31
Bentone
8.6
Oil pump replacement
1.
Disconnect the main power and shut off the fuel supply.
2.
Disconnect the oil hoses from the oil pump.
3.
Service position 3 can be used.
4.
Remove the solenoid cable from the pump.
5.
Remove the connecting pipe (G) from the pump.
6.
Undo the screws (F) and pull out the oil pump.
7.
Install the oil pump in the burner. Tighten the screws and attach the
connecting pipe (G). (It is important that the splines engage the pump
coupling correctly.)
8.
Connect the oil hoses. (For conversions from one- and two-pipe
systems refer to the Pump instructions.)
9.
Switch on the main power and open the fuel supply.
10. Start burner, purge pump, adjust to correct pressure and check/
adjust combustion.
!
When servicing/replacing components that affect combustion,
flue gas analysis and soot test must be carried out following installation.
F
G