background image

17

 

ENGLISH

 

 

 

MAIN

 

START END

 

SELECT 

A DAY

 

 

THURSDAY

 

 
 
 
 
 

ZONE  SCHEDULE

 

07:30   08:30

 

11:30   13:30

 

18:00   22:30

 

 

 

INSTALLATION 

PARAMETERS 

THERMOREGULATION 

RANGE RATED 

CALIBRATION

 

 

-  Using the 

“up” 

and 

“down” 

keys select  TIME SCHEDULE confirming 

the selection

 

 

MENU

 

 

SETTINGS

 

 
 
 
 

TIME SCHEDULE

 

SELECT OPTION

 

 

From this menu it is possible to access the display and adjustment of the 

programme timing for the heating functions of the zone. For each day   of 

the week it is possible to set up to 4 bands, with a start time and end time. 

 

Note: 

for more details for the use of the programme timing see the USER 

MANUAL section.

 

 

MON 

SCHEDULE

 

18/11/2013 

12:17

 

 
 
 
 

MAIN

 

SELECT THE ZONE

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

5.2.4  Setting up thermoregulation

 

(Weather compensation)

 

Thermoregulation  only  works  with  an  outdoor  temperature  sensor  is 

connected  and  is  active  only  for  the  HEATING  function;  -  connect  the 

outdoor  temperature  sensor  to  the  specific  connections  on  the  boiler 

terminal board.

 

This enables use of the THERMOREGULATION function.

 

The temperature measured by the outdoor temperature sensor is displayed 

on screen in the top right, alternating with the display of the time. When 

thermoregulation is enabled the algorithm for automatically calculating the 

outlet set point depends on the type of heat request.

 

In any case, the thermoregulation algorithm will not directly use the outdoor 

temperature,  but  rather  a  calculated  outdoor  temperature  that  takes  into 

account  the  building’s  insulation:  in  well  insulated  buildings,  the  outdoor 

temperature  variations  will  have  less  impact  than  those  that  are  poorly 

insulated. 

 Enabling THERMOREGULATION occurs in the following way:

 

-  Access the technical parameters as explained in section “4.1 Access to 

the technical parameters”

 

-  Select THERMOREGULATION with the 

“up” 

and 

“down” 

keys, 

confirming the selection.

 

 

TECHNICAL

 

Then 

Using the control it is possible to set values of the following parameters:

 

BUILDING TYPE

 

This is indicative of the frequency  with  which the value of the calculated 

outdoor temperature for thermoregulation is updated, a low value for this 

will be used for buildings with little insulation.

 

Setting range: 

[5min - 20min]

 

Factory default: 

[5min]

 

REACTIVITY EXT SENSOR

 

This  is  an  indication  of the  speed  with  which  variations  of  the measured 

outdoor  temperature  affect  the  calculated  outdoor  temperature  value  for 

thermoregulation, low values indicate high speeds.

 

Setting range: 

[0 - 255]

 

Factory default: 

[20] 

 

To change the value of the above parameters proceed as described 

 

-  Access technical parameters as explained in the section “4.1 Access to 

the technical parameters”

 

-  In  sequence  select  THERMOREGULATION  and  TYPE  OF  BUILDING 

with the 

“up” 

and 

“down” 

keys, set & confirm the selection

 

 

Note: 

The  value  of  the  calculated  outdoor  temperature  used  by  the 

thermoregulation  algorithm  is  displayed  in  the  INFO  menu  under  TEXT 

FOR THERMOREG.

 

HEAT REQUEST FROM THERMOSTAT or POR (Programmable Timer) 

In  this case the  outlet set  point  depends  on  the  outdoor  temperature  for 

obtaining a reference ambient temperature of 20°C. There are 2 parameters 

that compete to calculate the output set point:

 

-  Slope of the compensation curve  (KT)

 

-  Offset on the reference ambient temperature.

 

SELECTING THE COMPENSATION CURVE- fig. 17

 

The compensation curve for heating maintains a theoretical temperature of 

20°C indoors, when the outdoor temperature is b20°C and -20°C. 

The  choice  of  the  curve  depends  on  the  minimum  outdoor  temperature 

envisaged (and therefore on the geographical location), and on the delivery 

temperature envisaged (and therefore on the type of system). It is carefully 

calculated by the installer on the basis of the following  formula:

 

KT = T. outlet envisaged – T shift

 

 

20- min. design external T

 

T shift =   30°C standard system

 

    25°C floor installations

 

If the calculation produces an intermediate value between two curves, you 

are advised to choose the compensation curve nearest the value obtained. 

