20
COMMANDS
ENGLISH
STANDARD Communication Protocol
W95
MIN/AVG/MAX RECORDING SETUP
Format:
W95=VV1VV2VV3VV4VV5VV6VV7VV8,M,TT,W,YYMMDDHHMMSS(1),YYMMDDHHMM
SS(2)<ETX> <BCC>
VV1VV2..VV8
selected variable (see section 4.4)
M
recording mode: 0=NONE; 1=FILL; 2=RING
TT
integration time to calculate the DMD: 01, 05, 10, 15, 30,
60 min or 61 in case of external (Synchronization with
DMD calculation)
W
start/stop: 0=NO; 1=YES
YYMMDDHHMMSS(1)
start recording date
YYMMDDHHMMSS(2)
stop recording date
Example:
W95=00000200300900A00B094096,1,60,0,040229125559,040229125559
W96
CLEAR RECORDINGS
Format:
W96=X
Available values:
0=clear min/avg/max recordings
1=clear daily counter recordings
2=clear all recordings
3=clear waveform capture recording (only 315/3080 ENH)
4=clear event LOG recordings (ENH)
Example:
W96=0
W98
DMD INTEGRATION TIME
Format:
W98=XX
Available values:
01,05,10,15,30,60 minutes or 61 in case of external (Sync. with
DMD calculation)
Example:
W98=01
W9B
DISPLAY BACKLIGHT ON TIME
Format:
W9B=XXX
Available values:
0...999
Example:
W9B=001
W9C MEASUREMENT
SYNCHRONIZATION
Format:
W9C=X,YYYY
X
synchro mode: 0=internal (fi xed); 1=external (auto)
YYYY
fi xed measurement synchronization: 0500 (050.0 Hz)
Example:
W9C=0,0500
W9E
WAVEFORM CAPTURE SETUP (ENH)
Format:
W9E=XXX,Y,Z,TT
XXX
number of periods: 1..200
Y
samples/period: 0=8 samples/period; 1=16 samples/period; 2=32 sam-
ples/period; 3=64 samples/period; 4=128 samples/period
Z
bit resolution: 0=8 bit resolution; 1=10 bit resolution
TT
trigger type: 00=manual; 11=SP1...18=SP8; 21=DO1...26=DO6;
31=DI1...34=DI4
WEF
START WAVEFORM CAPTURE (ENH)
Command Description
UBN310
UBN315