Locking the DALI participants or groups
individually
The gateway is in permanent manual mode.
- Press briefl y on the
key ( < 1 second) until the
desired DALI number is displayed.
The
and
LEDs display the status.
- Press the
and
keys simultaneously for at
least 5 seconds.
The DALI number selected fl ashes on the display
screen.
The DALI participant or group is locked.
- Enable bus mode (leaving permanent manual
mode).
A locked DALI participant can be controlled in
manual mode.
Unlocking the DALI participants or groups
individually
The gateway is in permanent manual mode
- Press briefl y on the key
(<1 second) until the
desired DALI number is displayed.
- Press the
and
keys simultaneously for
at least 5 seconds.
The DALI participant or group is released.
The display on the screen no longer fl ashes.
- Enable bus mode (leaving permanent manual
mode).
Connection
7571 00
15
Area
Line
Ptcp.
Nb.
230 V 50/60 Hz
L1
L2
L3
N
da+
da -
da da N L da da N L
Bus 30 V
all
Electrical connection
DALI devices from some manufacturers have
expanded functions and can be controlled. In the
case of upgrades of existing DALI installations,
remove all the corresponding control devices.
The DALI control voltage is a functional extra-low
voltage (FELV).
G
Please separate the routing of the power cables
from that of the DALI low-voltage cables.
- Connect the device.
- Connect the bus cable to the connection terminal.
Operation of the emergency lighting
The gateway can be used in emergency lighting
systems to supply central or decentralized power.
In the case of an emergency lighting system with
decentralized power supply, the emergency lighting
will be operated with individual batteries and
specialist DALI components.
G
Pay attention to the number of DALI participants
present in the emergency lighting.
Emergency lighting supplied by the central
emergency power supply
AC 230 V
AC/DC 230 V
KNX
L, N
da
KNX
DALI
DALI
L, N
da
Emergency lighting, KNX supply and the DALI
gateway are supplied by the central emergency
power supply circuit.
AC 230 V
AC/DC 230 V
KNX
L, N
da
KNX
DALI
DALI
L, N
da
Commissioning
Downloading the physical address and the
application software
- Supply power to the product from the mains
- Connect the KNX bus
- Download the physical address
- Download the application software into the
device.
Programming is not possible if the product is not
powered via the mains.
Technical characteristics
KNX power supply
30 V DC
KNX power used
Typ. 150 mW
Mains power
110 / 240 V AC±10 %
Mains frequency
50 / 60 Hz
Total power dissipated
max. 3 W
DALI voltage
16V DC
Number of DALI products (Electrical consumption
2 mA each)
max. 64
DALI transmission rate
1200 bit / s
DALI protocol
EN 62386
Length of the DALI cables
For cable cross section 1,5mm²
max. 300 m
For cable cross section 1,0mm²
max. 238 m
For cable cross section 0,75mm²
max. 174 m
For cable cross section 0,5mm²
max. 116 m
DALI connection capacity
0.2 … 4 mm² or 2 x 0.2 … 2,5 mm²
Flexible cable without lug
0,5 … 4 mm²
Flexible cable with lug
0.5 … 2,5 mm²
Operating temperature
5 °C … +45 °C
Storage temperature
-25 °C … +70 °C
Assembly width
72 mm (4 modules)
What to do if…
1
The screen displays
, the connected
DALI devices have no functions, no control
is possible
Cause :
network
voltage on the DALI
bus
Solution : correct the
installation wiring fault
2
The screen displays bc in manual mode,
control of some light fi ttings is not possible.
Cause :
the gateway is
not programmed
Solution :
program the
gateway, commission
the DALI system
3
Some DALI devices have no functions
Cause :
a load is
defective (e.g. : a lamp)
Solution :
replace the
load
Cause :
the DALI
product is defective
Solution :
replace the
defective DALI product
and reconnect
Press the keys
and
all
simultaneously
for at least 10 seconds. The DALI gateway
recognizes the DALI devices which have been
replaced and loads the necessary data.
LE
is
displayed on the screen. Repeat the operation
for each defective product.
4
Manual control is not possible by means of
the keyboard
Cause :
manual control
is not enabled
Solution :
reprogram the
device, enable manual
control (see Activating
manual mode)
Cause :
manual
control is disabled via
the bus
Solution :
enable
manual control via the
bus
5
It is not possible to control the DALI group
Cause :
DALI group
disabled via the bus or
manual control
Solution :
enable the
DALI group via the bus
and disable manual
mode
6
No DALI group can be programmed
Cause :
all the DALI
groups are disabled
via the bus or manual
control
Solution :
enable the
DALI groups via the
bus and disable manual
mode manuel
Cause :
permanent
manual mode is
enabled
Solution :
disable
permanent manual
mode
Cause :
the
programming LED is
fl ashinge
Solution :
disconnect
the product from the
bus and restart after 5
seconds
If the fault persists, re-download the
S75710015 application software.
q
q
Warranty
We reserve the right to make technical and formal
changes to the product in the interest of technical
progress.
Our products are under guarantee within the
scope of the statutory provisions.
If you have a warranty claim, please contact
the point of sale or ship the device postage free
with a description of the fault to the appropriate
regional representative.