Example: if the value obtained from the calculation is 1.3, this is between 

curve 1 and curve 1.5. Choose the nearest curve, i.e.  1.5.

 

The settable KT values are as follows

:

 

Standard system: 1.0-3.0

 

Floor system 0.2-0.8.

 

Using the screen it is possible to set the selected thermoregulation curve:

 

-  Access technical parameters as explained in the section “4.1 Access to 

technical parameters”

 

-  In sequence select THERMOREGULATION and then CLIMATIC CURVES

 

-  Select the desired heating zone with the 

“up” 

and 

“down” 

keys, 

confirming the selection

 

-  Set the desired climatic curve with the 

“up” 

and 

“down” 

keys, confirming 

the selection.

 

 

OFFSET ON THE REFERENCE AMBIENT TEMPERATURE - fig. 17

 

In any event, user action can indirectly modify the value of the HEATING 

set  point  inserting  an  offset  on  the  reference  temperature  that  can  vary 

within the range -5-+5 (offset 0 = 20°C). 

 

NIGHT COMPENSATION - fig. 17

 

Whenever a programmable timer is connected to the ROOM THERMOSTAT 

input, from the TECHNICAL\THERMOREGULATION\CLIMATIC CURVES\ 

MAIN the NIGHT COMPENSATION function can be enabled. 

 

In this case, when the  CONTACT is CLOSED, the heat request is made  

by  the  flow  sensor,  on  the  basis of  the  outdoor  temperature,  to  obtain  a 

nominal ambient temperature on DAY level  (20°C). 
Opening of the contact does not produce a switch-off, but a reduction 

(parallel translation) of the climatic curve on NIGHT level (16°C). 
 

in this case, the user can indirectly modify the value of the HEATING set 

point  inserting  once  again  an  offset  on  the  reference  DAY  temperature 

(20°C) rather than NIGHT (16°C) that can vary within the range [-5 - +5]. 

 

 

 

 

 

 

 

5.3 

First commissioning ; See Over 

 

 

 

 

INSTALLER

 

 

Summary of Contents for EXCLUSIVE 25C

Page 1: ...Please remember to service this appliance annually RO MANUAL DE INSTALARE SI UTILIZARE EXCLUSIVE C Installation and usermanual INSTALLER AND USER MANUAL NZ Gas adaptive condensing boiler...

Page 2: ...nd the prohibition of actions other than by a qualified engineer The manufacturer is not Liable for any failure to observe the requirements set out in this manual or relevant New Zealand code Some pro...

Page 3: ...e heating and domestic hot water system Drain if there is a risk of freezing Boiler maintenance must be carried out at least once a year servicing m ust be carried out by a suitably qualified competen...

Page 4: ...rrent NZ installation standards By a certifying Gas fitter Ensure the supply pipework supports the delivery of the relevant Gas being used and is correctly sized If the appliance is to use LPG attach...

Page 5: ...pes 60 100 mm Position the bend so that the 60 pipe goes fully into the flue gas turret of the boiler Once positioned make sure that the 4 notches A on the flangeconnect to the groove B on the 100 of...

Page 6: ...of a button A a two colored red green LED B and four yellow LEDs C arranged in a row The user interface allows the operating performance to be viewed operating status alarm status it also allows the c...

Page 7: ...the LEDs B and C indicate for 2 seconds the last setting carried out If the button A is not pressed for more than 2 seconds the user interfaces switches to the Operating status display The availablese...

Page 8: ...e information might not be available on the REC10 depending on the access level the status of the machine or the system configuration LED Light signal indicating the operating status of the boiler Can...

Page 9: ...RE PROBE REC10 MASTER REC10 SLAVE INSTALLER 1 6 INSTALLER Only zones with ACTUATION BE16 DIRECT ZONE DIRECT ZONE MIXING ZONE INSTALLER Only zones with ACTUATION BE16 HIGH TEMP HIGH TEMP LOW TEMP INSTA...

Page 10: ...E FUNC ACTIVATE FUNCTION INSTALLER 0 0 1 SERVICE 6sec 1sec 255sec SERVICE If CH DELAY POST DHW 1 1 0 1 SERVICE 1 0 1 SERVICE Only if PRESS TRANSDUCER 1 0 6 0 4 1 SERVICE Only if LOAD ENABLE 1 0 0 1 IN...

