background image

General rules

The installation of an oil burner 
should be carried out in accordance 
with local regulations. The installer 
of the burner must therefore be 
aware of all regulations relating to 
oil and combustion.
Only oil suitable for the burner should 
be used and then in combination with 

a suitable oil ilter before the oil pump 

of the burner.
If the burner is replacing an existing 

burner make sure that the oil ilter is 

replaced or cleaned. The installation 
must only be undertaken by experienced 
personnel. Care should be taken by 
the installer to ensure that no electrical 

cables or fuel/gas pipes are trapped or 

damaged during installation or service/

maintenance.

Installation instructions

General installation instructions 
ac company the burner and should be 
left in a prominent place adjacent to 
the burner.

Adjustment of burner

The burner is from the factory pre-set 
to an average value that must then be 
adjusted to the boiler in question.
All burner adjustments must be 
made in accordance with boiler 
manufacturers instructions. These 
must include the checking of flue 
gas temperatures, average water 
temperature and CO

2

 or O

2

 

concentration.
To adjust the combustion device, 
start by increasing the air volume 

somewhat. When the burner starts it 

is  burning with excess air and smoke 
number 0. Reduce the air volume until 
soot occurs and increase again to 
reach a combustion free of soot. 
By this procedure an optimum 
adjust ment is obtained. If larger 
nozzles are used the preadjustment of 
the air volume must be increased.
 

Condensation in chimney

A modern burner works with less 
excess air and often also with smaller 
nozzles than older models. This 

increases the eficiency but also the 

risk of condensation in the chimney. 
The risk increases if the area of 
the chimney flue is too large. The 
temperature of the flue gases should 
exceed 60°C measured 0,5 metres 
from the chimney top.

Air adjustment

On all burners the air adjustment can 
be made with or without the cover 

itted. Final ine adjustment must be 

made with the cover on.

Maintenance

The boiler/burner should be examined 

regularly for any signs of malfunction 
or oil leakage.

Fastening of the burner to the 

boiler (lange)

GENERAL INSTRUCTIONS

Measures to raise the temperature:
Insulate the chimney in cold attics
Install a tube in the chimney
Install a draught regulator (dilutes the 

lue gases during operation and dries 

them up during standstill)

Increase the oil quantity

Raise  the  lue  gas  temperature  by 

removing turbulators, if any, in the 
boiler.

Instructions for use

The end user of the burner should be 
instructed about the operation and 
safety features of the burner.
He should also be made aware of 
the  importance of the area around 

the  boiler/burner  being  kept  free  of 

combustible material.

Pump adjustment

See separate description.

Adjustment of burner

To obtain a correct adjustment a 

lue gas analysis and a temperature 

measurement must be carried out. 
Otherwise there is a risk that a bad 
adjustment may cause a formation of 

soot, bad eficiency or condensate in 

the chimney.

Air adjustment

171 305 17  07-01

Summary of Contents for B10E

Page 1: ...Providing sustainable energy solutions worldwide 178 013 03 2 2016 05 26 Installation and maintenance instruction B 10 E R...

Page 2: ......

Page 3: ...last tube 8 Ignition electrodes 9 Ignition cables 10 Ignition transformer 11 Electrical connection 12 Control box 13 Solenoid valve 14 Reset button 15 Pump 16 Motor 17 Indicating lamp preheater 18 Fan...

Page 4: ...nd nozzles recommended Flange A Flange B Flange C 89 5 21 10 5 130 150 89 5 26 130 150 12 89 5 12 130 150 12 The net caloriic value of 11 86 kWh kg for light oil has been used Burner tube Length of bu...

Page 5: ...btained If larger nozzlesareusedthepreadjustmentof the air volume must be increased Condensation in chimney A modern burner works with less excess air and often also with smaller nozzles than older mo...

Page 6: ...Retractthenozzleassemblyso farthattheignitioncablescanbe removed from the ignition electrodes 6 Remove the nozzle assembly 171 305 14 07 01 Service of burner head alt B 1 Slacken retaining screws 2 Re...

Page 7: ...olenoid valve X1 Plug in contact burner X2 Plug in contact boiler OIL BURNER CONTROL LOA21 LOA24 Wiring diagram If there is no plug in contact X2 on the boiler connect to the contact enclosed In case...

Page 8: ...urneroperationisinterruptedbymeansofthemainswitchorthe thermostat a new start takes place when the conditions in accordance with point 1 are fulilled The oil burner control cuts out A red lamp in the...

Page 9: ...ercial quality according to current standards On commissioning with an empty tube system the oil pump should not be run without oil for more than 5 min a condition is that the pump is being lubricated...

Page 10: ...cum stances the oil pressure falls below the set value andthevalveclosesagainstthe returnside R bymeansofthe diaphragm D andgoesintostarting position This can be remedied by Reducing the pump pressure...

Page 11: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Page 12: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Page 13: ...f magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocel...

Page 14: ...nnect a steel pipe 6 4 to the combustion chamber or the lue of the boiler Connect the rubber hose enclosed in the carton to the steel pipe and to the hose nipple marked on the pressure switch The pres...

Page 15: ...171 905 04 08 01 A1 Burner control S20 Pressure switch P1 Terminal strip B1 Ionisation electrode R1 Photoresistor 2 2...

Page 16: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...170 080 06 10 01...

Reviews: