10
400E-Y Deluge Valve
3.1.7
Model 5DC Trim Illustration: Hydraulic Pressure Control
Item Description
Qty Note
1
400E-Y Deluge Valve
1
5
1A
Alarm Test Valve 1/2"
1
8
2A
Gauge Valve 1/4"
2
8
2B Restriction
Orifice
2
2R
Pressure Reducing Valve, 2UL
1
3A
Pressure Gauge 4"
2
2, 8
4B
Priming Strainer 1/2"
1
5A
Drain Valve
1
1, 4, 8
2R
Pressure Reducing Pilot
1
7B
Priming Check valve 1/2"
1
15B
Manual Emergency Release
1 1,
9
18B
Priming Valve 1/2" Ball Valve
1
19A
Drip Check Device 1/2"
1
8
26B
Hydraulic Relay Valve (HRV)
1
F
Fittings and Tubing
6
Optional System Items:
P Pressure
Switch
I
Valve Visual Position Indicator
S
Valve Limit Switch
W Water
Motor
Alarm
Notes:
(1) Shall be UL Listed in accordance with UL 258
(2) Shall be UL Listed in accordance with UL 393
(3) Shall be UL Listed in accordance with UL 753
(4) For 1½ & 2”: ¾” Drain Valve ; 2½ & 3”: 1½” Drain Valve & 4”
and larger: 2” Drain Valve
(5) Shall be UL Listed for fire protection service
(6) Construction material Brass/S.S 316 or corrosion resistant
equivalent
(7) Items marked by 'B' standard Trim components provided in
the Trim package
(8) Items marked by 'A' are required trim components for the
proper installation and use of the deluge valve and are not
provided in the Trim package. These items must be obtained
from Bermad or an outside supplier prior to installation
package of the deluge valve and trim.
(9) Manual Emergency Release may be Model B (open
Bracket) or Model D (with box)