Page 11: ...ALLER Current speed MIN MAX INSTALLER WEEKLY FUNCTION F NOT ACTIVE DAILY FUNCTION WEEKLY FUNCTION INSTALLER ENABLE FUN ENABLE FUN DISABLE FUN SERVICE SERVICE SERVICE INSTALLER Only if VENT CYLCE in pr...

Page 12: ...TALLER Only if heat pump not configured INSTALLER INSTALLER Only if heat pump configured USE BUS USE BUS USE FREE CONTACTS SERVICE DEACTIVATE FUNCTION FUNCTION ACTIVE DEACTIVATE FUNCTION INSTALLER DHW...

Page 13: ...word menu about 5 sec FRI MENU 18 11 2013 12 17 SETTINGS SELECT OPTION Using the keys and select the value of the password to access the INSTALLER or SERVICE authorisation level depending on 5 5 1 sel...

Page 14: ...es and air suction pipes are installed correctly that spacing conditions for regular maintenance are guaranteed if the boiler is placed inside or between items of furniture The Gas system is sound Tha...

Page 15: ...n keys confirming the selection DOMESTIC HOT WATER THERMOSTAT This parameter allows you to set the type of DOMESTIC HOT WATER THERMOSTAT The factory setting for this parameter is RELATED i e for domes...

Page 16: ...equest is generated by the REC10 MASTER in this case the REC10 assumes the function of BOILER INTERFACE TYPE OF ZONE This parameter allows you to specify the type of zone to be heated it is possible t...

Page 17: ...confirm the selection Note The value of the calculated outdoor temperature used by the thermoregulation algorithm is displayed in the INFO menu under TEXT FOR THERMOREG HEAT REQUEST FROM THERMOSTAT or...

Page 18: ...trument panel and pressing the combustion analysis button SW1 or else from the TECHNICAL menu of the control in the following way access the technical parameters as explained in section 4 1 Access to...

Page 19: ...n Note when there is an outdoor temperature sensor connected it is still possible to have the boiler operate at a fixed point setting the values of MIN SP HEAT and MAX SP HEAT at the desired HEATING s...

Page 20: ...natural Gas G20 To convert the boiler to LPG G31 proceed as follows Access technical parameters as explained in section 4 1 Access to technical parameters Set the password for SERVICE Select COMBUSTI...

Page 21: ...e the analyser probe and close the combustion analysis sockets with appropriate caps and screw If the value displayed is different DO NOT MAKE ANY ADJUSTMENT OF THE GAS VALVE please contact Heat IQ NZ...

Page 22: ...16 18 20 22 24 26 28 30 Heat output kW CO s a curve Qnheating 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Heat output kW EXCLUSIVE 35C HTG c...

Page 23: ...ing message appears on the foot of the page SEMI AUTOMATIC FILLING IN PROGRESS the green and red LEDs flash while the pressure shown on the display should start to rise When the loading is finished th...

Page 24: ...097 is displayed and is followed by post purging for 45 seconds at the fan s maximum speed It is not possible to release the alarm before the end of the post purging unless the boiler s power supply i...

Page 25: ...the systems Heating anti freeze this function is activated if the temperature measured by the flow sensor drops below 5 C A heat request is generated in this phase with the ignition of the burner at...

Page 26: ...toring the factory setting of the parameters SELECT THE TYPE OF CONFIGURATION FROM AKM NEW With NEW configuration selected proceed as follows select REC10 functionality Select ON BOARD The REC10 is us...

Page 27: ...n the saved configuration data on the AKM01 PCB board and those saved in the REC10 therefore when replacing theAKM01 electronic board it can happen that the system detects an inconsistency between the...

Page 28: ...d minimum output Checking the position of the ignition flame detection glow plug Check the gas failure safety device Check adjust the dosage of inhibitor in the attached system Remove and clean the sy...

Page 29: ...will be flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the top of the domestic ho...

Page 30: ...ssing the ok and back keys it will be possible to select the other zones in this sequence PLANT MAIN ZONE ZONE 1 if optioned ZONE 2 if optioned The TIME AND DATE LANGUAGE and BACKLIGHT settings are in...

Page 31: ...ction by pressing ok Press back to return to the SET screen without making any selection SET HEATING 78 0 C When an outdoor temperature sensor is installed the outlet temperature is automatically sele...

