background image

 

14

The supply pressure is too high

The flow rate is too high

Blockages or deposits

are present

The pump is malfunctioning

Little hot water is produced

Fit a pressure limiter

Fit a flow reducer

Check and clean as necessary

Check the pump

Troubleshooting

The water temperature is low in 

the heat generator or solar heating 

system

The storage cylinder thermostat is 

set badly

The pump is malfunctioning

There is lime scale or sludge in 

the cylinder

Water temperature is low

Check the setting and condition 

of the thermostat

Check the setting and condition 

of the thermostat

Check the pump

Check and clean as necessary

There is air in the primary circuit

Bleed the circuit

The water temperature in the heat 

generator or solar heating

system is low

The filling pump is malfunctioning

There is air in the circuit

Replenishment times are too 

long

Check the setting of the thermo-

stat

Check the pump

Bleed the circuit

CAUSE

CORRECTIVE ACTION

PROBLEM

Summary of Contents for STOR 2000

Page 1: ...Installation Manual Solar Solar Storage STOR STOR M Installation Manual EN...

Page 2: ...2...

Page 3: ...ned to keep your storage tank efficient and cheap to run Technical Assistance Centres also stock any original spare parts that might be required This instruction manual contains important instructions...

Page 4: ...allation in older systems and systems requiring modernisation 11 Fitting the insulation 12 Preparing for initial start up 13 TECHNICAL ASSISTANCE Maintenance page 13 Cleaning and removing internal com...

Page 5: ...another user or to another installation If you lose this manual order a repla cement immediately Keep the product purchase documents to be presented to the BERETTA autho rised Technical Assistance Ce...

Page 6: ...heat exchanger to be added only for models where provided Storage tanks can be connected to a special solar con troller and can be integrated in solar heating systems in which Riello boilers or water...

Page 7: ...8 Coil STOR 300 M 500 M 1000 M 1500 M models STOR 2000 3000 5000 models 1 Soft polyurethane insulation 100 mm 2 Vent flow connection 1 1 4F 3 Flow return connection 1 1 2F 4 Probes sockets 8 mm 7 Tank...

Page 8: ...sulation 790 1000 1100 1250 1600 mm Height with insulation 1635 1775 2190 2165 2480 2720 2870 mm Height without insulation 2115 2090 2405 2645 2795 mm Insulation thickness 100 mm Flange diameter exter...

Page 9: ...O mbar PORTATA m3 h H H STOR 300 M 500 M 1000 M 1500 M models STOR 2000 3000 5000 models Dimensions and weight PRESSURE DROP mbar FLOW RATE m3 h DESCRIPTION STOR 300 M STOR 500 M STOR 1000 M STOR 1500...

Page 10: ...caps The counter flange comes ready bolted to the tank s flange and fitted with a seal The second package contains another plastic bag with the elegantly finished polyurethane insulation connec tion s...

Page 11: ...dren since it can become a potential hazard STOR solar storage tanks can be installed in any room where there is no specific requirement for an electrical protection rating higher than IP X0D bThe roo...

Page 12: ...nside of the insulation Secure the insulation in place with the zips 2 at the edges of the two sections Perforate the insulation at the fittings and fit the insula tion sleeves 3 Fit the flange cover...

Page 13: ...boi ler OFF at the main switch and at the control panel Close the shut off cocks for the heating water circuit Drain the storage tank or its secondary circuit if a pri mary circuit is connected EXTER...

Page 14: ...ly The pump is malfunctioning There is lime scale or sludge in the cylinder Water temperature is low Check the setting and condition of the thermostat Check the setting and condition of the thermostat...

Page 15: ...a T of 8 10 C There is lime scale or sludge in the tank Check and clean as necessary The flow rate is too high Reduce pump speed and turn the flow rate adjustment screw on the valve group to set a flo...

Page 16: ...to 23 A 23900 Lecco LC www berettaboilers com The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are theref...

Reviews: