16
Bentone
165 105 46
4.6 Mount the burner on the boiler
1.
Separate the burner body and the flange.
2.
Remove the brake disc from the oil pipe.
3.
Install the selected nozzle. (See Technical data)
4.
Install the brake disc on the oil pipe
5.
Remove the burner pipe from the flange.
6.
Install the flange with gasket on the boiler.
7.
Install the burner pipe on the flange. Make sure that the holes in the
front edge of the burner pipe are pointing down (not on all burner
pipes). This allows any drops of oil to run out.
8.
Insulate between the burner and boiler door to reduce radiated heat.
9.
Install the burner body on the flange.
10. Lock the burner body using with the nut/nuts.
11. Connect the oil pipes to the pump, refer to the chapter - servicing of
burners
12. Connect the burner electrically, refer to the chapter - servicing of
burners
A
A
A
A
4.7 Check oil line
seals
Once the burner has been installed
and commissioned, the seals of the
various coupling elements should be
checked (A).
When a leak is detected, it is usually
sufficient to tighten the coupling
element that is leaking.
!
If the burner tube must be installed from the inside of the boiler,
this means that the boiler must be opened or have a spectacle
flange that is designed so that it can be reconnected with the
burner tube mounted.