In many cases, gas recovery will not be exact since part of the gas
remains in the recovery circuit.
Symptom
Cause
Solution
• The unit works but does not cool.
• Insufficient or excess load.
• Dirt in the condenser.
• Condenser fan defective.
• Blockage in the circuit.
• Verify the load by checking the pressure; if it is below 0.5 bars or above 5.0
bars with the unit running, restore the load and vacuum deair for at least 30
minutes and introduce 250 g.
• Clean the condenser with pressurised air.
• Connect or replace the condenser fan.
• Check the pressure; if it is below 0.5 bars with the unit running, clean the
circuit or replace the obstructed components (
possibly the continuous flow
capillary pipe
).