Exception Code
Exception Condition
1
illegal function in request message
2
Illegal data address in request message
3
Illegal data range in request message
•
•
System Monitor
80175-01
16
PROTOCOL SPECIFICATIONS
MODBUS PROTOCOL EXCEPTION RESPONSES
Error codes will be returned in the response message when the interface receives a message with
an illegal
function,
address, or data range.
Example:
An unprotected read is attempted from address 36 which is an illegal address for a register
read request. The reply message returns the exception code 2.
The maximum number of valid register addresses is 36. First valid address is 0, last valid
address is 35.
Point (status) data addresses start at 0 also. The maximum number of valid point addresses
is 36 (3 status points for each of 12 monitors). The last valid status address is 35.
Data requests outside of these ranges will either result in an exception code 2 or exception
code 3 message response. Exception code 3 will occur if the starting address is valid but the
number of registers or points requested results in a data address outside the valid range.
Exception code 2 occurs if the starting register or point address is outside the valid address
range.
45
Summary of Contents for 3300/01 Series
Page 2: ...3300 01 SYSTEM MONITOR OPERATION MANUAL BENTLY re NEVADA PART NO 80175 01 ...
Page 5: ...System Monitor 80175 01 Blank Page iv ...
Page 7: ...System Monitor 8 0 1 7 5 0 1 Blank Page vi ...
Page 58: ... System Monitor 80175 01 18 SCHEMATICS AND DRAWINGS 51 ...
Page 59: ... 5 Z 5 s 0 0 3 T4 E a 1 p L SERIALINTERFACE SCHEMATIC SHEET 1 OF 4 ...
Page 62: ... T 7 1 0 1 0 z g i i IS P ig SERIAL INTERFACE SCHEMATIC SHEET 4 OF 4 ...
Page 64: ... I I ...
Page 67: ... SYSTEM MONITOR SCHEMATIC SHEET 3 OF 6 ...
Page 73: ...t ...