29
METEO GREEN HE R.S.I.
CH1 = first CH circuit / CH2 = second CH circuit
Parameter with password 53
PAR.
MEANING
UNIT
MIN
MAX
STEP
DEFAULT
1
Gas type - don’t change
--
1 = G20 - LPG
1
1
2
Boiler power - not used - don’t change
--
26-30-34
26
3
Kind of building
min
5
20
1
5
10
Domestic hot water type
--
0= OFF
1= Instantaneous
(COMBO)
2= Minitank
3= System
storage tank with
thermostat (SOLO)
4= System
storage tank with NTC
sensor (SOLO)
5= Not used
1
1
(COMBO)
11
Maximum set point for DHW (Instantaneous)
°C
40
60
1
60
12
Maximum set point for DHW (storage tank)
°C
40
80
1
60
13
Maximum flow temperature for storage tank
°C
50
85
1
80
14
Detection hysteresis ON for storage tank
°C
0
10
1
5
20
CH type
--
0= OFF
1= ON
2= unused
3= external pump or
CONNECT AP
4= unused
5= unused
6= 2nd circuit
is connected or
CONNECT AT/BT
1
1
21
Maximum flow temperature CH1
°C
45
80
1
80
22
Minimum flow temperature CH1
°C
20
39
1
20
23
Maximum output CH (fan speed)
The value is shown on the display is rpm/100 (e.g.: 3700/100 = 37)
CH1 = 1st CH circuit / CH2 = 2nd CH circuit
rpm
36 (3600)
25 kW
G20 = 60
G31 = 60
35 kW
G20 = 60
G31 = 59
1
MAX
24
Minimum output CH (fan speed)
The value is shown on the display is rpm/100 (e.g.: 3700/100 = 37)
CH1 = 1st CH circuit / CH2 = 2nd CH circuit
rpm
25 kW
G20 = 12
G31 = 19
35 kW
G20 = 12
G31 = 19
36 (3600)
1
MIN
25
CH Hysteresis OFF
°C
2
10
1
6
26
CH Hysteresis ON
°C
2
10
1
6
28
CH timer: force burner (75%)
min
0
20
1
15
29
CH timer: blocking time
min
0
20
1
5
(continued)