Basic settings should only be seen as setting values to get burner to start
and establish flame. Once the burner has started and established flame, it is
necessary to adjust the settings so that they are adapted to the installation
and the fuel used.
4.9 Example of Basic settings
B 30 A
Burner output:
154 kW
Estimated nozzle output:
154 / 11.86*
=
13.0 kg/h
(* Calorfic value Fuel oil
=
11.86 kWh/kg)
This provides the following nozzle according to the nozzle table, (see
Technical data).
Nozzle:
3.50 Gph
Pump pressure:
10.0 bar
Setting values for 154 kW according to basic setting diagram, (see Technical
data).
Air setting:
=
8.0
Insert setting:
=
2.0