background image

6

CONTROL WIRING

1.

Use min. 600 volts, NEC Class 1 insulated wire for all control

circuit wiring.

2.

Use a crimp-on type fork terminal on the wire ends that attach

to the control terminal board if more than one connection is

to be made under the terminal screw.

3.

On units not provided with internal contactor (3 & 5 KW), refer

to Figure 4 for wiring diagram. 

Note: Thermostat and control circuit wiring must be suitable

to handle the full load of the heater (example HUHAA520 is

rated 24 amps)

4.

On  units  provided  with  internal  contactor (units  rated  7  KW

and  higher)  refer  to  Figure  5  for  wiring  diagram.    Control

wiring must be rated minimum 18 AWG.

LINE  VOLTAGE  IS  PRESENT ON  SOME  OF  THE  TERMI-

NALS  ON  THE  CONTROL TERMINAL BOARD.    ALWAYS

DISCONNECT THE POWER FROM THE HEATER BEFORE

MAKING ANY CONNECTIONS TO THE CONTROL BOARD

TO PREVENT ELECTRIC SHOCK HAZARD.

MT-1

MT-2

2-STAGE
INTERNAL
THERMOSTAT

BLACK

RED

RED

BLACK

P2

H2

F 1

F 2

S

REMOTE SUMMER
FAN SWITCH (MRFS-1)
OR SUMMER FAN
SWITCH MCFS (MANUAL)

P1

H1

REMOTE SUMMER FAN
SWITCH (HUHAARFS-1) OR
SUMMER FAN SWITCH
HUHAAFS (MANUAL)

HUHAA MT-2

HUHAA MT-1

Figure 4. Control Terminal Board
(for Heaters Without Contactors)

Mounting

Basic Model

Height

Width

Depth

Weight

No.

in (mm)

in. (mm)

in. (mm)

lbs. (kg)

!

Table 4. Specifications

HUHAA320

HUHAA324

HUHAA327

HUHAA348

HUHAA520

HUHAA524

HUHAA527

HUHAA548

HUHAA720

HUHAA724

HUHAA727

HUHAA748

HUHAA1020

HUHAA1024

HUHAA1027

HUHAA1048

HUHAA1520

HUHAA1524

HUHAA1548

HUHAA2020

HUHAA2024

HUHAA2048

HUHAA2524

HUHAA2548

HUHAA3020

HUHAA3024

HUHAA3048

HUHAA4024

HUHAA4048

HUHAA5020

HUHAA5024

HUHAA5048

16

(406.4)

21-3/4

(552.5)

21-3/4

(552.5)

30

(76.2)

30

(76.2)

14

(355.6)

19

(482.6)

19

(482.6)

26-5/8

(676.4)

26-5/8

(676.4)

8-1/2

(214.4)

8-1/2

(214.4)

13-3/4

(346.8)

13-3/4

(346.8)

18-1/8

(457.2)

27 (12.2)

27 (12.2)

27 (12.2)

27 (12.2)

27 (12.2)

27 (12.2)

27 (12.2)

30 (13,6)

38 (17.2)

38 (17.2)

38 (17.2)

38 (17.2)

38 (17.2)

38 (17.2)

38 (17.2)

38 (17.2)

53 (24.0)

53 (24.0)

53 (24.0)

60 (27.2)

60 (27.2)

60 (27.2)

93 (42.3)

93 (42.3)

93 (42.3)

93 (42.3)

93 (42.3)

119 (54.0)

119 (54.0)

119 (54.0)

119 (54.0)

119 (54.0)

WARNING  

NOTES:
1. THIS  STYLE  CONTROL TERMINAL BOARD

USED 

WITH 

MODELS 

HUHAA320,

HUHAA324, 

HUHAA327, 

HUHAA520,

HUHAA524, HUHAA527.

2. WHEN UNIT IS WIRED FOR SINGLE PHASE,

JUMPER  H1  TO  H2.    IF  SINGLE  POLE
THERMOSTAT IS USED WITH SINGLE PHASE 
UNIT, CONNECT THERMOSTAT LEADS TO 
P1 AND H1.

3. EXTERNAL LINE VOLTAGE THERMOSTATS

SHOULD  BE  TREATED  AS  SINGLE  STAGE
ONLY.

Summary of Contents for HUHAA520

Page 1: ...n accordance with the National and Local Electrical Codes and the heater must be grounded as a pre caution against possible electric shock 3 Verify the power supply voltage coming to heater matches th...

Page 2: ...thread ed rod sizes required Observe the detailed procedures in the following installation instructions The heater may also be suspended from the wall or ceiling by means of an optional mounting brack...

Page 3: ...und wire should be connected before other connections are made 6 The power terminal board is equipped with box terminals sized to accept the correct size power supply wire Wire rated at 600 V and 60 C...

Page 4: ...any other wiring The element lead wire marked B1 which is factory connected to the power termi nal block terminal located closest to the elements must be moved to terminal B on the three phase termin...

Page 5: ...D FOR SINGLE PHASE POWER FIELD WIRED FOR THREE PHASE POWER B 3 PHASE BLOCK FACTORY WIRED FOR SINGLE PHASE POWER C1 D1 D1 C1 C D B C D 3 PHASE BLOCK B 3 PHASE BLOCK FIELD WIRED FOR THREE PHASE POWER C1...

Page 6: ...AA MT 2 HUHAA MT 1 Figure 4 Control Terminal Board for Heaters Without Contactors Mounting Basic Model Height Width Depth Weight No in mm in mm in mm lbs kg Table 4 Specifications HUHAA320 HUHAA324 HU...

Page 7: ...TERNAL THERMOSTAT MHRT HEAT RECOVERY THERMOSTAT OR REMOTE FAN SWITCH MRFS 2 BLACK RED RED BLACK C R W1 W2 F2 F1 G TR T S S REMOTE SUMMER FAN SWITCH MRFS 1 FAN RELAY FOR MRFS 2 AMD MHRT SUMMER FAN SWIT...

Page 8: ...ould be returned to the nearest Marley authorized service center or the Marley Engineered Products Service Center and we will repair or replace at our option at no charge to you with return freight pa...