4  PLACE OF INSTALLATION

B

 

IDRA BV

 storage cylinders can be installed in any 

room where there is no specific requirement for an electri-

cal protection rating higher than IP X0D.

≥ 0,6 m

≥ 0,4 m

≥ 0,3 m

≥ 0,4 m

≥ 0,8 m

 

b

Respect the minimum specified installation distances to 

ensure correct installation and access for maintenance.

Adjust the feet to ensure that the storage cylinder is per-

fectly level.

17

5  INSTALLATION IN OLDER 

SYSTEMS AND SYSTEMS 

REQUIRING MODERNISATION

When installing 

B

 

IDRA BV

 storage cylinders in old sys-

tems or systems requiring modernisation, always perform 

the following checks.

 - Make sure that the system is fitted with safety and 

control devices in accordance with applicable legis-

lation and standards

 - Make sure that the central heating circuit has been 

flushed out to remove all sludge and lime scale, and 

has been vented and seal tested

 - Make sure that a suitable water treatment system is 

installed if the quality of the supply/recirculation water 

so demands. (Refer to the reference values listed in 

the table alongside.)

REFERENCE VALUES

pH

6-8

Electrical conductivity

less than 200 μS/cm (25°C)

Chlorine ions

less than 50 ppm

Sulphuric acid ions

less than 50 ppm

Total iron

less than 0.3 ppm

Alkalinity M

less than 50 ppm

Total hardness

less than 35°F

Sulphur ions

none

Ammonia ions

none

Silicon ions

less than 30 ppm

6  MAINTENANCE

Perform the following operations before beginning any 

maintenance:

 - Switch the electricity supply to the storage cylinder’s 

valve group and to any associated boiler OFF at the 

main switch and at the control panel

 - Close the shut-off cocks for the domestic hot water 

circuit

 - Drain the storage cylinder’s DHW (secondary) water 

circuit.

7  CLEANING AND REMOVING 

INTERNAL COMPONENTS

EXTERNAL CLEANING

Clean the outside of the storage cylinder with a soft cloth 

damped in soapy water.

 

a

Do not use abrasive products, petrol or triethylene.

INTERNAL CLEANING
Removing and checking the magnesium anode

 - Remove the cover (1) (removing the screws first from 

models 800 and 1000), and remove the insulation (2). 

Use a suitable wrench to unscrew the anode holder (3)

 - Check the magnesium anode for wear and replace it 

if necessary.

1

2

3

MODELS IDRA BV 800 - 1000

Removing and checking the second magnesium anode

 - Remove the plug (5) and use a suitable wrench to 

unscrew the anode holder (6).

 - Check the magnesium anode for wear and replace it 

if necessary.

5

6

On completion of cleaning, follow the above steps in the 

reverse order to refit all removed parts.

NOTE: Tighten the anode plug to a torque of 25-30 Nm.

8  RECYCLING AND DISPOSAL

At the end of its useful working life, do not abandon the 

storage cylinder in the environment, but dispose of it 

through the proper channels in accordance with applica-

ble legislation.