Page 32: ...wn keys to change the desired values Once the sequence has finished by pressing ok the settings will be saved and the display will return to the initial screen By pressing back at any time the system...

Page 33: ...eys Press the up and down keys to select the desired time band and press ok to confirm the selection SELECT OPTION Press the up and down keys to increase or decrease the start time by 30 minutes and p...

Page 34: ...and press ok to confirm the selection MAIN SELECT DAYS ON WHICH YOU WANT TO COPY SCHEDULE OF THURSDAY MON TUE WED THU FRI SAT SUN CONFIRM USE THE ARROWS TO MODIFY The day will be highlighted and othe...

Page 35: ...ture probe flashing 0 5 sec on 0 5 off flashing 0 5 sec on 0 5 off transitional definitive E091 clean primary heat exchanger flashing 0 5 sec on 0 5 off flashing 0 5 sec on 0 5 off transitional water...

Page 36: ...tly contact the installer or service engineer For fault E091 The boiler has an auto diagnostic system which based on the total number of hours in certain operating conditions can signal the need to cl...

Page 37: ...98 1 Useful efficiency Pn max Pn min 50 30 106 5 107 8 103 9 105 8 106 5 106 4 104 5 106 7 105 9 107 4 103 2 101 0 Useful efficiency Pn max 30 30 return 109 8 105 8 109 7 107 3 109 3 106 6 Efficiency...

Page 38: ...harge head of boiler without pipes Pa 199 199 190 Concentric flue gas outlet pipes Diameter mm 60 100 60 100 60 100 Maximum length m 10 10 8 Losses for a 45 90 bend m 1 3 1 6 1 3 1 6 1 3 1 6 Hole in w...

Page 39: ...m holes n 1 1 Diaphragm holes diameter mm 4 3 4 3 Heating maximum gas capacity Sm h 2 54 kg h 1 86 DHW maximum gas capacity Sm h 3 17 kg h 2 33 Heating minimum gas capacity Sm h 0 45 kg h 0 47 DHW min...

Page 40: ...erature means for condensing boilers 30 C for low temperature boilers 37 C and for other heaters 50 C return temperature at heater inlet INSTALLER SERVICE ENGINEER PLEASE NOTE USER Conditional Warrant...

Page 41: ...1 Fan 12 Mixer 13 Ignition transformer 14 Flue gas exhaust 15 Degassing unit pipe 16 Flue gas probe 17 Upper air vent valve 18 Limit thermostat 19 NTC delivery probe 20 Flame ignition electrode 21 Fla...

Page 42: ...16 1 2 3 4 X10 T L A C S M S R t t F L S S T P 3 1 D V Lv 3V S F t MOD 12 X9 1 10 X19 1 4 X13 1 1 2 3 4 5 X12 F rosa 2 1 1 2 3 4 5 1 X23 REC EXCLUSIVE L N POLARITY IS RECOMMENDED 2 41 X11 blu blu gial...

Page 43: ......

Page 44: ...onnections T P Pressure transducer A B Bus 485 MOD Modulator TA Room thermostat contact without voltage V Lv Fan control signal TBOL Not used 3V 3 way valve stepper servomotor EN Serial number plate D...

Page 45: ...ny installation conditions graph1 6 metre circulator as standard 600 550 500 450 400 350 300 250 200 150 100 50 0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Flow rate l h graph 2 7 metre cir...

Page 46: ...e F EN A condensate drain B water gas 9 R M G AC AF EN R heating return 3 4 M M heating delivery 3 4 M G gas connection 3 4 M AC hot water 1 2 M AF cold water 1 2 M 10 measured in mm 6 V 11 V1 6a dist...

Page 47: ...talled as standard 15 flange installed as standard 90 bend TWIN PIPE 80mm 90 bend COAXIAL PIPE 80 125mm A A C A B C C A C B lange installed as standard lange installed as standard EN 1 2 3 4 A B Bus 4...

Page 48: ...ting temperature set point jumper pos 1 not inserted T45 floor systems heating temperature set point jumper pos 1 inserted chimney for ducting 60 mm or 50 mm A 90 bends 80 mm C B 4 5m 80 mm 4 5m 80 mm...

Page 49: ...55 160 165 170 175 air suction pipe length m EXCLUSIVE 30C 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 a...

Page 50: ...ta reserves the right to modify the characteristics and information contained in this manual at any time andwithoutpriornotice Consumersstatutoryrightsarenotaffected Cod 20125304 05 17 Ed 1 Thank you...

Reviews: