System Monitor
80175-01
14
CABLING
CABLE CONNECTION TO ALLEN BRADLEY
1771-KE OR 1785-KE COMMUNICATIONS MODULES
Both the 1771-KE and the 1785-KE are designed to be installed in an I/O chassis. A 1771-KE
provides an interface between a RS-232C communication link and an Allen Bradley Data Highway
Communication link. A 1785-KE provides an interface between a RS-232C communication link and
an Allen Bradley Data Highway Plus communication link.
771 • rIE: (111
1785 KE.
•
DAT?, I11131-1WA O R
DATA F I W1-1,0 Y ! J 5 . 1 .
41.11
-
II
r
!
!
RS- 1 3 7
!. 1 NI
A -
I
/ 0 C:i-iASSIS
AMUN I CA1 !OH',
Make the cable connection between the Allen Bradley module and the PIM using a cable part
number 85343. Connect the cable t o the HOST connector o n t h e PIM. T h e 85343 cable i s
available in lengths of 10, 25, 50 or 100 feet. When distances beyond 100 feet are required, a
common method used is to employ a pair of modems in the communications link. The connection
to the modem should be made with a standard 25-pin male/female computer cable.
Be sure to set the jumpers W4 through W13 prior to connecting link cables.
Note
Since Allen Bradley protocol is full duplex, only one 3300 rack may be connected per KE module.
26
•
Summary of Contents for 3300/01 Series
Page 2: ...3300 01 SYSTEM MONITOR OPERATION MANUAL BENTLY re NEVADA PART NO 80175 01 ...
Page 5: ...System Monitor 80175 01 Blank Page iv ...
Page 7: ...System Monitor 8 0 1 7 5 0 1 Blank Page vi ...
Page 58: ... System Monitor 80175 01 18 SCHEMATICS AND DRAWINGS 51 ...
Page 59: ... 5 Z 5 s 0 0 3 T4 E a 1 p L SERIALINTERFACE SCHEMATIC SHEET 1 OF 4 ...
Page 62: ... T 7 1 0 1 0 z g i i IS P ig SERIAL INTERFACE SCHEMATIC SHEET 4 OF 4 ...
Page 64: ... I I ...
Page 67: ... SYSTEM MONITOR SCHEMATIC SHEET 3 OF 6 ...
Page 73: ...t ...