

the valve is used in corrosive environments such as seashore, 

chemical environments or petrochemicals and other industrial 

processing plants.
Note: in case of Seawater service, brackish/ desalinated water or if 

Foam Concentrate is used please refer to BERMAD FS 400E series 

engineering  data.

Standard Configurations

Item 

Number

Description

Code

FP-C-PR

FP-C-ER

FP-S-ER

1

Cover

Ductile Iron

Ductile Iron

Cast Steel

2

Valve Body

Ductile Iron

Ductile Iron

Cast Steel

3

Elastomeric Assembly

NR with VRSD*

NR with VRSD*

NR with VRSD*

4

External Bolts / Nuts

S.S. 316

S.S. 316

S.S. 316

5

Coating

Polyester

H.B. Epoxy

H.B. Epoxy

*  VRSD - Vulcanized Radial Seal Disk

Specifications

Castings 

 Ductile Iron to ASTM A536 65-45-12 (coated)

 Cast Steel ASTM A216 Grade WCB (coated)

 Nickel Aluminum Bronze ASTM B148 C95800 

 Stainless Steel 316 ASTM A351 Grade CF8M 

 Hastelloy C-276 

Standard Bolting:

 Stainless Steel 316 to ASTM A320 Gr.B8F

 

Option: Internal Spring - S.S. 302 or Inconel 

Elastomer

 NR, Polyamide fabric reinforced Polyisoprene,    

  Temperature Rating 50°C  

 NBR, Polyamide fabric reinforced Nitrile (Buna-N),  

  Temperature Rating 80°C

 EPDM, Polyamide fabric reinforced Ethylene-

Propylene, Temperature Rating 90°C

Coating 

 

 Electrostatic Powder Coating Polyester

 High Built Epoxy Fusion-Bonded with UV  

  Protection, Anti-Corrosion

 Color: Fire Red to RAL 3002

Note: 

Internal & External coating applied on Ductile Iron 

 

or Cast Steel Castings only.

Material

End Connection 

Standard Inlet & 

Outlet

Class  

& Type

Max. working 

Pressure

psi

bar

Ductile Iron

Flanged ANSI B16.42

#150RF

250 

17.4 

Flanged ISO 7005-2

PN16

235 

16

Grooved ANSI C606

250

250 

17.4

Threaded ISO-7-RP/NPT 

250

250 

17.4

Cast Steel

Flanged ANSI B16.5

#150RF

250 

17.4

Flanged ISO 7005-2

PN16

235 

16

Stainless 
Steel

Flanged ANSI B16.5

#150RF

250 

17.4

Flanged ISO 7005-2

PN16

235 

16

Ni-Al 
Bronze

Flanged ANSI B16.24

#150RF

250 

17.4

Flanged ISO 7005-2

PN16

235 

16

Pressure Rating

Notes:

1. To attach a grooved valve to flanged line or vice versa, apply a grooved- 
  flange adapter suited to the designated conditions.
2. Factory pressure testing: Each valve is tested at 375 psi (26 bar)
3. Water Temperature: 0.5 - 50ºC (33 - 122ºF) for standard construction.
4. Standard flange facing: Raised Face (RF), Serrated Finish. 
  Flat Face (FF) flanges available on request.

2

3

1
4

2

5

Summary of Contents for FP 400E

Page 1: ...ing resilient drip tight sealing The elastomeric assembly is carefully balanced and peripherally supported to avoid tension and protect the elastomer resulting in long life controlled actuation even u...

Page 2: ...TM B148 C95800 Stainless Steel 316 ASTM A351 Grade CF8M Hastelloy C 276 Standard Bolting Stainless Steel 316 to ASTM A320 Gr B8F Option Internal Spring S S 302 or Inconel Elastomer NR Polyamide fabric...

Page 3: ...187 Valve flow coefficient Kv or Cv Equivalent Pipe Length Leq Flow resistance or Head loss coefficient Cv 1 155 Kv Where Kv Valve flow coefficient flow in m3 h at 1bar Diff Press Cv Valve flow coeffi...

Page 4: ...ed Threaded LG a d a RG H L T a d a RT H a d LF RF H a b C b b W Flanged Grooved Threaded Size DN mm inch 50 2 80 3 100 4 150 6 200 8 Grooved LG mm 205 250 320 415 500 W mm 120 175 200 306 365 H mm 74...

Page 5: ...ved Threaded LG a d a RG H L T a d a RT H a d LF RF H a b C b b W Flanged Grooved Threaded Size inch 2 3 4 6 8 Grooved LG inch 81 16 913 16 125 8 165 16 195 8 W inch 4 67 8 77 8 121 16 143 8 H inch 21...

Page 6: ...eluge Valve according to the relevant illustration 7 All additional accessories although not packed together with the BERMAD Deluge Valve must be installed as shown in the relevant P ID and other illu...

Page 7: ...Service signs in the area protected by the system Inspection and Testing 1 Warning Do not turn the water supply off to make repairs without placing a roving fire patrol in the area covered by the sys...

Page 8: ...ling Parts Breakdown Lifting Ring Body Diapragm Assembly Cover Disk Bolt Bolt Valve name plate bermadfire bermad com www bermad com The information herein is subject to change without notice BERMAD sh...

Reviews: