background image

Horizontal Discharge (Rod-mount from Ceiling)

1. Install four threaded mounting rods in the threaded holes and

secure in place using lock nuts.  (See Table 2).

2. Securely attach the four mounting rods to the ceiling.  (Refer

to Table 1 for wall and ceiling clearances, and Table 2 for
mounting rod spacing).

Vertical Discharge (Rod-Mount from Ceiling)

1. Remove bolts  from the threaded holes in the back of the

heater.

2. Install four threaded mounting rods in the threaded holes and

secure in place using lock nuts.

3. Securely attach the four mounting rods to the ceiling.  (Refer

to Table 1 for wall and ceiling clearances, and Table 3 for
mounting rod spacing dimensions.)

Table 3. Rod Thread Type and Spacing Dimensions, inches (mm) 
for Vertical Discharge

Rod Thread

Unit

Type

E

F

G

H

3 - 5 kW

6

9

3

/

4

2

4

1

/

16

5

/

16

- 18

(152.4)

247.7)

(50.8)

(103.1)

7.5 - 20 kW

8

7

/

8

14

5

/

8

2

5

1

/

8

(225.6)

(371.6)

(50.8)

(130.3)

25 - 30 kW

3

/

8

- 16

14

1

/

2

21

1

/

4

2

3

/

16

6

3

/

16

(308.1)

(539.8)

(55.6)

(157.2)

WIRING

Branch Circuit (Power)

1. Connect heater only to the voltage, amperage and frequency

specified on the nameplate.

2. Field wiring must be properly sized to carry the amperage in

accordance with the NEC.

3. The access door is hinged.  There are either one or two

screws accessible from the bottom, that must be removed to
gain access.  

4. A knockout is provided in the back of the heater close to the

power terminal block and the control terminal board. The 
control terminal board knockout is 1/2 inch (12.7 mm) conduit
size.  The power terminal block knockout is multiple diame-
ter.  Use the diameter that fits the required conduit size.

5. A ground terminal is provided near the power terminal board.

The ground wire should be connected before other connec-
tions are made.

6. The power terminal board is equipped with box terminals

sized to accept the correct size power supply wire.  Wire
rated at 600 V and 60° C is satisfactory for the heater branch
circuit.  Either aluminum or copper wire is satisfactory for
connection to the heater power terminal board box terminal.
Copper wire is recommended and must be used with built-in
disconnect switch.

7. Each heater has a wiring diagram affixed to the inside of the

access door.  Consult this diagram before making any field
connections.

Important Note - Installation Screw Lug Torque: 
During transportation it is possible screw lug connections can
loosen. After installation, before power is turned on to the
heater, check all screw lug connections for tightness to a 
recommended minimum torque of 35 in-lbs. (3.9 N-m). 

8. Single or three-phase power connections may be used with

heater models HUHAA520, HUHAA524, HUHAA720,
HUHAA724, HUHAA1020, HUHAA1024  and HUHAA1520.
These units are factory wired for single phase operation.  If
these heaters are  for use with three-phased power, recon-
nect  the wires as indicated in the wiring diagram attached to
the heater.  Additional information can be found by looking at
the wiring illustrations in Figures 3a and 3b and following the
directions shown below.

On models HUHAA520, HUHAA524, HUHAA720, HUHAA724,
HUHAA1020 and HUHAA1024 (Figure 3a), move only the two
wires marked “A1” and marked “B1”; do not move or change any
other wiring.  The element lead wire marked “B1” which is facto-
ry connected to the power terminal block (terminal located clos-
est to the elements) must be moved to terminal “B” on the three-
phase terminal block.  

The relay (contactor) lead wire “A1” must be moved from the
end terminal of the power terminal block (terminal closest to the
contactor or control terminal board) to the “A” terminal of the
lower terminal block (center terminal).

Model HUHAA1520 (Figure b) has two three-phase terminal
blocks located adjacent to the relays (contactors).  Move only
the two wires marked “C1” and “D1” on each of these two three-
phase terminal blocks to terminal “B”.  Do not move or change
any other wires. 

9.

Electrical Accessories, either kits or factory-installed
options, are shown connected by a dashed line on the
heater wiring diagram.

10. 208/240 Volt Heater: The heaters are wired for 240V from

factory. When heater is to be connected to 208V supply, the
transformer leads have to be interchanged. For units rated
30/40kW or higher, interchange ORANGE and RED primary
leads. The black colored lead is the COMMON for the trans-
former (50VA) provided with the high wattage units. For
lower kW rated heaters, interchange BLACK and RED pri-
mary leads. The WHITE colored lead is the COMMON for
the control transformer provided with these heaters. Always
refer to the wiring diagram on the cover of the heater before
making this reconnection of transformer primary leads.

Control Wiring

1. Use min. 600 volts, NEC Class 1 insulated wire for all control

circuit wiring.

2. Use a crimp-on type fork terminal on the wire ends that

attach to the control terminal board if more than one connec-
tion is to be made under the terminal screw.

3. On units not provided with internal contactor (3 & 5 KW),

refer to Figure 4 for wiring diagram. 

Note: Thermostat and control circuit wiring must be suitable
to handle the full load of the heater (example HUHAA520 is
rated 24 amps)

4. On units provided with internal contactor (units rated 7 KW

and higher) refer to Figure 5 for wiring diagram.  Control
wiring must be rated minimum 18 AWG.

LINE  VOLTAGE  IS  PRESENT  ON  SOME  OF  THE  TERMI-
NALS  ON  THE  CONTROL  TERMINAL  BOARD.    ALWAYS
DISCONNECT  THE  POWER  FROM  THE  HEATER  BEFORE
MAKING  ANY  CONNECTIONS  TO  THE  CONTROL  BOARD
TO PREVENT  ELECTRIC SHOCK HAZARD.

3

Figure 2. Vertical Discharge Mounting and Rod Spacing

(TOP VIEW)

Summary of Contents for HUHAA series

Page 1: ...fire do not block air intakes or exhaust in any manner Keep combustible materials such as crates d r a p e s etc away from heater Do not install behind door furniture towels or boxes 7 A heater has hot and arcing or sparking parts inside Do not use it in areas where gasoline paint or flammable liquids are stored 8 Use this heater only as described in this manual Any other use not recommended by th...

Page 2: ...all and ceiling clearances before mounting heater The heater may be mounted for either vertical or horizontal dis charge by the use of threaded rods Refer to Table 2 for thread ed rod sizes required Observe the detailed procedures in the following installation instructions The heater may also be suspended from the wall or ceiling by means of an optional mounting bracket type HUHAAB or HCMB which p...

Page 3: ...hese units are factory wired for single phase operation If these heaters are for use with three phased power recon nect the wires as indicated in the wiring diagram attached to the heater Additional information can be found by looking at the wiring illustrations in Figures 3a and 3b and following the directions shown below On models HUHAA520 HUHAA524 HUHAA720 HUHAA724 HUHAA1020 and HUHAA1024 Figur...

Page 4: ...OVERY AT OR REMOTE H HUHAARFS2 REMOTE SUMMER FAN SWITCH HUHAARFS 1 OR SUMMER FAN SWITCH HUHAAFS MANUAL HUHAA MT 2 HUHAA MT 1 HUHAA MT 2 Figure 4 Control Terminal Board for Heaters Without Contactors NOTES 1 THIS STYLE CONTROL TERMINAL BOARD USED WITH MODELS HUHAA320 HUHAA324 HUHAA327 HUHAA520 HUHAA524 HUHAA527 2 WHEN UNIT IS WIRED FOR SINGLE PHASE JUMPER H1 TO H2 IF SINGLE POLE THER MOSTAT IS USED...

Page 5: ...27 2 HUHAA2024 60 27 2 HUHAA2048 60 27 2 HUHAA2524 93 42 3 HUHAA2548 30 26 5 8 13 3 4 93 42 3 HUHAA3020 76 2 676 4 346 8 93 42 3 HUHAA3024 93 42 3 HUHAA3048 93 42 3 HUHAA4024 119 54 0 HUHAA4048 30 26 5 8 18 1 8 119 54 0 HUHAA5020 76 2 676 4 457 2 119 54 0 HUHAA5024 119 54 0 HUHAA5048 119 54 0 MODEL NO HUHAA324 DATE CODE 0395 MFG NO VOLTS AC KILOWATTS PHASE 60 HZ 208 240 2 2 3 1 MOTOR CONTROL VAC A...

Page 6: ... Products THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT WHETHER BASED UPO...

Reviews: