background image

6

INSTALLATION

7  UNPACKING THE PRODUCT

B

 

IDRA DS N

 solar heaters are supplied in a single 

package on a wooden pallet.

The insulation and the lining components of the models 750 

and 1000 are supplied separately from the structural work 

and are to be assembled upon receiving the product as 

described in the paragraph "Assembly of the insulation and 

the lining (models 750 - 1000)". For these models the mag-

nesium anode is supplied in a cardboard box.

The following items are delivered in a plastic bag inside the 

packaging:

-  Instruction manual

-  Bar code label

-  Hydraulic test certificate

-  Energy label (to be applied to device upon installa-

tion)

-  No. 4 adjustable feet to be mounted during installa-

tion (for models 750 - 1000 only).

The instruction manual is an integral part of the so-

lar storage cylinder. Once located, read it thoroughly 

and keep it safe.

For handling operations, thoroughly follow the in-

structions on device package label.

8  ASSEMBLY OF THE INSULATION 

AND THE LINING (MODELS 750 - 

1000)

The assembly of the insulation and lining components must 

be performed at the site of installation to facilitate passage 

through any doors and/or entries to the room.

4

5

2

1

7

3

3

1

6

1

3

L

3

L

Proceed as follows:

-  Fit the magnesium anode (6) with its seal in the sleeve 

and fix it in place

-  Assemble the insulating covers (1) around the body of 

the heater, making sure that the engagement points 

on the edges are positioned correctly. The edges are 

not required to be closed completely

-  Place the front protection plate (3) correctly on the 

attachments

-  Place the washers on the attachments and the pro-

tection for the inspection flange (4)

-  Place the rear protection plate by closing the inter-

locking  flaps  (L)  without  closing  completely  (leave 

one tooth open)

-  Apply the upper insulation (2) and the upper cover 

(5) (in order to insert the cover, exert a light and ho-

mogeneous pressure)

-  Close  the  interlocking  flaps  (L)  completely,  which 

were previously left with an open tooth

-  Fit the cover of the inspection flange using the two 

self-tapping screws (7) provided

-  Apply the technical data plate and serial number 

plate.

If disassembling is required, proceed in reverse order.

Wear  suitable  personal  protective  equipment  and 

use suitable safety devices.

9  PLACE OF INSTALLATION

B

 

IDRA DS N

 solar heaters can be installed in all rooms 

not requiring a level of electrical protection of the device 

greater than IP X0D. 

≥ 0,3 m

≥ 0,3 m

≥ 0,3 m

≥ 0,6 m

≥ 0,7 m

NOTE:

 the above-indicated dimensions are recommended 

for a correct maintenance and access to the device.

10  INSTALLATION IN OLDER 

SYSTEMS AND SYSTEMS 

REQUIRING MODERNISATION

When installing 

B

 

IDRA DS N

 storage cylinders in old 

systems or systems requiring modernisation, always per-

form the following checks.

-  Make  sure  that  the  system  is  fitted  with  safety  and 

control devices in accordance with applicable legis-

lation and standards

-  Make sure that the central heating circuit has been 

flushed out to remove all sludge and lime scale, and 

has been vented and seal tested

-  Make sure that a suitable water treatment system is 

installed if the quality of the supply/recirculation water 

so demands (refer to the reference values listed in 

the table alongside).

11  WATER QUALITY 

REQUIREMENTS

REFERENCE VALUES

pH

6-8

Electrical conductivity

less than 200 μS/cm (25°C)

Chlorine ions

less than 50 ppm

Sulphuric acid ions

less than 50 ppm

Total iron

less than 0.3 ppm

Alkalinity M

less than 50 ppm

Total hardness

less than 35°F

Sulphur ions

none

Ammonia ions

none

Silicon ions

less than 30 ppm

The values above ensure proper operation of the system. 

Refer to the limit values specified in the current standards 

and regulations on the installation site.

Installation

Summary of Contents for IDRA DS 200 N

Page 1: ...Installation and Operation Manual IDRA DS 200 300 430 550 N IDRA DS 750 1000 N Solar solar storage cylinder IDRA DS N Installation and Operation Manual EN...

Page 2: ...eaks from the storage cylinder turn off the wa ter supply and contact B s Technical Assistance Centre or a qualified heating engineer immediately b If the product is not going to be used for an extend...

Page 3: ...ange is provided for easy cleaning and mainte nance of the anti corrosion magnesium anode 4 IDENTIFICATION The B IDRA DS N solar heaters can be identified by Data plate This lists the technical specif...

Page 4: ...cording to UNI 11300 1 38 1 53 1 67 1 89 2 13 2 33 W K Energy class B B B B B B PERFORMANCE RELATING TO INTEGRATION COIL Upper coil continuous efficiency ACS 10 45 C Vbu reference volume Upper coil de...

Page 5: ...heater pre heated to the indicated temperature considering an increase of the domestic water temperature of 30 C between inlet and outlet according to EN 12897 Temperature of accumulation tank lower...

Page 6: ...h open Apply the upper insulation 2 and the upper cover 5 in order to insert the cover exert a light and ho mogeneous pressure Close the interlocking flaps L completely which were previously left with...

Page 7: ...348 289 289 mm C 403 393 427 443 428 421 mm D 598 693 684 788 799 834 mm E 738 903 824 1088 969 1006 mm F 878 1113 964 1328 1144 1337 mm G 953 1233 1064 1428 1234 1426 mm H 1029 1323 1174 1538 1321 15...

Page 8: ...uit are all open Switch the electricity supply ON at the mains power switch and at control panel switch if fitted 15 TEMPORARY SHUTDOWN To reduce to the environmental impact and save energy in case of...